Mnps Discharge Monitoring Rept for Apr 1997
ML20140C572
Person / Time
Site: Millstone  
Issue date: 04/30/1997
From: Scace S
NORTHEAST NUCLEAR ENERGY CO., NORTHEAST UTILITIES SERVICE CO.
To:
CONNECTICUT, STATE OF
References
SES-97-GN-083, SES-97-GN-83, NUDOCS 9706090326
Download: ML20140C572 (44)


Text

.

ggg 107 Selden Street, Berlin, Cr 06037 Utilities System Snhe veintie. service comp.nr P.o Box 270 g

Hartford, CT 061410270 May 30,1997 m 665-5000 SES-97-GN-083 4

i D11112 4

DMR Processing i

2 Department of Environmental Protection Water Management Bureau 79 Elm Street Hartford, CT 06106-5127

Reference:

Letter (C04876), NPDES Permit No. CT0003263, Millstone Nuclear Power Station, Northeast Nuclear Energy Company, dated December 14,1992.

Millstone Nuclear Power Station Monthly Discharge Monitoring April 1997 Paragraph 3 of the referenced NPDES Permit requires that discharges from the permitted facility be monitored according to a specified schedule and results be reported to the Water Management Bureau by the end of the month after the month in which samples are taken. Northeast Nuclear Energy Company (NNECO) herein submits the attached report for the month of April 1997.

Any variations from the permit are explained in the section headed "Results and Discussions" enclosed.

Additional samples taken at NPDES locations and analyzed with approved methods are included on Tables 3,4 and 5.

Should you have any questions or require further information, please call Mr. Paul Jacobson, Northeast Utilities Service Company, Environmental Services-Nuclear at (860) 447-1791 ext.

2335.

I Very truly yours, NORTHEAST NUCLEAR ENERGY COMPANY cud S.'E. Scace' Director - Nuclear Engineering Programs Enclosure

[DR

. h[t 9706090326 970430

~

t ADOCK 0500 5

cc:

Mr. James Grier N

1 RC5 NRC Resident Inspector lllllllllllllllllllllllllllllllll m 22 arv.&e

~

L DMR Processing D11112/ Enclosure SES-97-GN-083 l

'May 30,1997 Millstone Nuclear Power Station Nonheast Nuclear Energy Company Results and Discussions NPDES Monthly Reoort - April 1997 Introduction l

j.

This report fulfills the monitoring requirements for Millstone Nuclear Power Station, NPDES l

Permit No. CT0003263, renewed December 14,1992.

i l

As requested by the DEP in a letter to each NPDES facility, dated January 1,1988 (C01988),

l and recognizing DEP's requirement to submit data to EPA, NNECO will make every effort l

possible to submit the DMRs by the 20th of the month. However, in cases where the required data are not available, the DMRs will be submitted no later than the last day of the month in which they are due.

Results and Discussions Results of the continuous, weekly and monthly monitoring programs are summarized on the DMR sheets attached. With the exception of hydrazine, ethanolamine and boron, all sampling l

and analyses were conducted in accordance with approved procedures set forth in EPA l

Publication 600/4-79-02. Northeast Nuclear Energy Company submitted its own analysis l

procedures for these chemical substances (D10309) for DEP approval on October 4,1996.

The computerized data logging report of the continuous monitoring program is included as l

Table 1 for each month. This report is included because it provides data for the daily range of pH, temperature and flow, a requirement of the NPDES permit. The DMR form does not have provisions for daily ranges. These data are computer-generated summaries of 15 minute sample I

averages.

General Note - DMR Forms The DMR forms have some errors, omissions, and incorrect reporting requirements when l

compared to the permit requirements. They are included and defined ori Table 2.

i l

l I

i DMR Processing D11112/ Enclosure SES-97-GN-083 j

May 30,1997 l

Hydrazine Removal Prior to Discharge via DSN 001C-2 Waste waters containing trace amounts of hydrazine were detected in the High Level Waste i

Drains Tanks (HLWDT) associated with DSN 001C-2. Consistent with the manner in which I

similar wastewater has been previously handled, and as previously discussed with ti;e Department l

and described in correspondence (D11114) to the Department, the wastewaters in the HLWDT l

were processed through the demineralizers and filters associated with DSN 001C-2 prior to discharge from the Waste Test Tanks. These waste waters met all limits associated with DSN 001C-2; no hydrazine above detectable limits (< 5 ppb) using spectrophotometry was found.

Hydrazine Removal Prior to Discharge via DSN 001C-3 Waste water containing trace amounts of hydrazine was detected in the "B" Low Level Waste Drains Tank (LLWDT) associated with DSN 001C-3. Consistent with the manner in which similar waste water has been previously handled, and as previously discussed with the Department and described in correspondence (D11114) with the Department, the water in the LLWDT was processed through a filter and demineralizer to remove hydrazine to below detectable levels based on spectrophotometry (<5 ppb). This waste water met all limits associated with DSN 001C-3.

Aerated and Coolant Waste Monitoring Tank Dischalggs NNECO has previously discussed with the Department and reported (D)1074) the discharge via DSN 0018-2 and 001B-3 of Reactor Building Closed Cooling Water (RBCCW) wastewaters due to maintenance activities associated with the draining of the Unit 2 "A" RBCCW header. These activities occurred on April 12,19 and 241997. This wastewater included system drains from the radioactive portion of the RBCCW system and contained hydrazine. Hydrazine is not addressed in NNECO's NPDES permit at DSN 0018-2 or DSN 001B-3. These wastewaters were processed through demineralizers and filters associated with DSN 001B-2 and 0018-3. At the time of each discharge, the wastewaters were below detectable limits for hydrazine (<3.2 ppb).

Discharge of Unit 2 Reactor Building Closed Cooling Water (RBCCW) Sumo Wastewater NNECO has pre,viously discussed with the Department the protocol for the discharge via DSN 001B-9 of certam wastewaters due to certain maintenance activities at Unit 2. Due to these activities, the normal pathway (DSN 001B-5) could not be used, and these wastewaters were j

directed to the RBCCW sump and discharged from DSN 001B-9. Discharges occurring during l

the month of April were reported in writing to the Department (D11074). At the time of each l

discharge, hydrazine was not detected (<350 ppb) using the titration method.

l r

2 l

DMR Processing D11112/ Enclosure SES-97-GN-083 May 30,1997 l

1 1

Discharge of Unit 2 Deicing Pit as DSN 0018-1(a)

On April 24,1997 Unit 2 discharged approximately 3,500 gallons of wastewater from the deicing i

pit. As this discharge contained wastewater from the Steam Generator sample sinks, the results are reported as DSN 001B-1(a) in this report. The discharge was analyzed and met all discharge requirements for DSN 001B-1(a).

Use of Emergency Service Water System Beginning on March 29,1997, and throughout the month of April, Unit I used the Emergency Service Water (ESW) System in place of the normal service water system to cool the Turbine Building and Reactor Building heat exchangers. As previously discussed with the Department, ESW is sea water taken from the intake structure through backup service water pumps. During plant shutdown, ESW backup pumps provide approximately 25% of the flow of normal service water. There is temporary chlorination of this system to prevent biofouling. The water gets routed to the circulating water discharge tunnel (DSN 001 A) and service water discharge tunnel (DSN 001 A-5). Both locations are permitted to discharge up to 0 25 mg/L Free Available Chlorine. The Department was previously notified of this activity verbally and in writing (D10932).

l 1

Fuel Oil Soill On April 28,1997 a spill of approximately two gallons of Number 4 fuel oil onto pavement occurred at Unit 3. A spill report was called into the National Response Center, and this was followed by a written report (D11079) to the DEP and the Coast Guard.

Notification of Service WMer System Strainer Backwash Discharge By way of verbal notification on May 20 and 22,1997, and by way ofletter dated May 27,1997 (SES-97-GN-090), NNECO advised the Denartment of the discharge of service water system strainer backwash at Millstone Units 1,2 and 3. As expWd at a meeting with the Department on May 29,1997, backwash water is supplied by the se..Me water system. NNECO has confirmed that the strainer backwash water at all three Units cotains residual chlorine. The wastewater generated from the backwash operation at Units 1 and 2 flows to the screenwash discharge (DSN's 002 and 003 respectively). The discharge of the Unit 3 strainer backwash flows to two pipes (each approximately 3 inches in diameter) located on the east and west faces of the Millstone 3 intake structure. While chlorination and discharge of service water in authorized by the Department, NNECO is continuing to review the discharge of service water at these specific locations had been previously identified to the Department. Also, as discussed with the Department on May 27,1997, NNECO is in the process of reviewing engineering and regulatory l

options with respect to the discharge of service water backwash at each Unit.

3

DMR Processing j

D11112/ Enclosure SES-97-GN-0.83.

May 30,1997 Unit 3 Closed Cooling Water System Discharges As discussed in last month's DMR, (D11003) NNECO has identified the presence of freon at trace levels in the Unit 3 Reactor Plant Chilled Water System (RPCW). Due to cross ties with the RPCW system, freon may also be present in the Reactor Plant Closed Cooling Water System

- (RPCCW). Additional analytical testing was performed as part of NNECO's investigation into this matter and will be provided under separate cover as requested by the Department. While l

l freon was not found above detection in any of the subsequent sampling, trace levels of other 1

organic substances were detected. Upon receipt of the laboratory results, these findings were verbally reported to the Department on May 12,1997 and are as follows:

DSN Date Chloro Acetone 1,2 Dichloro Xylene Dichloro Carbon methane ethane difluoro Disulfide -

methane 001C-3 4/8/97 34 33" 9.5 6.6 001C-2 4/8/97 33 21 **

9.9 001C 4/8/97 l

001C-2 4/8/97 l

001C-3 4/25/97 2.6*"

001C-2 4/25/97 210 001C-2 4/25/97 110 l

001C-3 4/26/97 21 "

4.6"*

5. 3""

l 001C-2 4/26/97 84 l

001C-3 5/2/97 26" 001C-2 5/3/97 001C-3 5/6/97 001C-2 5/7/97 l

001C-2 5/9/97 1

001C-3 5/9/97 all results in parts per billion estimated result; belew detection limit of 50 ppb estimated result; below detection limit of 5 ppb j

below detection limit of 10 ppb i

4

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Discharge Monitoring Report (DMR)

DATE RECEIVED (STAMPED)

Permit: CT0003263 MAJ Dist: 12 Town:152 Loc:003 Facility-MILLSTONE NUCLEAR POWER STA.

