l i
)
5'-
APPENDIX A NOTICE Oc DEVIATION Long Island Lighting Company Docket No.
50-322 Shoreham Nuclear Power Station.
License No. CPPR-95 As a result of an inspection conducted on December 3-7, 1984, the following deviations from licensee commitments were identified:
A.
. The Fire Hazard Analysis Report (FHAR), Revision 1, dated June 1982 (an enclosure to your letter to NRC dated August 6, 1982), Section 1, Para-graph E.1.a., describes the licensee commitment to design the fire detector systems in the Reactor Building in accordance with NFPA 72D/E.
Contrary to the above, your design does not conform to NFPA 72D/E, in that the number of detectors per square foot of floor space has not been met; the maximum distance between individual-detectors is exceeded (120 feet instead of 30 feet); and the location of detectors relative to ceilings does not conform to NFPA 72'D/E.
p
. B.
The :FHAR, Revision 1, Section 1, Paragraph D.I.J., describes the licensee commitment to provide fire doors having a fire resistance rating at least equal to the required rating of the barriers in which the doors are located.
Contrary to the'above, the resistance rating of a significant number of fire doors in the plant is less than the rating of fire barriers in which they are located in that the fire doors have been degraded due to their modifications for security reasons.
C.
The FHAR, Revision 1, Section 1, Paragraph E.2.c., describes the licensee commitment to separate the diesel and electric fire pumps and their asso-ciated components by a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barrier.
Contrary'to the above, the cables from the ' diesel fire pwq) controller-and -
day tank pumps are routed through the same fire area as the electric fire pump, thereby not meeting the required 3. hour fire barrier separation.
t' D.
The 'fH/Ut, Revision 1,- Section -1, Paragraph D.I.J., describes the licensee's
. commitment to provide an adequately rated fire damper where a ventilation duct penetrates a fire wall.
Contrary to.the above, no fire damper is provided.in the ventilation duct
-penetrating the 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> fire wall between the HVAC and chiller rooms at.
. elevation 44 feet.
E.
The FHAR, Revision 1, Section 1, Paragraph E.5., describes the -licensee commitment to design the Carbon Dioxide Suppression Systems in accordance with NFPA 12.
B501100611 841221
~
PDR ADOCK 05000322 O
PDR w
r Appendix A 2
Contrary to the above, the Acceptance Test results for such systems in the i
Battery Rooms and Cable Tunnel indicate that the design objective was not achieved in that the carbon dioxide design density was not achieved at the highest test point.
F.
The FHAR, Revision 1, Section 1, Paragraph E.5., describes the licensee commitment to design the Carbon Dioxide Suppression systems in accordance with NFPA 12.
Contrary to the above, the design criteria for such system in the Computer Room is not met in that the fire detectors which actuate the system are located above the suspended ceiling and such location would prevent timely successful actuation o,f the system if a fire occurred.
G.
The FHAR, Revision 1, Section 1, Paragraph D.I.J., describes the licensee l
connitment to provide a minimum of 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire rating for ceiling / floor assemblies.
Contrary to the above, such protection was not maintained for the struc-tural steel which forms a part of the ceiling / floor assemblies in the charcoal filter. room and chiller room in that their fireproofing protection l
("pyrocrete" coating) was found damaged at elevation 63 feet.
L H.
Supplecent 1 to the Shoreham Safety Evaluation Report, Section 9.5.4, documents the licensee commitment to install self-contained 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> battery pack emergency lighting in all areas of the plant which could be manned to
[
bring the plant to a safe cold shutdown.
l l
Contrary to the above, such lighting in several such7 reas in the Reactor Building was not installed.
(see Inspection Report 50-322/84-46, Paragraph 8.b. for exact locations).
Long Island Lighting Company is hereby requested to submit to this office within fifteen days of the date of the letter which transmitted this Notice, a written statement or explanation in reply, including: (1) the corrective steps which have been taken and the results achieved; (2) corrective steps which will be taken to avoid further deviations; and (3) the date when full compliance will be achieved. Where good cause is-shown, consideration will be given to e'xtending this response time.
