GPU Nuclear, Inc.

(

Route 441 South NUCLEAR Post Office Box 4B0 April 21,1997 M;ddletown, PA 17057-0430 6710-97-2133

" """48" U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, DC 20555

Dear Sir:

Subject:

Three Mile Island hecles. Station, Unit 1, (TMI-1)

Operating License No. DPR-50 Docket No. 50-289 Technical Specification Change Request (TSCR) No. 263 in accordance with 10 CFR 50.4(b)(1), enclosed is TSCR No. 263. Also enclosed is the Certificate of Service for this request certifying service to the chief executives of the township and county in which the facility is located, as well as the designated official of the Commonwealth of Pennsylvania, Bureau of Radiation Protection.

The purpose of this TSCR is to request three (3) changes to the TMI-l Technical Specifications.

Technical Specification (TS) 3.3.1.2 which provides a Limiting Condition for Operation that requir 1040 ff of borated water in each Core Flood Tank, would be changed to 940 fl on the basis of revised analyses performed by Framatome Inc. for operations at higher power levels up to 2772 MWt. TS 4.5.2.1.b which specifies a surveillance acceptance criteria for the Emergency Core Cooling System (ECCS) high pressure injection (HPI) flow rate, currently at 500 gpm, would be lowered to 431 gpm, based upon the LOCA analyses performed by Framatome for operation at 2772 MWt. Lastly, the TS 3.3.1.1.f LCO which currently allows either local or remote manual operability ofdecay heat valves would be revised to delete the local manual valve operability option.

GPU Nuclear Inc. requests that the amendment authorizing this change become effective prior to the restart from the 12R refueling outage scheduled to begin on September 5,1997.

i Sincerely, I

y James. W. Lang n ach i

Vice President and Director, TMI Enclosures g

l)f cc:

Administrator Region I TMI Senior Resident inspector 1))]

TMl-1 Senior Project Manager u

9704250164 970421ADOCK05000289}3 l

l Bli li l P

pon $

UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION IN THE MATTER OF DOCKET NO. 50-289 GPU. NUCLEAR INC.

LICENSE NO. DPR-50 CERTIFICATE OF SERVICE This is to certify that a copy of Technical Specification Change Request No. 263 to Appendix A of the Operating License for Three Mile Island Nuclear Station Unit 1, has, on the date given below, been filed with executives of Londonderry Township, Dauphin County, Pennsylvania; Dauphin County, Pennsylvania; and the Pennsylvania Department of Environmental Resources, Bureau of Radiation Protection, by deposit in the United States mail, addressed as follows:

Mr. Darryl LeHew, Chairman Ms. Sally Klein, Chairman Board of Supervisors of Board of County Commissioners Londonderry Township of Dauphin County R. D. #1, Geyers Church Road Dauphin County Courthouse Middletown, PA 17057 Harrisburg, PA 17120 Director, Bureau of Radiation Protection PA Dept. of Environmental Resources Rachael Carson State Oflice Building P.O. Box 8469 Harrisburg, PA 17105-8469 Att: Mr. Stan Maingi GPU NUCLEAR INC.

BY:

AN hi1M i e Eresident and irector, TMI i

f

,, Rl, 9 7 DATE:

I t

METROPOLITAN EDISON COMPANY JERSEY CENTRAL POWER & LIGHT COMPANY AND PENNSYLVANI A ELECTRIC COMPANY THREE MILE ISLAND NUCLEAR STATION, UNIT 1 Operating License No. DPR-50 Docket No. 50-289 Technical Specification Change Request No. 263 This Technical Specification Change Request is submitted in support of Licensee's request to change Appendix A to Operating License No. DPR-50 for Three Mile Island Nuclear Station, Unit 1. As a part of this request, proposed replacement pages for Appendix A are also included.

GPU NUCLEAR INC.

I

(

BY:

DAM.tk AMAH JM ce President and ector, TMI l

Sworn and Subscrib to before me this//# day of s7

,1997.

Y i

[ Notary Public(

L Notaria! Sca!

Suzanne C. MNosh. Notary Public Londonderry Two, Dauphn County My Comrnicsion &piras Nov. 22.1999 f.iember, PennsyNan:a Associatan of Nounes t

(,