Contact:

Paul Jacobson Town: WATERFORD Phone: (860) 447-1791 Ext. 2335 Logged:

Delivered:

OK'd:

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month ADril 1997 Average Flow-2738000000 GPD ND = none detected Discharg 0011 Mon Loc: 1 COOLING WATER < 5000 Samp% Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

50064 121492 0/1 G

MG/L CHLORINE, FREE AVAILA ND 0.04 01/07 <0.02 0.04 0.04 <0.02 <0.02 50060 121492 0/1 G

MG/L CHLORINE, TOTAL RESID ND 0.07 01/07 <0.02 0.07 0.04 0.02 <0.02 50050 121492 0/1 i

MGD FLOW, IN CONDUIT OR THRU 1313.2 24/01 SEE ATTACHED TABLE 1

~

~

00400 121492 0/1 G

SU PH 7.9 8.3 24/01 SEE ATTACHED TABLE 1

?

00018 121492 0/1 1

DEG TEMP DIFF BETWEEN SAMP 0.0 1.7 4.2 02/14 SEE ATTACHED TABLE 1 t

00011 121492 Oli i

DEG TEMP. DEG FAHRENHEIT 41.6 44.9 50.5 24/01 SEE ATTACHED TABLE 1 i

00015 121492 0/1 CA BTUI THERMAL DISCHARGE MILLION 252.7 1012.7 01/01 SEE ATTACHED TABLE 1 l

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month ADnl 1997 Average Flow-2738000000 GPD ND = none detected Discharg 0011 Men Loc: 7 COOLING WATER < 5000 Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00011 121492 0/1 1

DEG TEMPERATURE DEG FAHR 49.5 24/01 SEE ATTACHED TABLE 1 COMMENTS:

1 Page1

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Descharge Monitoring Report (DMR)

KEY: CT0003263 isstar:121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-604800000 GPD ND = none deteded Descharg 001 A Mon Loc-1 COOLING WATER < 5000 Sample Weeks:

[

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

50064 120192 0/1 G

KG/D CHLORINE, FREE AVAILABLE 3.9 01/07

~

~

50064 120192 0/1 G

MGIL CHLORINE, FREE AVAILA ND 0.06 01/07 0.06 0.05 <0.02 <0.02 <0.02

~

~

i Unit shutdown, upstream flows only.

01042 091986 0/0 CP UG/L COPPER, TOTAL (AS CU) 01/90 l

E4 py %.:o.10Jv fL. 0.4, i

50050 091986 0/0 I

MGD FLOW,IN CONDUIT OR THRU 17.3 24/01 SEE ATTACHED TABLE 1

~

~

Upstream flows only. No circ water flow.

01051 091986 0/0 CP UG/L LEAD. TOTAL (AS PB) 01/90

~

~

6%eryt.cy9AcLAJt,R.w0.p 01067 091986 0/0 CP UG/L NICKEL, TOTAL (AS NI) 01/90 l

00610 091986 0/0 CP UG/L NITROGEN AMMONIATOTAL 01/90 1

01/90

~

00556 091986 0/0 CP UG/L O!L & GREASE FREON EXTR 00400 091986 Ol0 I

SU PH 7.7 8.0 24/01 SEE ATTACHED TABLE 1 Unit shutdown, upstream flows only.

00530 091986 0/0 CP UG/L SOUDS, TOTAL SUSPENDED 01/90 38260 091986 Ol0 CP UG/L SURFACTANTS(MBAS) 01/90 l'

00018 091986 Ol0 I

DEG TEMP DIFF BETWEEN SAMPLE 0.4 3.6 8.9 01/01 SEE ATTACHED TABLE 1 Unit shutdown, upstream flows only.

00011 091986 0/0 1

DEG TEMPERATURE DEG FAHR 41.7 46.8 53.2 24/01 SEE ATTACHED TABLE 1 Unit shutdown, upstream flows only.

00015 091986 0/0 CA DTU/ THERMAL DISCHARGE MILLION 1.3 41.5 01/01 SEE ATTACHED TABLE 1 Unit shutdown, upstream flows only.

i 01092 091986 0/0 CP UG/L ZINC, TOTAL (AS ZN) 01/90 COMMENTS:

Page 2 i

t

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Discharge Monitoring Report (DMR)

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flove. 604800000 GPD ND = none detected Discharg 001 A Mon Loc-G COOUNG WATER < 5000 Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

01042 091986 0/0 CP UG/L COPPER TOTAL (AS CU) 01/90

~

~

1 01/90 01051 091986 0/0 CP UG4. LEAD TOTAL (AS PB) 01067 091986 0/0 CP UG/L NICKEL, TOTAL (AS NI) 01/90 00610 091986 0/0 CP UG/L NITROGEN. AMMONIATOTAL 01/90 00556 091986 0/0 CP UG/L OfL & GREASE FREON EXTR.

01/90

~

~

01190

~

~

00530 091986 0/0 CP UG/L SOLIDS, TOTAL SUSPENDED 01/90 38260 091986 0/0 CP UG/L SURFACTANTS(MBAS) 01/90

~

~

01092 091986 0/0 CP UG/L ZINC, TOTAL (AS ZN)

COMMENTS:

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow. 604800000 GPD ND = norie deteded Discharg 001 A Mon Loc T COOLING WATER < 5000 Sample Weeks:

Code Start shn Typ _ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

i 02/99 TGB6A 091986 0/0 CP P/F P/F STAT ACU CYPRINODON

~

~

02/99 TGA3E 091986 0/0 CP P/F P/F STAT ACU MYSIDOPSIS 02/99 TGC6A 091986 0/0 CP P/F P/F CHR CYPRINODON 02/99 TGC3E 091986 0/0 CP P/F P/F CHR WS!DOPSIS

~

~

Page 3

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Descharge Monitoring Repost (DMR)

- KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-820000000 GPD ND = none detected Discharg 001 B Mon Loc: 1 NON-CONTACT COOLING WATER Sample Weeks:

_ Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

50064 121492 0/1 G

KG/D CHLORINE, FREE AVAILABLE 120 01/07 i

50064 121492 0/1 G

MG/L CHLORINE, FREE AVAILABLE 0.08 01/07 0.08 0.07 0.06 0.07 0.08 01042 0919o0 0/0 CP UG/L COPPER, TOTAL (AS CU)

ND

<20 01/90 <20 f.ast sampled 4-97 f

50050 121492 Oli 1

MGD FLOW, IN CONDUIT OR THRU 394.6 24/01 SEE ATTACHED TABLE 1 i

01051 091986 0/0 CP UG/L LEAD TOTAL (AS PB)

ND

<10 01/90 <10 Last sampled 4-97 01067 091986 0/0 CP UG/L NICKEL, TOTAL (AS NI)

ND

<10 01/90 <10 Last sampled 4-97 i

00610 091986 0/0 CP UG/L NITROGEN, AMMONIA TO ND

<20 01/90 <20 Last sampled 4-97

[

00556 091986 0/0 CP UG/L OIL & GREASE FREON EX ND

<500 01/90 <500 Last sampled 4-97 j

f 00400 091986 0/0 i

SU PH 7.7 8.1 24/01 SEE ATTACHED TABLE 1 00530 091986 0/0 CP UG/L SOLIDS, TOTAL SUSPENDED 21200 01/90 12800 21200 Last sampled 4-97 f

38260 091986 0/0 CP UG/L SURFACTANTS(MBAS) 1500 01/90 1500 20 Last sampled 4-97 t

00018 091986 0/0 1

DEG TEMP DIFF BETWEEN SAMPLE 0.0 0.6 2.8 01/01 SEE ATTACHED TABLE 1 00011 091986 0/0 1

DEG TEMPERATURE DEG FAHR 41.3 44.9 51.0 24/01 SEE ATTACHED TABLE 1 00015 091986 0/0 CA BTU / THERMAL DISCHARGE MILLION 44.2 153.0 01/01 SEE ATTACHED TABLE 1 01092 091986 0/0 CP UG/L ZINC, TOTAL (AS ZN)

ND

<10 01/90 <10 Last sampled 4-97 l

COMMENTS:

i l

Page 4 l

STATE OF CONNECTICUT ** DEPARTMENT OF ENVIRONMENTAL PROTECTION

[

Bureau of Water Management - Descharge Monitoring Report (DMR)

[

t f

KEY: CT0003263 Issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow 820000000 GPD ND = none detected Discharg 001 B Mon Loc: G NON-CONTACT COOLING WATER Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq _ 1 2

3 4

5 01042 091986 0/0 CP UG/L COPPER, TOTAL (AS CU)

ND

<20 01/90 <20 Last sampled 4-97 I

01051 091980 0!O CP UG/L LEAD. TOTAL (AS PB)

ND

<10 01/90 <10 Last sampled 4-97 t

01067 091986 0/0 CP UG/L NICKEL, TOTAL (AS NI)

ND

<10 01/90 <10 Last sampled 4-97 f

00610 091986 0/0 CP UG/L NITROGEN, AMMONIA TO ND

<20 01/90 <20 Last sampled 4-97

}

~

00556 091986 0/0 CP UG/L OIL & GREASE FREON EX ND

<500 01/90 <500 Last sampled 4-97 00530 091986 0/0 CP UG/L SOLIDS. TOTAL SUSPENDED 15200 01/90 15200 Last sampled 4-97 38260 091986 0/0 CP UG/L SURFACTANTS (MBAS) 20 01/90 20 Last sampied 4-97

~

~

01092 091086 0/0 CP UG/L ZINC, TOTAL (AS ZN) 20 01/90 20 Last sampled 4-97 l

t COMMENTS:

i KEY: CT0003263 Issue: 121492 Expire: 12/14/97 Sample Month April 1997 l

Average Flow-820000000 GPD ND = none detected Discharg 001 B Mon Loc: T NON-CONTACT COOLING WATER Sample Weeks:

Code

.%. r'

-_ s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

t TGB6A

.,e E t.