Under the authority of section 182 of the Atomic Energy Act, 42 U.S.C. 2232, this response shall be submitted under oath or affirmation.
l r
l L
!t
=
Construction 4
'50-322 MHB Technical Associates Dr. Peter A. Morris 1723 Hamilton Avenue, Suite K Administrative Judge San Jose, California 95125 Atomic Safety & Licensing Board U.S. Nuclear Regulatory Commission j
Stephen Latham, Esquire Washington, D.C.
20555 i~
John F. Shea, Esquire j
Twomey, Latham & Shea Post Dffica Box 398 Eleanor L. Frucci, Esquire 33 West.Second Street Attorney 4
Riverhead, New York 11901 Atomic Safety & Licensing Board PaneT U.S. Nuclear Regulatory Commission Jonathan D. Feinberg, Esquire Washington, D.C.
20555 New York State Department of Public Service
_ Leon Friedman, Esquire Three Empire State Plaza Costigan, Hyman and Hyman, P.C.
Albany, New York 12223 120 Mineola Boulevard i
Mineola, New York 11501 Ezra I. Bialik, Esquire Assistant Attorney General Alan S. Rosenthal, Esquire Environmental Protection Bureau Chairman, Atomic Safety &
1 New York State Department of Law 1censino A>oeal Panes 2 World Trade Center U..i. Nuclear leculatory Commissiotr
.New York, New York 10047 Washinaton, D.C.
20555 l
Herbert H. Brown, Esquire Gary J. Edles, Esquire Lawrence Coe Lamnpher, Esquire Atomic Safety & Licensing Appeal Kirkpatrick, Lockhart, Hill,
_ Panel J
Christopher & Phillips U.S. Nuclear Reaulatory Commission 1900 M Street, N.W.
Washinoton. D.C.
20555 Washington, D.C.
20036 Karla J. Letsche, Esquire Howard A. Wilbur. Esauire Kirkpatrick, Lockhart, Hill, Atmic Safety & Licensina Anneal Christopher & Phillips e
>anel
'1900 M Street, N.W.
U.S. Nuclear Reaulatory Commission Washington, D.C.
20036 Washington, D.C.
20555 Lawrence Brenner, Esq. Administrative Judge ltobert Abrams. Esauire Atomic Safety & Licensing Board
)eter Bienstock. Esautre U.S. Nuclear Regulatory Commission hoartment of Law Washington, D.C.
20555 State of New York Room 46-14 Dr. George A. Ferguson Two World Trade Center Administrative Judge New York, New York 10047 School of Engineering
/
Howard University 2300 - 6th Street N.W.
Washington, D.C.
20059 p
Construction 4
50-322 Edward M. Barrett, Esq.
Department of Public Service General Counsel Director, Power Division Long Island Lighting ' Company Three Empire State Plaza 250 Old Country Road Albany, New York..2223 Mineola, New York 11501 SHOREHAM HEARING SERVICE LIST ADDRESSES (just make labels the individuals are not listed in the cc's)
Gerald C. Crotty, Esquire Ben Wiles, Esquire Counsel to t.he Governor Executive Chamber State Capitol Albany, New York 12224 Mr. Jay Dunkleberger Fabian G. Palomino, Esquire New York State. Energy Office Suffolk' County Attorney Agency Building 2 Executive Chamber Empire State Plaza State Capitql Albany, New York 12223 Albany, NY 12224-Energy Research Group, Inc.
400-1 Totten Pond Road Waltham, Massachusetts 02154 W. Taylor Reveley,.III, Esquire Hunton'& Williams
- Post Office Box 1535 Richmond. Virginia 23212
~
Honorable Peter Cohalan Suffolk County Executive County Executive / Legislative Bldg.
Veteran's Memorial Highway Hauppauge, New York 11788 Martin Bradley Ashare, Esquire Suffolk County Attorney
- H. Lee Dennison Building Veteran's Memorial Highway Hauppauge, New York 11788
' James B. Dougherty, Esquire 3045 Porter Street, N.W.
Washington, D.C.
20008
/
1 w--
..-..,.-,_w--.,c.,,,
.w...-e,,,-.-.,-.,
,,,,,~,.r-,,-.,
,,--ew,,
-,e-,--m----,ww--..-
vw--
,.. - -., -.,- - -