Notice of Violation from Insp on 850701-0831
ML20140J547
Person / Time
Site: Fort Calhoun, 05000701 
Issue date: 10/18/1985
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML20140J520 List:
References
50-285-85-15-01, 50-285-85-15-1, NUDOCS 8510240334
Download: ML20140J547 (2)


Text

e

.

. 7 I

'

,

APPENDIX A NOTICE OF VIOLATION Omaha Public Power District Docket:

50-285 Fort Calhoun Station License:

DPR-40 During an NRC inspection conducted on July 1-August 31, 1985, violations of NRC requirements were identified.

The violations involved a failure to meet the licensing requirements for UF6 storage at the site and a failure to implement surveillance requirements required by Technical Specifications.

In accordance with the " General Statement of Policy and Procedure for NRC Enforcement Actions," 10 CFR Part 2, Appendix C (1985), the violations are listed below:

A.

Failure to Meet Licensing Requirements US NRC License SMC-1420, dated September 3, 1982, authorizes OPPD to store up to 630 tons of UF6 at the Fort Calhoun Station, subject to the conditions contained in the licensee's application dated August 27, 1981, and supplements dated February 26, 1982, and April 1, 1982.

In paragraph A-2 of the supplement dated February 26, 1982 (LIC-82-051),

in response to an NRC question, the licensee stated that the " proposed storage locations will be maintained free of combustible materials."

Contrary to the above, on July 17, 1985, the NRC inspector observed two cans of paint with " flammable" markings, two open paint buckets, and assorted paint trays, rollers, and brushes within the UF6 storage area.

This is a Severity level IV violation (Supplement VI.D 2) (285/8515-02).

B.

Failure to Implement Technical Specification Surveillance Requirements t

Amendment 87 to the Fort Calhoun Station Technical Specifications incorporated Item 29.a into Table 3-3 for the Toxic Gas Detectors which requires that " comparison of readings from redundant channels" be done on

{

a shift basis.

Surveillance Test ST-TGM-1, " Toxic Gas Monitors," was issued on June 18, 1985, to implement this requirement and Section F.1 requires that every shift the Operations Department " read, compare, and record readings on ppm gauge on each Toxic Gas Monitor.

Enter readings on Form FC-71."

Contrary to the above, on July 15, 1985, the NRC inspector reviewed Form FC-71 and determined that the licensee had failed to perform this routine surveillance test.

This is a Severity Level IV violation (Supplement I.D.3) (285/8515-03).

!

!

I

0

W s

,

,:

I-2-Pursuant to the provisions of 10 CFR 2.201, OPPD is hereby required to submit to this Office, within 30 days of the date of this letter transmitting this Notice, a written statement or explanation in reply, including for each violation:

(1) the reason for the violations if admitted, (2) the corrective steps which have been taken and the results achieved, (3) the corrective steps which will be taken to avoid further violations, and (4) the date when full compliance will be achieved. Where good cause is shown, consideration will be given to extending the response time.

Dated at Arlington, Texas this 18th day of October, 1985

,

-

-

-