0/0 CP P/F P/F STAT ACU CYPRINODON 0

02/99 0

Last sampled 4-97

)

~

TGA3E 091986 0/0 CP P/F P/F STAT ACU MYSIDOPSIS 0

02/99 0

Last sampled 4-97 i

(

TGC6A 091986 0/0 CP P/F P/F CHR CYPRINODON 0

02/99 0

Last sampled 4-97

[

TGC3E 091986 0/0 CP P/F P/F CHR MYSIDOPSIS 0

02/99 0

Last sampled 4-97 j

l Page 5 f

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION

~

~

Bureau of Water Management - Discharge Monitoring Report (DMR)

KEY: CT0003263 -

Issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow: 1313200000 GPD ND = none detected Discharg 001 C Mon Loc: 1 NON-CONTACT COOLING WATER Sample Weeks:

Code Sta:t s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

50064 121492 0/1 G

KG/D CHLORINE, FREE AVAILABLE 487 01/07 50064 121492 Ol1 G

MG/L CHLORINE, FREE AVAILABLE 0.14 01/07 0.10 0.08 0.14 0.12 01042 091986 0/0 CP UG/L COPPER, TOTAL (AS CU) 01/90 Last sampled 1-97 50050 121492 Ol1 l

MGD FLOW, IN CONDUIT OR THRU 918.7 24/01 SEE ATTACHED TABLE 1 01051 091986 0/0 CP UG/L LEAD, TOTAL (AS PB) 01/90 Last sampled 1-97 01067 091986 0/0 CP UG/L NICKEL. TOTAL (AS NI) 01/90 Last sampled 1-97 00610 091986 0/0 CP UG/L NITROGEN. AMMONIA TOTAL 01/90 Last sampled 1-97 00556 091986 0/0 CP UG/L OIL & GREASE FREON EXTR 01/90 Last sampled 1-97 00400 091986 0/0 i

SU PH 7.9 8.2 24/01 SEE ATTACHED TABLE 1 00530 091986 0/0 CP UG/L SOLIDS, TOTAL SUSPENDED 01/90 Last sampled 1-97 38260 091986 0/0 CP UG/L SURFACTANTS (MBAS) 01/90 Last sampled 1-97 00018 091986 0/0 t

DEG TEMP DIFF BETWEEN SAMPLE 0.0 0.5 1.9 01/01 SEE ATTACHED TABLE 1 00011 091986 0/0 1

DEG TEMPERATURE DEG FAHR 41.7 44.7 48.7 24/01 SEE ATTACHED TABLE 1 00015 091986 0/0 CA BTUI THERMAL DISCHARGE MILLION 6.1 248.3 01/01 SEE ATTACHED TABLE 1 01092 091986 0/0 CP UG/L ZINC, TOTAL (AS ZN) 01/90 Last sampled 1-97 COMMENTS:

Page 6

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Burelu of Water Management - Discharge Monitoring R:; port (DMR) e KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-1313200000 GPD ND = none detected Discharg 001 C Mon Loc: G NON-CONTACT COOLING WATER Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

01042 091986 0/0 CP UG/L COPPER, TOTAL (AS CU)

ND

<20 01/90 <20 Last sampled 4-97

~

01051 091986 0/0 CP UG/L LEAD, TOTAL (AS PB)

ND

<10 01/90 <10 Last sampled 4-97 01067 091986 0/0 CP UG/L NICKEL, TOTAL (AS NI)

ND

<10 01/90 <10 Last sampled 4-97 i

00610 091986 0/0 CP UG/L NITROGEN, AMMONIATO ND

<20 01/90

<20 Last sampled 4-97 t

00556 091986 0/0 CP UG/L O!L & GREASE FREON EX ND

<500 01/90 <500 Last sampled 4-97 00530 091986 0/0 CP UG/L SOLIDS, TOTAL SUSPENDED 25100 01/90 25100 Last sampled 4-97 38260 091986 0/0 CP UG/L SURFACTANTS (MBAS) 20 01/90 20 Last sampled 4-97 01092 091986 0/0 CP UG/L ZINC, TOTAL (AS ZN) 19 01/90 19 Last sampled 4-97 COMMENTS:

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month ADril 1997 Average Flow-1313200000 GPD ND = none detected Discharg 001 C Mon Loc: T NON-CONTACT COOLING WATER Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

TGB6A 091986 0/0 CP P/F P/F STAT ACU CYPRINODON 0

02/99 0

Last sampled 4-97 l

TGA3E 091986 0/0 CP P/F P/F STAT ACU MYSIDOPSIS 0

02/99 0

Last sampled 4-97 TGC6A 091986 0/0 CP P/F P/F CHR CYPRINODON 0

02/99 0

Last sampled 4-97 TGC3E 091986 0/0 CP P/F P/F CHR MYSIDOPSIS 0

02/99 0

Last sampled 4-97 L

Page 7 l

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Descharge Monitoring Report (DMR)

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow: INTERMITT GPD ND = none detected Discharg 005 Mon Loc: 1 STORMWATER Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00056 120192 0/1 i

GPD FLOW RATE, AVERAGE DAILY 144000 02/99 144K 00556 120192 Ol1 G

MG/L OIL & GREASE FREON EX ND

<0.5 02/99

<0.5 00530 120192 0/1 G

MG/L SOLIDS, TOTAL SUSPENDED 5.9 02/99 5.9 COMMENTS:

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-432000 GPD ND = none detected Discharg 006 Mon Loc

  • 1 STEAM ELECTRIC POWER PLNT Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00698 120192 0/1 CP KG/D BORIC ACID Code 9 01/07 00698 120192 0/1 CP MG/L BORIC ACID Code 9 01/07 50060 120192 0/1 G

MG/L CHLORINE, TOTAL RESID ND 0.02 0.09 01/07 0.05 0.02 0.09 0.04 0.07 Weekly high values. See Table 3.

01042 120192 0/1 CP KG/D COPPER, TOTAL (AS CU) 0.0031 01/07.0022.0031.0020.0019.0012 01042

^20192 0/1 CP MG/L COPPER, TOTAL (AS CU)

ND

<0.02 01/07 <0.02 <0.02 <0.02 <0.02 <0.02 00056 120192 Ol1 I

GPD FLOW RATE, AVERAGE DAILY 83424 02/99 60K 83K 53K 52K 33K 01051 120192 0/1 CP KG/D LEAD, TOTAL (AS PB) 0.0157 01/07.0113.0157.0100.0098.0062 01051 120192 0/1 CP MG/L LEAD TOTAL (AS PB)

ND

<0.10 01/07 <0.10 <0.10 <0.10 <0.10 <0.10 01067 120192 0/1 CP KG/D NICKEL TOTAL (AS NI) 0.0078 01/07.0056.0078.0050.0049.0031 Comment:

Page 8

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Discharge Monitoring Report (DMR)

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-432000 GPD ND = none detected Discharg 006 Mon Loc-1 STEAM ELECTRIC POWER PLNT Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

01067 120192 0/1 CP MG/L NICKEL, TOTAL (AS NI)

ND

<0.05 01/07 <0.05 <0.05 <0.05 <0.05 <0.05 00556 120192 0/1 G

MG/L O!L & GREASE FREON EX ND

<0.5

<0.5 01/30

<0.5

<0.5

<0.5

<0.5

<0.5

<0.5

<0.5

<0.5

<0.5

<0.5 00400 120192 Oli G

SU PH 7.36 7.85 01/07 7.57 7.36 7.65 7.72 7.53 7.37 7.59 7.49 7.66 7.85 00530 120192 0/1 CP MG/L SOLIDS, TOTAL SUSPENDED 1.0 1.7 01/07 0.3 1.0 0.8 1.7 1.4 01092 120192 0/1 CP KG/D ZINC, TOTAL (AS ZN) 0.0762 01/07.0227.0440.0462.0591.0762 01092 120192 0/1 CP MG/L ZINC, TOTAL (AS ZN) 0.61 01/07 0.10 0.14 0.23 0.30 0.61 COMMENTS:

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow: 432000 GPD ND = none detected Discharg 006 Mon Loc: T STEAM ELECTRIC POWER PLNT Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

TGA3E 120192 0/0 CP P/F P/F STAT ACU MYSIDOPSIS 0

02/99 0

Last sampled 4-97 TGC3E 120192 0/0 CP P/F P/F STAT CHR MYSIDOPSIS 0

02/99 0

Last sampled 4-97 i

COMMENTS:

i Page 9

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION

^

Bureau of Water Management - Discharge Monitoring Report (DMR)

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month ADril 1997 Average Flow-INTERMITT GPD ND = none detected Discharg 008 Mon Loc: 1 STORMWATER i

Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00056 120192 Oli I

GPD FLOW RATE. AVERAGE DAILY 7200 02/99 7200 00556 120192 0/1 G

MG/L Oil & GREASE FREON EX ND

<0.5 02/99

<0.5

~

~

00530 120192 0/1 G

MG/L SOLIDS,TOTALSUSPENDED 24.8 02/99 24.8

~

~

i KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow: INTERMITT GPD ND = none detected Discharg 009 Mon Loc: 1 STORMWATER Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00056 120192 Oli i

GPD FLOW RATE, AVERAGE DAILY 36000 02/99 36000 00556 120192 Oli G

MG/L OIL & GREASE FREON EX ND

<0.5 02/99

<0.5 I

~

~

i 00530 120192 0/1 G

MG/L SOLIDS, TOTAL SUSPENDED 6.8 02/99 6.8

~

~

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-INTERMITT GPD ND = none detected i

Discharg 016 Mon Loc: 1 STORMWATER Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

i 00056 120192 0/1 I

GPD FLOW RATE, AVERAGE DAILY 21600 02/99 21600

~

00556 120192 0/1 G

MG/L OIL & GREASE FREON EXTR 0.5 02/99 0.5

~

~

5 00530 120192 0/1 G

MG/L SOLIDS, TOTAL SUSPENDED 1.1 02/99 1.1 l

~

~

Page 10

.m.

~

[

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION

~

Bureau of Water Management - Discharge Monitoring Report (DMR) i i

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 l

Average Flow-604800000 GPD ND = none detected j

Descharg 01 A 1 Mon Loc-1 COOLING WATER < 5000

~

Sample Weeks:

f Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00164 120192 0/1 T

GPB FLOW, GALLONS / BATCH NF 02/99 No Discharge 00400 091686 0/0 G

SU PH NF 01/07 No Discharge

}

i 5

00095 091686 0/0 G

HM/C SPECIFIC CONDUCTANCE NF 01/07 No Discharge i

~

~

Comments:

}

I KEY: CT0003263 issue: 121492 Expre: 12/14/97 Sample Month Antil 1997 Average Flow: 14000 GPD ND = none detected Discharg 01 A2 Mon Loc-1 BUILDING FLOOR DRAIN Sample Weeks L

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

l t

i 00164 120192 0/1 T

GPB FLOW, GALLONS / BATCH 11100 01/01 11100 10950 10750 9900 Weekly max. only, see Table 4 00400 091986 0/0 G

SU PH 9.01 01/07 9.01 8.01 8.33 8.37 l

~

Weekly max. only, see Table 4 i

00530 120192 0/1 G

KG/D SOLIDS, TOTAL SUSPENDED 0.3829 01/07.3829.0830.0543.0262 i

Weekly max. only, see Table 4 j

00530 120192 0/1 G

MG/L SOLIDS, TOTAL SUSPENDED 9.4 01/07 9.4 2.0 1.4 0.7 Weekly max. only, see Table 4 KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 i

Average Flow-3500 GPD ND = none detected

[

Discharg 01 A 4 Mon Loc: 1 WATER PRODUCTION WASTEWTR Sample Weeks Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

r 00698 120192 0/1 G

KG/D BORIC ACID Code 9 H/DS i

00698 120192 Ol1 G

MG/L BOEIC ACID Code 9 H/DS l

1 00164 120192 0/1 T

OPB FLOW, GALLONS / BATCH 01/BA No Discharge j

~

~

Page 11 j

?

E

~

m..

9 STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Discharge Monitoring Report (DMR)

KEY: CT0003263 issue: 121492 Expire: 12/14/97, Sample Month April 1997 Average Flow-43200000 GPD ND = none detected Discharg 01 A 5 Mon Loc-1 NON-CONTACT COOLING WATER Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

50064 120192 0/1 G

MG/L CHLORINE, FREE AVAILABLE 0.15 01/07 0.15 0.14 0.15 0.08 0.13 50050 091986 0/0 1

MGD FLOW, IN CONDUIT OR THRU 3.6 01/07 3.6 3.6 3.6 3.6 3.6 E,erysuy St % e. k le. Ass t

00011 091986 0/0 G DEG TEMPERATURE DEG FAHR 72 01/07 72 72 68 66 50 COMMENTS:

+

KEY: CT0003263 Issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow: 1,440.000 GPD ND = none detected Discharg 01B 1 Mon Loc 1 BLOWDOWN FR HEAT & COOL Sample Weeks Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

I 00696 091986 0/0 G

KG/D BORIC ACID Code 9 02/99 During treatment or%

50050 091986 0/0 T

MGD FLOW,IN CONDUIT OR THRU 01/07 NO DISCHARGE 01/07 NO DISCHARGE i

00530 121492 0/1 G

KG/D SOLIDS, TOT l4. SUSPENDED 00530 121492 0/1 G

MGA. SOLIDe, TOTAL SUSPENDED 01/07 NO DISCHARGE i

00011 091986 0/0 1

DEG TEMPERATURE DEG FAHR 01/07 NO DISCHARGE l

~~*

COMMENTS:

Page 12 j

r

--. ~.

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureru of Water Management - DischarDe Monitoring Report (DMR)

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-5000 GPD ND = none detected Discharg 01B 2 Mon Loc: 1 BLOWDOWN FR HEAT & COOL Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00698 120192 0/1 BC KG/D BORIC ACID 41.4 01/07 41.4 NF 24.3 25.2 NF 00164 120192 0/1 T

GPB FLOW, GALLONS / BATCH 2452 01/07 1664 NF 1576 2452 NF 00400 091986 0/0 G

SU PH 7.04 01/07 5.26 NF 6.69 7.04 NF l

00530 091986 0/0 G

MG/L SOLIDS, TOTAL SUSPENDED 3.7 5.3 01/07 5.3 NF 2.7 3.1 NF

[

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow: 30000 GPD ND = none detected Discharg 01B 3 Mon Loc-1 BLOWDOWN FR HEAT & COOL l

Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00698 091986 0/0 BC KG/D BORIC ACID 305.6 01/07 NF 305.6 NF NF NF 00164 091986 0/0 T

GPB FLOW, GALLONS / BATCH 19656 01/07 NF 19656 NF NF NF t

00530 091986 0/0 G

MG/L SOLIDS, TOTAL SUSPENDED 1.7 1.7 01/07 NF 1.7 NF NF NF f

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 5

Average Flow-28800000 GPD ND = none detected Discharg 01B 5 Mon Loc: 1 NON-CONTACT COOLING WATER Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

[

50064 120192 Oli G

MG/L CHLORINE, FREE AVAILABLE 0.14 01/07 0.11 0.10 0.11 0.10 0.14 r

50050 120192 0/1 T

MGD FLOW, IN CONDUIT OR THRU 18.0 01/07 9.9 9.7 11.8 11.6 18.0 00011 120192 Ol1 l

DEG TEMPERATURE DEG FAHR 52 01/07 50 51 48 50 52 f

Page 13

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Disch rge Monitonog Report (DMR)

KEY: CT0003263 issue: 121492 Enire: 12/14/97 Sample Month April 1997 l

Average Flow-25000 GPD ND=c ne detected l

Discharg 01B 6 Mon Loc: 1 WATER PRODUCTION WASTEWTR j

Samr!> Weeix Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2,

_.5 4

5 00698 091986 0/0 BC KG/D BORIC ACID Code 9 02/99 00164 120192 0/1 T

GPB FLOW, GALLONS / BATCH 18300 01/07 NF NF 18300 NF NF Weekly mar. only, see Table 4 00556 120192 0/1 G

MG/L OIL & GREASE FREON EX ND

<0.5 01/30 NF NF

'0.5 NF NF 00400 091986 0/0 G

SU PH 7.31 01/07 NF NF 7.31 NF NF Weekly max. only, see Toble 4 00530 120192 0/1 G

MG/L SOLIDS TOTALSUSPENDED 7.0 01/07 NF NF 7.0 NF NF Weekly max. only, see Table 4 COMMENTS:

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-5760000 GPD ND = none detected Discharg 01B 7 Mon Loc: 1 NON-CONTACT COOLING WATER Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

50064 091986 0/0 G

KG/D CHLORINE, FREE AVAILABLE 01/07 NO DISCHARGE 50064 091986 0/0 G

MG/L CHLORINE, FREE AVAILABLE 01/07 NO DISCHARGE 50050 120197.

0/1 T

MGD FLOW, IN CONDUIT OR THRU 02/99 NO DISCHARGE 00011 120192 Oli i

DEG TEMPERATURE DEG FAHR 01/07 NO DISCHARGE COMMENTS:

Page 14

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Discharge Monitoring R; port (DMR)

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-100000 GPD ND = none detected Discharg 01B 8 Mon Loc: 1 BLOWDOWN FR HEAT & COOL Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

i 00164 120192 0/1 T

GPB FLOW, GALLONS / BATCH 01/DD NF NF NF NF NF 81313 120192 0/1 G

MG/L HYDRAZINE 01/DD NF NF NF NF NF 01045 120192 0/1 G

MG/L IRON, TOTAL (AS FE) 01/DD NF NF NF NF NF 01/DD NF NF NF NF NF 00100 120192 Oli i

SU PH 00530 120192 0/1 G

MG/L SOLIDS, TOTAL SUSFENDED 01/DD NF NF NF NF NF 01/DD NF NF NF NF NF 00011 120192 0/1 G DEG TEMPERATURE DEG FAHR COMMENTS:

Note 1 = Discharged through deicing pit.

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month ADril 1997 Average Flow: 30000 GPD ND = none detected Discharg 01B 9 Mon Loc: 1 NON-CONTACT COOLING WATER Sample Weeks:

Code Start s!m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00056 120192 0/1 T

GFD FLOW RATE, AVERAGE DAILY 7652 01/DD 7652 2680 1200 1836 NF l

Note 1 weeidy max see Table 4 81313 091986 0/0 G

MG/L HYDRAZINE ND

<0.350 01/DD <.350 <.350 <.350 <.350 NF Weekly max. see Table 4 00011 120192 Oli i

DEG TEMPERATURE DEG FAHR 74 01/DD 74 71 70 68 NF

(

Weekly max. see Table 4 COMMENTS:

Note 1 = See Results and Discussion.

Page 15

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - DischerDe Monitoring Report (DMR)

KEY: CT0003263 Issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-1400000 GPD ND = none detected Discharg 01C 1 Mon Loc: 1 STEAM ELECTRIC POWER PLNT Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00698 091986 0/0 G

KG/D BORIC ACID Code 9 02/99 Conditional Monitoring

~

~

50050 120192 0/1 1

MGD FLOW, IN CONDUIT OR THRU 01/07 NO DISCHARGE

~

~

l 00400 091986 0/0 G

SU PH 01/07 NO DISCHARGE 00530 120192 0/1 G

MG/L SOLIDS, TOTAL SUSPENDED 01/07 NO DISCHARGE 00011 120192 0/1 G DEG TEMPERATURE DEG FAHR 01/07 NO DISCHARGE KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow: 25000 GPD ND = none detected Discharg 01C 2 Mon Loc: 1 BUILDING FLOOR DRAIN Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00698 120192 0/1 BC KG/D BORIC ACID 788.6 01/07 2.1 533.3 788.6 654.2 NF Weekly max. see Table 5 00164 120192 0/1 I

GPB FLOW, GALLONS / BATCH 19110 01/07 3978 18481 18499 19110 NF i

~

~

Weekly max. see Table 5 01132 091986 0/0 G

MG/L LITHlUM, TOTAL (AS LI)

ND

<0.10 01/07 <0.10 <0.10 <0.10 <0.10 NF Weekly max. see Table 5 00400 091986 0/0 G

SU PH 8.45 01/07 8.45 5.60 4.36 4.96 NF Weekly max. see Table 5 00095 091986 0/0 G

HM/C SPECIFIC CONDUCTANCE 24.8 01/07 0.9 20.7 24.8 5.9 NF Weekly max. see Table 5 COMMENTS:

Page 1B

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Discioge Monitoring Report (DMR) i KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month ADril 1997 Average Flow: 5000 GPD ND = none detected Discharg 01C 3 Mon Loc-1 BLOWDOWN FR HEAT & COOL Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

[

00698 120192 0/1 G

KG/D BORIC ACID 13.8 H/D 10.4 7.7 NF 13.8 NF 7.1 10.0 00164 120192 0/1 T

GPB FLOW, GALLONS / BATCH 3480 01/07 3200 3239 NF 3480 NF I

2920 2919 00400 091986 0/0 G

GU PH 11.60 01/07 11.26 11.60 NF 9.60 NF 11.47 9.41 00530 120192 0/1 G

MG/L SOLIDS, TOTAL SUSPENDED 17.1 01/07 9.6 17.0 NF 17.0 NF 2.5 17.1 KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month ADril 1997 Average Flow-80000 GPD ND = none deteded Discharg 01C 4 Mon Loc: 1 WATER PRODUCTION WASTEWTR f

Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

i 00164 091986 0/0 T

GPB FLOV/, GALLONS / BATCH 44000 01/07 NF NF NF 45000 43000 i

81313 091986 0/0 G

MG/L HYDRAZINE ND 2.0 02/99 NF NF NF

<.350 2.0 l

00400 091986 0/0 G

SU PH 6.43 01/07 NF NF NF 6.30 6.43 l

00530 120192 0/1 G

MG/L SOLIDS. TOTAL SUSPENDED 43.5 01/07 NF NF NF 43.5 35.2 f

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month ADnl1997 Average Flow 43200000 GPD ND = none detected Discharg 01C 5 Mon Loc: 1 NON-CONTACT COOLING WATER l

Sample Weeks:

Code Start s/m Typ Unit Parameter Min Ave.

Max.

Freq 1

2 3

4 5

50064 120192 0/1 G

MG/L CHLORINE, FREE AVAILABLE 0.18 01/07 0.14 C.16 0.16 0.18 0.16 Weekly maximum. See Table 3 l

50050 120192 Ol1 1

MGD FLOW IN CONDUlT OR THRU 43.2 02/99 21.6 21.6 43.2 43.2 43.2 l

00011 120192 0/1 i

DEG TEMPERATURE DEG FAHR 54 01/07 49 49 50 52 54 Page 17 i

t

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Discharge Monitoring Report (DMR) l KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-25000 GPD ND = none detected I

Discharg 01C 6 Mon Loc: 1 WATER PRODUCTION WASTEWTR Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave Max.

Freq 1

2 3

4 5

00164 120192 0/1 T

GPB FLOW, GALLONS / BATCH 12420 01/07 NF 12420 NF NF NF 81313 120192 0/1 G

MG/L HYDRAZINE 0.04 02/99 NF 0.04 NF NF NF 00556 120192 0/1 G

KG/D OIL & GREASE FREON EXTR 0.0117 01/30 NF.0117 00556 120192 0/1 G

MG/L OlL & GREASE FREON EX ND

<0.5 01/30 NF

<0.5

"~

00400 091986 0/0 G

SU PH 6.81 01/07 NF 6.81 NF NF NF r

L 00530 120192 0/1 G

KG/D SOLIDS TOTAL SUSPENDED 0.02 01/07 NF 0.02 NF NF NF 00530 120192 Ol1 G

MG/L SOLIDS, TOTAL SUSPENDED 0.5 01/07 NF 0.5 NF NF NF 00011 120192 0/1 G DEG TEMPERATURE DEG FAHR 67 01/07 NF 67 NF NF NF KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month ADnl1997 Average Flow: 100000 GPD ND = none detected l

Discharg 01C 8 Mon Loc: 1 BLOWDOWN FR HEAT / COOL Sample Weeks:

l Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

l 00164 120192 0/1 BC GPB FLOW, GALLONS / BATCH 02/99 NF NF NF NF NF 81313 120192 0/1 G

MG/L HYDRAZINE 01/DD NF NF NF NF NF 01045 120192 Ol1 G

MG/L IRON, TOTAL (AS FE) 01/DD NF NF NF NF NF 00400 091986 0/0 G

SU PH 01/DD NF NF NF NF NF 00530 120192 0/1 G

MG/L SOLIDS, TOTAL SUSPENDED 01/DD NF NF NF NF NF 00011 120192 0/1 G DEG TEMPERATURE DEG FAHR 01/DD NF NF NF NF NF Page 18

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Discharge Monitoring Report (DMR)

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-300000 GPD ND = none detected Discharg 01C 9 Mon Loc: 1 NON-CONTACT COOLING WATER Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00056 120192 Oli I

GPD FLOW RATE, AVERAGE DAILY 700 01/DD 700*

NF NF NF NF

  • volume composed of evee smes drscharges 81313 091986 0/0 G

MG/L HYDRAZINE ND 0.007 01/DD 0.007 NF NF NF NF

<.005/<.005 00011 120192 0/1 G DEG TEMPERATURE DEG FAHR 69 01/DD 69 NF NF NF NF f

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-220 GPD ND = none detected Discharg 1 A2 A Mon Loc: 1 MISC LAUNDRY & GARMENT Sample Weeks:

t Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00164 120192 0/1 T

GPB FLOW, GALLONS / BATCH 01/DD NO DISCHARGE 70015 091986 0/1 G

MG/L FREON, TOTAL 01/DD NO DISCHARGE 01/DD NO DISCHARGE 00556 120192 0/1 G

MG/L OIL & GREASE FREON EXTR KEY: CT0003263 Issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow: 6500 GPD ND = none detected Discharg 1 A2 B Mon Loc: 1 MISC LAUNDRY & GARMENT Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00164 120192 0/1 T

GPB FLOW, GALLONS / BATCH 01/DD NO DISCHARGE 70015 091986 0/1 G

MG/L FREON, TOTAL 01/DD NO DISCHARGE 00556 120192 0/1 G

MG/L OIL & GREASE FREON EXTR OfiDD NO DISCHARGE Page 19 l

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Discharge Monitoring Report (DMR)

KEY: CT00032*3 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-70000 GPD ND = none detected Discharg 1B1 A Mon Loc: 1 BLOWDOWN FR HEAT & COOL Sample Weeks:

Code Start s/m Typ Unit Parameter ICin.

Ave.

Max.

Freq 1

2 3

4 5

00164 120192 0/1 G

GPB FLOW, GALLONS / BATCH 3500 01/DD NO DISCHARGE 3500 See Results and Discussion 81313 120192 0/1 I

KGO HYDRAZINE 0.0023 01/DD NO DISCHARGE

.0023 See Results and Discussion 81313 120192 Oli l

MG/L HYDRAZINE ND

<0.350 01/DD NO DISCHARGE

<.350 See Results and Discussion 00011 120192 0/1 1

DEG TEMPERATURE DEG FAHR 52 01/DD NO DISCHARGE 52 See Results and Discussion KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow: 107000 GFD ND = none detected Dtscharg 182 A Mon Loc: 1 BLOWDOWN FR HEAT & COOL Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00619 091986 0/0 CP MG/L AMMONIA, UNIONIZED 01/07 NO DISCHARGE 00998 091986 0/0 CP MG/L BERYLLIUM, TOTAL RECOVE 01/DD NO DISCHARGE 00310 091986 0/0 CP MG/L BOD 5 DAY (20 DEG C) 01/07 NO DISCHARGE 01027 091986 0/0 CP MG/L CADMlUM, TOTAL (AS CD) 01/DD NO DISCHARGE 00335 091986 0/0 CP MG/L CHEMICAL OXYGEN DEMAND 01/DD NO DISCHARGE 01034 091986 0/0 CP MG/L CHROMlUM, TOTAL (AS CR) 01/DD NO DISCHARGE 01042 091986 0/0 CP MG/L COPPER, TOTAL (AS CU) 01/DD NO DISCHARGE 00164 120192 Oli G

GPB FLOW, GALLONS / BATCH 01/DD NO DISCHARGE 01045 091986 0/0 CP MG/L IRON, TOTAL (AS FE) 01/DD NO DISCHARGE Page 20

~

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau cf Water Management - Discharge Monitoring Report (DMR)

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow: 107000 GPD N3 = none detected Discharg 182 A Mon Loc: 1 BLOWDOWN FR HEAT & COOL Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

f 01051 091986 0/0 CP MG/L LEAD, TOTAL (AS PB) 01/DD NO DISCHARGE 01067 091986 0/0 CP MG/L NICKEL, TOTAL (AS NI) 01/DD NO DISCHARGE

~"

00556 091986 0/0 G

MG/L OIL & GREASE FREON EXTR 01/DD NO DISCHARGE 00400 091986 0/0 G

SU PH 01/DD NO DISCHARGE 00530 091986 0/0 CP MG/L SOLIDS, TOTAL SUSPENDED 01/DD NO DISCHARGE 01092 091986 0/0 CP MG/L ZINC. TOTAL (AS ZN) 01/DD NO DISCHARGE KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month ADril 1997 Average Flow 30000 GPD ND = none detected Discharg 1B2 B Mon Loc: 1 STEAM ELECTRIC POWER PLNT Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00310 091986 0/0 CP MG/L BOD 5 DAY (20 DEG C) 01/DD NO DISCHARGE t

~ **

i 01/DD NO DISCHARGE

"~

01027 091986 0/0 CP MG/L CADMlUM, TOTAL (AS CD) 00335 091986 0/0 CP MG/L CHEMICAL OXYGEN DEMAND 01/DD NO DISCHARGE 01034 091986 0/0 CP MG/L CHROMlUM, TOTAL (AS CR) 01/DD NO DISCHARGE L

77666 120192 0/1 CP MG/L CITRIC ACID WHOLE WATER 01/DD NO DISCHARGE 01042 091986 0/0 CP MG/L COPPER, TOTAL (AS CU) 01/DD NO DISCHARGE l

78151 120192 0/1 CP MG/L EDTA 01/DD NO DISCHARGE

"~

~

l i

Page 21 I

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Discharge Monitoring Report (DMR)

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 i

Average Fiow-30000 GPD ND = none detected Discharg 1B2 B Mon Loc-1 STEAM ELECTRIC POWER PLNT Sample Weeks:

Code Start s/m Typ Unit Parameier Min.

Ave.

Max.

Freq 1

2 3

4 5

00164 120192 0/1 1

GPB FLOW, GALLONS / BATCH 01/DD NO DISCHARGE 77006 120192 0/1 CP MG/L FORMIC ACID WHOLE WATER 01/DD NO DISCHARGE i

00139 091986 0/0 CP MG/L HYDROGEN PEROXIDE 01/DD NO DISCHARGE i

01045 091986 0/0 CP MG/L IRON, TOTAL (AS FE) 01/DD NO DISCHARGE 01051 091986 0/0 CP MG/L LEAD, TOTAL (AS PB) 01/DD NO DISCHARGE 01067 091986 0/0 CP MG/L NICKEL, TOTAL (AS NI) 01/DD NO DISCHARGE 00556 120192 0/1 G

MG/L OIL & GREASE FREON EXTR 01/DD NO DISCHARGE 77081 120192 0/1 CP MG/L OXALIC ACID 01/DD NO DISCHARGE 00400 091986 0/0 RC SU PH 01/DD NO DISCHARGE 00530 091986 0/0 CP MG/L SOLIDS, TOTAL SUSPENDED 01/DD NO DISCHARGE 01092 091986 0/0 CP MG/L ZINC, TOTAL (AS ZN) 01/DD NO DISCHARGE 5

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample ~ Month ADril 1997 Average Flow: 144000 GPD ND = none detected Discharg 1C1 A Mon Loc: 1 BLOWDOWN FR HEAT & COOL Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00164 120192 0/1 1

GPB FLOW, GALLONS / BATCH 01/DD NF NF NF NF 81313 120192 0/1 G

MG/L HYDRAZINE 01/DD NF NF NF NF Page 22

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Discherge Monitoring Report (DMR) i KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-40000 GPD ND = none detected Discharg 1C6 A Mon Loc: 1 WATER PRODUCTION WASTEWTR I

Sample Weeks:

Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

i 01/DD NO DISCHARGE f

00310 091986 0/0 CP MG/L BOD 5 DAY (20 DEG C) 01027 091986 0/0 CP MG/L CADMlUM, TOTAL (AS CD) 01/DD NO DISCHARGE h

00335 091986 0/0 CP MG/L CHEMICAL OXYGEN DEMAND 010 D NO DISCHARGE 01034 091986 0/0 CP MG/L CHROMlUM, TOTAL (AS CR) 01/DD NO DISCHARGE 77666 120192 0/1 CP MG/L CITRIC ACID WHOLE WATER 01/DD NO DISCHARGE 01/DD NO DISCHARGE I

01042 091986 0/0 CP MG/L COPPER TOTAL (AS CU) 78151 120192 0/1 CP MG/L EDTA 01/DD NO DISCHARGE

{

00164 120192 Ol1 I

GPB FLOW, GALLONS / BATCH 01/DD NO DISCHARGE 77006 120192 0/1 CP MG/L FORMIC ACID WHOLE WATER 01/DD NO DISCHARGE l

00139 091986 0/0 CP MG/L HYDROGEN PEROXIDE 01/DD NO DISCHARGE i

01045 091986 0/0 CP MG/L IRON, TOTAL (AS FE) 010D NO DISCHARGE i

01051 091986 0/0 CP MG/L LEAD, TOTAL (AS PB) 01/DD NO DISCHARGE l

01067 091986 0/0 CP MG/L N!CKEL, TOTAL (AS NI) 010 D NO DISCHARGE 00556 120192 0/1 G

MG/L OIL & GREASE FREON EXTR 01/DD NO DISCHARGE l

77081 120192 0/1 CP MG/L OXALIC ACID 01/DD NO DISCHARGE 00400 091986 0/0 RC SU PH 01/DD NO DISCHARGE I

01/DD NO DISCHARGE 00530 091986 0/0 CP MG/L SOLIDS TOTAL SUSPENDED i

01092 091986 0/0 CP MG/L ZINC, TOTAL (AS ZN) 010D NO DISCHARGE Page 23 i

STATE OF CONNECTICUT " DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Management - Discharge Monitoring Report (DMR)

KEY: CT0003263 issue: 121492 Expire: 12/14/97 Sample Month April 1997 Average Flow-72000 GPD ND = none detected Discharg 1C6 B Mon Loc: 1 BLOWDOWN FR HEAT & COOL Sample Weeks:

i Code Start s/m Typ Unit Parameter Min.

Ave.

Max.

Freq 1

2 3

4 5

00056 120192 011 T

GPD FLOW RATE AVERAGE DAILY 3270 01/07 3270 1460 1630 1420 1290

~

~

Weekly max. see Table 5 81313 091986 0/0 CP MG/L HYDRAZlNE 66 01/07 64 49 47 66 56 Weekly max. see Table 5 00011 120192 0/1 G DEG TEMPERATURE DEG FAHR 195 01/07 195 190 190 180 190 Weekly max. see Table 5 COMMENTS:

r I

k Page 24

I PERMIT: CT0003263 DIST: 12 TOWN: 152 LOC: 003 r

FACILITY: MILLSTONE NUCLEAR POWER STA.

MAILING NAME:

NORTHEAST NUCLEAR ENERGY CO.

ADDRESS: RTE 156 ADDRESS:

P. O. BOX 270 CITY, STATE ZIP: WATERFORD, CT 06385 CITY, STATE, ZIP:

HARTFORD, CT 06101 CONTACT:

MR. PAUL JACOBSON CONTACT:

MR. PAUL JACOBSON PHONE: (860) 447-1791 Ext. 2335 PHONE:

(860) 447-1791 Ext. 2335 If there are any changes or corrections with your facility information, please cross out incorrect information and replace with correct information.

THIS DMR CONSISTS OF 25 PAGES FOR THE REPORTING PERIOD April 1997 j

STATEMENT OF ACKNOWLEDGEMENT I certify under penalty of law that this document is identical in format and content to the preprinted Discharge Monitoring Report which I received from the Department of Environmental Protection on:

12/22/95 I

I certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the Information submitted is, to the best of my knowledge and belief, true, accurate and complete. I am aware that there are significant l

penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations.

Authorized Official:

S. E. Scace

Title:

Director-Nuclear Engineering Programs

[

ca.cp-Date:

5 17 Signature:

~

/

)

Page 25

TABLE 1. Pagn 1 EILLSTONE STATION / ALL UNITS MONTNLY WATER QUALITY DATA

SUMMARY

/ DISCHARGE SERIAL NUMBER 001 DATA PERIOD = 1 APR 97/0000 - 30 APR 97/2345 DATA ACQUISITION INTERVAL = MINUTES 00-15 0F EACH NOUR i

DAY PM RANGE FLOW RANGE MAX MIN AVG SDEV MAX MIN AVG SDEV MAX NL MIN NL AVG NL SD NL MRC ML MAX MIN AVG TEMP TEMP TEMP TEMP DEL T DEL T DEL T DEL T 1

8.2-8.1 305 304 304 42.0 41.9 41.9 0.0 2.4 1.7 2.1 0.2 363.1 264.0 315.5 33.2

-39.6 2

8.2-8.1 304 288 293 42.3 41.6 41.9 0.2 2.2 1.1 1.8 0.3 341.4 161.8 265.3 53.1

-82.0 3

8.2-8.2 299 289 290 42.9 42.0 42.4 ~

0.3 2.2 a.7 1.5 C.5 324.7 102.9 224.5 73.1

-65.8 i

4 8.2-8.2 296 289 290 43.6 42.8 43.2 0.3 1.8 1.2 1.5 0.2 258.2 173.6 211.7 25.8

-40.6 5

8.3-8.2 906 289 518 44.2 42.9 43.5 0.5 1.9 0.4 1.4 0.5 779.0 67.3 358.7 242.7 -435.0 6

8.2-8.2 289 289 289 44.3 43.7 43.9 0.1 1.9 1.5 1.7 0.1 278.5 214.1 243.6 19.5 44.3 P

7 8.2-8.1 289 288 289 44.1 43.5 43.6 0.2 1.5 1.0 1.3 0.2 221.6 142.8 182.6 22.9

-29.3 8

8.2-8.1 301 289 291 44.6 43.7 44.1 0.4 2.1 1.1 1.7 0.3 307.2 158.8 240.5 45.4-

-97.8 9

8.2-8.1 301 288 291 44.4 43.6 43.9 0.2 2.5 1.4 1.9 0.3 371.2 202.3 275.4 51.5

-70.1 10 8.2-8.1 301 286 291 43.4 42.8 43.2 0.1 2.4 1.2 1.8 0.3 355.0 176.0 267.0 52.3

-70.0 11 8.2-8.1 301 288 290 44.1 42.9 43.4 0.4 2.4 1.0 1.7 0.4 349.8 146.8 240.8 58.C

-84.2 12 8.2-8.1 912 289 800 44.1 43.6 43.8 0.2 2.2 1.6 1.9 0.2 1012.7 318.6 761.2 190.4 338.2 13 8.2-8.1 593 301 340 44.9 44.0 44.3 0.3 2.1 0.3 1.4 0.5 547.5 40.5 249.2 136.9 -261.1 14 8.2-8.1 316 303 306 44.8 44.1 44.4 0.2 2.3 0.7 1.6 0.5 354.5 110.8 246.3 78.2 -120.5 15 8.2-8.1 316 303 306 45.1 43.7 44.4 0.4 2.1 0.8 1.5 0.4 314.2 119.2 236.2 61.9 97.6 16 8.2-8.0 316 300 305 45.t 44.5 45.1 0.4 2.1 0.7 1.5 0.4 321.3 110.8 227.7 68.3

-67.2 17 8.2-8.1 608 303 384 45.8 45.4 45.7 0.1 1.8 1.2 1.6 0.2 506.5 187.7 305.9 110.5 227.2 18 8.2-8.1 608 607 608 45.8 44.4 44.8 0.4 1.6 1.0 1.3 0.2 497.7 309.2 3%.2 50.4 114.3 19 8.1-8.1 912 304 634 44.4 43.9 44.1 0.1 1.8 1.5 1.7 0.1 803.5 261.4 528.7 231.1 -506.5 20 8.1-8.1 316 304 305 45.5 44.0 44.6 0.6 2.0 0.6 1.4 0.5 303.1 85.3 208.7 75.7

-84.7 21 8.2-8.1 315 304 305 46.3 45.2 45.7 0.4 2.2 1.0 1.5 0.4 330.4 151.2 223.7 55.2

-90.4 22 8.1-8.1 316 304 306 46.6.45.6 46.1 0.4 2.2 0.0 1.2 0.6 341.7 0.0 181.4 98.1

-82.5 23 8.1-8.1 304 304 304 46.8 46.2 46.5 0.2 1.8 0.0 1.1 0.6 279.3 0.0 164.8 97.2 -124.5 24 8.1-8.0 304 301 304 46.3 45.5 45.9 0.3 2.0 1.3 1.7 0.2 311.5 205.6 261.3 28.9 52.2 2$

8.1-C.0 346 42 269 46.0 45.3 45.7 0.2 2.3 1.1 1.7 0.3 311.1 37.1 223.6 97.2 -256.9 26 8.1-8.0 506 346 371 46.9 45.7 46.2 0.4 2.0 0.2 1.4 0.6 492.4 28.7 255.1 129.2 -180.8 27 8.1-8.0 358 54 93 48.5 46.3 47.3 0.8 2.7 1.0 1.7 0.6 272.7 26.1 77.2 76.2 -229.2 28 8.1-8.0 54 54 54 48.2 47.3 47.9 0.3 2.8 1.8 2.3 0.3 75.8 47.8 63.0 9.4 8.2 1

29 8.3-8.0 66 54 56 49.2 47.5 48.1 0.6 3.9 2.6 3.2 0.4 125.6 70.6 89.3 16.0 23.9 30 8.2-7.9 65 54 55 30.5 47.4 48.8 1.1 4.2 1.1 2.4 0.7 129.1 28.6 66.4 23.0

-73.7 4

MON 8.3-7.9 912 42 319 50.5 41.6 44.9 1.8 4.2 0.0 1.7 0.6 1012.7 0.0 252.7 165.1 -506.5 PM RANGE = LOWEST AND HIGNEST PM AT QUARRY CUT (PN UNITS)

FLOW RANGE = LOWEST AND HIGNEST FLOW FROM GUARRY CUT (10**3 GAL / MIN)

MAX TEMP = MAXIMUM TEMPERATURE AT DISCHARGE AREA (DEG F) f CIN TEMP = MINIMUM TEMPERATURE AT DISCHARGE AREA (DEG F)

AVG TEMP = AVERAGE TEMPERATURE AT DISCHARGE AREA (DEG F)

SDEV TEMP = STANDAR0 DEVIATION OF TEMPERATURE AT DISCHARGE AREA (DEG F)

MAX DEL T = MAXIORJM TEMPERATURE INCREASE BETWEEN INTAKE Am GUARRY CUT (DEG F)

KI3 DEL T = MINIMUM TEMPERATURE INCREASE SETWEEN INTAKE A2 QUARRY CUT (DEG F)

AVG DEL T = AVERAGE TEMPERATURE INCREASE SETWEEN INTAKE AND QUARRY CUT (DEG F)

SDEV DEL T = STASARD DEVIATION OF TEIN*ERATURE INCREASE BETWEEN INTAKE A 2 QUARRY CUT (DEG F)

MAX NL = MANIMUM NEAT LOAD OF DISCNARGE WATER (10**6 BTU /NR)

MI3 HL = MINIMUM NEAT LOAD OF DISCHARGE WATER (10**6 STU/NR)

AVG NL a AVERAGE HEAT LOAD OF DISCHARGE WATER (10**6 BTU /NR)

SD NL = STANDARD DEVIATION OF NEAT LOAD OF DISCHARGE WATER (10**6 BTU /NR)

MRC ML = MAXIMUM RATE OF CHANGE OF NEAT LOAD (NL FOR QUARTER HOUR T MINUS NL FOR QUARTER HOUR T-1/ QUARTER MOUR) (10**6 BTU /NR**2)

        • MEANS MISSING OR INSUFFICIENT DATA (LESS TNAN 12 NRS/ DAY OF VALID NOURLY DATA; LESS THAN 360 NRS/ MONTH OF VALID NOURLY DATA) i

_ - _ ~

TABLE 1, Page 2 trLLST ONE STATION / ALL UNITS MONTHLY WATER QUALITY DATA SUIN4ARY / DISCHARGE SERIAL NUMBER 001 ENCEPTION REPORT FOR MA11 MUM TEMPERATURE DIFFERENCE FROM INTAKE AREA TO QUARRY CUT GREATER THAN 32 DEG F r

1 NOME EXCEPTIDW REPORT FOR MAXIMUM QUARRY TEMPERATURE GREATER THAN 105 DEG F NONE EXCEPTION REPORT FOR PM AT QUARRY CUT LESS TMAN 6.0 OR GREATER THAN 9.0 PH UNITS NONE i

U i

h e

1 i

?

L

[

TABLE 1. Page.3 l

C'ILLSTONE STATION / UNIT 1

{

MONTMLY W TER QUALITY DATA SUINtARY / DISCHARGE SERIAL NUMBER 001A DATA PE210D = 1 APR 97/0000 - 30 APR 97/2345 DATA ACQUISITION INTERVAL = MINUTES 00-15 0F EACM NOUR DAY PH RANGE FL0st RANGE CIRC PUMP MAX MIN AVG SDEV MAX MIN AVG SDEV MAX ML MIN ML AVG NL SD NL MRC NL L

MAX MIN AVG MAX MIN TEMP TEMP TEW TEMP DEL T DEL T DEL T DEL T 1

7.9-7.8 0

0 0

0 0 45.0 42.0 42.9 1.3 5.4 1.8 3.1 1.3 0.4 0.0 0.0 0.1

-0.4 2

8.0- 7.8 10 0

1 0

0 47.9 41.7 43.5 2.1 7.3 1.3 3.4 2.0 11.4 0.0 1.0 3.2 11.0 3

8.0- 7.9 10 0

0 0

0 48.6 41.9 44.2 2.0 7.0 1.1 3.3 2.0 29.0 0.0 1.2 5.9

-29.0 4

8.0- 7.8 6

0 0

0 0 50.6 42.8 45.2 2.3 8.6 1.4 3.5 2.2 11.5 0.0 1.1 3.2

-11.0 5

8.0- 7.8 8

0 0

0 0 50.9 43.3 45.8 2.2 8.9 1.3 3.7 2.5 28.6 0.0 1.2 5.8

-28.6 3

6 8.0- 7.9 0

0 0

0 0 49.5 43.5 45.6 2.0 7.4 1.4 3.3 L9 0.0 0.0 0.0 0.0 0.0

[

7 8.0- 7.8 0

0 0

0 0 50.3 43.5 46.5 2.5 7.8 1.5 4.2 2.5 0.2 0.0 0.0 0.1

-0.2 L

8 8.0- 7.9 11 0

1 0

0 49.6 43.6 45.9 2.3 6.5 1.4 3.5 2.0 35.0 0.0 3.3 9.2

-30.5 f

9 7.9-7.8 12 0

1 0

0 49.9 43.3 46.4 2.5 7.5 1.8 4.4 2.1 26.8 0.0 2.3 6.5

-13.5 10 8.0- 7.8 12 0

2 0

0 49.2 42.8 46.0 2.3 8.2 1.8 4.6 2.2 12.2 0.0 1.9 4.3 12.0 11 8.0- 7.8 11 0

1 0

0 49.3 43.4 45.7 1.9 7.8 1.8 3.9 1.7 14.0 0.0 1.1 3.6

-13.8 s

12 8.0- 7.8 2

0 0

0 0 49.4 44.0 45.1 1.5 7.8 2.1 3.2 1.7 2.1 0.0 0.1 0.4

-2.1 l

13 8.0- 7.8 0

0 0

0 0 48.9 44.3 46.4 1.3 5.3 2.1 3.5 0.9 0.0 0.0 0.0 0.0 0.0 14 8.0- 7.8 12 0

2 0

0 50.3 44.1 47.0 2.2 7.9 1.0 4.2 2.3 22.5 0.0 2.6 5.9 14.3 l

15 8.0- 7.8 12 0

2 0

0 50.7 44.0 46.6 2.1 7.4 1.2 3.7 2.0 23.6 0.0 2.6 6.2 13.1 18 8.0- 7.8 11 0

0 0

0 52.4 44.6 47.8 2.7 8.4 0.9 4.2 2.7 39.3 0.0 1.8 8.0

-39.3 17 7.9-7.8 12 0

1 0

0 51.9 45.4 47.7 2.2 7.6 1.5 3.6 2.1 41.5 0.0 1.8 8.6 41.5 18 7.9-7.8 0

0 0

0 0 49.9 44.4 45.7 1.7 5.8 1.0 2.3 1.6 0.0 0.0 0.0 0.0 0.0 17 7.9-7.8 0

0 0

0 0 49.7 44.0 45.9 1.5 7.1 1.7 3.5 1.4 0.0 0.0 0.0 0.0 0.0 l

3 20 7.9-7.8 12 0

1 0

0 48.9 44.2 46.1 1.5 5.2 0.9 2.8 1.4 23.4 0.0 1.5 5.3

-23.4 21 7.9-7.8 12 0

1 0

0 51.8 45.1 48.1 2.4 7.2 1.5 3.9 2.3 33.0 0.0 1.7 6.9

-33.0 22 7.9-7.8 12 0

1 0

0 52.5 45.5 48.5 2.6 8.0 0.4 3.6 2.6 33.9 0.0 3.3 8.8

-25.1 23 7.9-7.8 0

0 0

0 0 53.1 46.3 48.7 2.4 7.7 1.0 3.3 2.0 0.0 0.0 0.0 0.0 0.0 24 7.9-7.7 0

0 0

0 0 42.0 45.3 47.3 2.2 7.2 1.4 3.1 2.0 0.0 0.0 0.0 0.0 0.0 t

25 7.9-7.7 12 0

1 0

0 'IP.5 45.5 48.6 2.4 8.2 1.8 4.7 2.2 12.9 0.0 0.8 2.8 12.9 26 7.9-7.8 8

0 1

0 0 50.3 46.5 48.0 1.2 4.0 2.3 3.2 0.5 9.6 0.0 1.2 2.8

-8.3 27 7.9-7.8 11 0

1 0

0 49.9 47.6 48.6 0.7 4.5 1.9 3.1 0.7 17.6 0.0 1.8 4.9

-14.7 28 7.8-7.8 0

0 0

0 0 53.1 48.2 49.7 1.6 7.2 2.2 4.1 1.5 0.0 0.0 0.0 0.0 0.0 29 7.9-7.8 12 0

2 0

0 50.6 47.8 49.1 0.7 5.2 2.9 4.1 0.7 24.2 0.0 3.8 8.8 23.4 i

30 7.9-7.7 11 0

2 0

0 53.2 47.9 50.1 1.7 5.2 2.1 3.7 0.9 27.4 0.0 3.3 7.9 15.3 MON 8.0- 7.7 12 0

1 0

0 53.2 41.7 46.8 2.6 8.9 0.4 3.6 1.9 41.5 0.0 1.3 5.2 41.5 PN RANGE = LOWEST AND HIGHEST PM AT DISCHARGE STRUCTURE (PN UNITS)

FLOW RANGE = LOWEST AND NIGNEST FLOW FROM DISCHARGE STRUCTURE (10**3 GAL / MIN) i CIRC PU W = LOWEST AND HIGNEST IRSt9ER OF CIRC PUMPS OPERATING MAX TEMP = MAXIRSt TEMPERATURE AT DISCHARGE STRUCTURE (DEG F)

MIN TEMP = MINIMUM TEMPERATURE AT DISCHARGE STRUCTURE (DEG F)

AVG TE W = AVERAGE TEMPERATURE AT DISCHARGE STRUCTURE (DEG F) l' SDEV TEM = STAWARD DEVIATION OF TEMPERATURE AT DISCHARGE STRUCTURE (DEG F)

MAX DEL T = MAXIMUM TEMPERATURE INCREASE SETWEEN INTAKE AND DISCHARGE (DEG F)

MIM DEL T = MINIMUM TEMPERATURE INCREASE SETWEEN INTAKE Am DISCHARGE (DEG F)

[

AVG DEL T = AVERAGE TEMPERATURE INCREASE SETWEEN INTAKE AIS DISCHARGE (DEG F)

~

SDEV DEL T = STANDARD DEVIATION OF TEWERATURE INCREASE SETWEEN INTAKE AND DISCNARGE (DEG F)

MAX NL = MAXIMUM MEAT LOAD OF DISCHARGE WATER (10**6 BTU /NR)

Mt:I NL = MINIMUM MEAT LOAD OF I;ISCHARGE WTER (10**6 BTU /NR)

AVG NL = AVERAGE HEAT LOAD OF DISCHARGE W TER (10**6 BTU /NR)

SP NL = STANDARD DEVIATION OF MEAT LOAD OF DISCHARGE WTER (10**6 STU/NR)

MRC NL = MAXIRSI RATE OF CHANGE OF MEAT LOAD (NL FOR QUARTER NOUR T MINUS NL FOR QUARTER NOUR T-1/ QUARTER NOUR) (10**6 BTU /NR**2)

        • MEANS MISSING OR INSUFFICIENT DATA (LESS THAN 12 NRSA.J.Y OF VALID MOURLY DATA; LESS THAN 360 MRS/MONTM OF VALID NOURLY DATA) i 5

i 4

. ~ -

-.- s-

- ~

TABLE 1, Page 4 tittST ONE STATION / UNIT 1 MONTMLY WRTE3 00ALITY DATA SUISEARY / DISCHARGE SERIAL NUMBER 001A I

EXCEPTIoni REPORT FOR MAXIMUM TEMPERATURE DIFFERENCE FRON UNIT 1 INTAKE TO UNIT 1 DISCHARGE GREATER THAN 32 DEG F i

N EXCEPTION REPORT FOR MAXIMUM DISCHARGE TENDERATURE AT UNIT 1 DISCHARGE GREATER THAN 105 DEG F NONE y

EXCEPTION REPORT FOR PM AT UNIT 1 DISCHARGE LESS THAN 6.0 OR GREATER THAN 9.0 PM UNITS NOME n

b t

f i

)

[

i s

TABLE 1, Pege 5 MILLSTONE STATION / UNIT 2 MONTMLY WATER QUALITY DATA Supe 44RY / DISCHARGE SERIAL NUMBER C018 DATA PERIOD = 1 APR 97/0000 - 30 APR 97/2345 DATA ACQUISITION INTERVAL = MINUTES 00-15 0F EACH HOUR DAY PN RANGE FLOW RANGE CIRC PUMP MAX MIN AVG SDEV MAX MIN AVG SDEV MAX HL MIN HL AVG HL SD HL MRC HL MAX MIN AVG MAX MIN TEMP TEMP TEMP TEMP DEL T DEL T DEL T DEL T 1

8.0- 7.9 274 274 274 2

2 41.9 41.4 41.8 0.2 0.6 0.3 0.5 0.1 81.3 34.6 62.1 12.6

-28.7 2

8.0- 7.9 274 273 274 2

1 42.5 41.3 41.9 0.4 0.9 0.2 0.6 0.2 123.1 26.5 81.9 24.7

-40.3 3

8.1-7.9 2 74 2 74 274 2

2 43.5 41.5 42.4 0.6 0.7 0.0 0.5 0.2 101.9 0.7 62.5 23.7

-73.4 4

8.1-8.0 274 274 274 2

2 44.0 42.6 43.2 0.5 1.1 0.3 0.6 0.2 153.0 42.8 83.3 31.5 49.9 5

8.1-8.0 274 274 274 2

2 44.8 42.6 43.6 0.7 0.7 0.0 0.4 0.2 92.0 0.0 50.6 29.2 51.7 6

8.0- 8.0 274 274 274 2

2 44.2 43.0 43.6 0.3 0.4 0.1 0.3 0.1 61.1 14.6 38.1 13.9

-37.1 7

8.0- 7.9 274 273 274 2

1 44.7 43.1 43.8 0.5 1.0 0.0 0.5 0.3 133.5 0.0 62.5 36.7 54.6 8

8.1-8.0 274 274 274 2

2 45.1 43.1 44.2 0.7 0.8 0.1 0.4 0.2 109.5 10.4 53.8 25.2 55.4 9

8.0- 8.0 274 273 274 2

1 44.2 43.0 43.5 0.3 0.7 0.0 0.4 0.2 98.1 5.2 52.0 20.9

-48.7 10 8.0- 7.9 274 271 274 2

1 43.6 42.4 43.0 0.4 0.9 0.1 0.4 0.2 119.4 10.6 57.4 32.2 41.5 11 8.0- 7.9 274 273 274 2

1 44.3 42.6 43.4 0.6 0.7 0.2 0.5 0.1 101.4 26.3 62.4 20.5 48.2 12 8.0- 7.9 274 273 274 2

1 44.1 43.3 43.7 0.3 0.6 0.2 0.4 0.1 78.6 32.6 54.2 10.8

-30.9 13 8.0- 7.9 274 271 274 2

1 45.4 43.6 44.4 0.5 0.6 0.0 0.3 0.2 79.1 0.0 43.9 24.8

-61.8 14 8.0- 7.9 274 2 73 274 2

1 44.9 43.7 44.3 0.4 0.5 0.1 0.4 0.1 74.5 19.3 56.6 16.6

-37.8 15 8.0- 7.9 274 273 274 2

1 45.3 43.2 44.3 0.7 0.7 0.0 0.4 0.2 95.4 0.0 52.8 23.3 55.9 16 8.0- 7.9 274 270 274 2

1 46.2 44.2 45.2 0.7 0.5 0.0 0.3 0.2 68.7 0.0 38.3 21.5

-61.6 17 8.0- 8.0 274 273 274 2

1 45.9 44.7 45.5 0.3 0.5 0.0 0.2 0.1 70.2 0.0 32.9 18.1

-40.8 18 8.0- 7.9 274 2 73 274 2

1 45.3 44.3 44.5 0.3 0.5 0.0 0.3 0.1 73.9 6.7 37.7 17.2 55.1 19 8.0- 7.9 274 274 274 2

2 44.2 43.8 44.0 0.1 0.5 0.2 0.4 0.1 69.5 29.7 50.2 10.2

-26.5 20 8.0- 7.9 274 2 74 274 2

2 46.1 43.8 44.8 0.8 0.6 0.0 0.3 0.2 84.8 0.0 45.3 21.9

-64.8 21 8.0- 7.9 274 2 73 274 2

1 46.7 44.7 45.6 0.7 0.6 0.0 0.4 0.2 84.8 0.0 51.6 22.1 63.8 22 8.0- 7.9 274 274 274 2

2 47.3 44.7 46.1 0.8 0.6 0.0 0.2 0.2 76.4 0.0 30.0 27.5

-63.5 23 8.0- 7.9 274 274 274 2

2 47.2 45.1 46.3 0.6 0.5 0.0 0.2 0.2 70.0 0.0 24.9 24.0 65.3 24 7.9-7.8 274 271 274 2

1 46.3 44.9 45.5 0.4 0.5 0.2 0.3 0.1 64.5 28.5 44.6 8.6 30.9 25 7.9-7.7 274 12 99 2

0 47J 44.9 46.1 0.9 2.2 0.3 1.0 0.6 56.9 1.9 20.0 18.3

-36.1 26 7.9-7.7 24 12 17 0

0 48.3 45.9 47.3 0.7 2.2 0.8 1.5 0.4 23.6 5.1 12.6 5.6.

6.2 27 7.9-7.7 24 24 24 0

0 49.4 46.9 48.0 0.8 2.6 0.7 1.5 0.4 30.6 8.5 18.6 5.0 14.3 28 7.9-7.8 24 24 24 0

0 48.7 41.6 48.2 0.3 2.0 1.3 1.6 0.2 24.1 16.1 18.9 1.9 4.9 29 7.8-7.8 24 24 24 0

0 48.2 47.0 47.7 0.4 2.4 1.3 1.7 0.3 28.6 16.1 20.9 3.7

-7.6 30 7.7-7.7 24 24 24 0

0 51.0 47.4 48.9 1.3 2.8 1.0 1.5 0.4 34.1 11.4 17.9 4.3

-20.8 MON 8.1-7.7 274 12 226 2

0 $1.0 41.E 44.9 1.9 2.8 0.0 0.6 0.5 153.0 0.0 44.2 27.2

-73.4 PH RANGE = LOWEST AND HIGHEST PM AT DISCHARGE STRUCTURE (PH UNITS)

FLOW RANGE = LOWEST AND HIGHEST FLOW FROM DISC ENGE STRUCTURE (10**3 GAL / MIN)

CIRC PUMP = LOWEST AND HIGHEST NtmBER OF CIRC PU W S OPERATING MAX TEMP = MAXIMUM TEMPERATURE AT DISCHARGE ETRUCTURE (DEG F) l MIN TEMP = MINIMUM TEMPERATURE AT DISCHARGE STRUCTURE (DEG F)

LVG TEMF = AVERAGE TEMPERATURE AT DISCHARGE STRUCTURE (DEG F)

SDEV TEMP = STANDARD DEVIATION OF TEMPERATURE AT DISCHARGE STRUCTURE (DEG F)

MAX DEL T = MAXIMUM TEWERATtitE INCREASE BETWEEN INTAKE AND DISCHARGE DEG F)

KI2 DEL T = MINIMUM TEMPERATURE INCREASE BETWEEN INTAKE AND DISCHARGE (DEG F)

AVG DEL T = AVERAGE TEMPERATURE INCREASE BETWEEN INTAKE A W DISCHARGE (DEG F)

SDEV DEL T = STANDARD DEVIATION OF TEMPERATURE INCREASE BETWEEN INTAKE AND DISCHARGE (DEG F)

MAX CL = MAXIMUM HEAT LOAD OF DISCHARGE WATER (10**6 BTU /HR)

MI HL = MINIMUM HEAT LOAD OF DISCHARGE WATER (10**6 BiU/NR)

AVG ML = AVERAGE HEAT LOAD OF DISCHARGE WATER (10**6 BTU /NR)

SD HL = STANDARD DEVIATION OF MEAT LOAD CF DISCHARGE WATER (10**6 BTU /HR)

MRC HL = MAXIMUM RATE OF CHANGE OF MEAT LOAD (NL FOR QUARTER HOUR T MINUS HL FOR QUARTER HOUR T-1/ QUARTER HOUR) (10**6 BTU /HR**2)

        • MEANS MIS $1NG OR INsufflCIENT DATA (LESS THAN 12 HRS / DAY OF VALID HOURLY DATA; LESS THAN 360 HRS /MOKTH OF VALID HOURLY DATA)

TABLE 1. Ptge 6

~

EI[Lst ONE STATION / UNIT 2 f

MONTMLY WATER QUALITY DATA StAetARY / DISCHARGE SERIAL NtASER 0018 EXCEPTION REPORT FOR MAXIMLM TEWERATURE DIFFERENCE FROM UNIT 2 INTAKE TO UNIT 2 DISCHARGE GREATER THAN 32 DEG F EXCEPTION REPORT FOR MAXIMLM DISCHARGE TEMKeATURE AT UNIT 2 DISCHARGE GREATER THAN 105 DEG F NOME EXCEPTION REPORT FOR PM AT UNIT 2 DISCHARGE LESS TMAN 6.0 OR GREATER THAN 9.0 PH UNITS t

..s,-

m m

m m

m

TABLE 1, Pcge 7 MILLSTONE STATION / UNIT 3 MONTHLY WATER SCALITY DATA SUMARY / DISCHARGE SERIAL NLMBER 001C DATA PERIOD = 1 APR 97/0000 - 30 APR 97/2345 DATA ACQUISITION INTERVAL = MINUTES 00-15 0F EACH HOUR DAY PH RANGE FLOW RANGE CIRC PUMP MAX MIN AVG SDEV MAX MIN AVG SDEV MAX HL MIN HL AVG HL SD HL MRC HL MAX MIN AVG MAX MIN TEMP TEMP TEMP TEMP DEL T DEL T DEL T DEL T 1

8.2-8.1 30 30 30 0

0 42.1 41.7 42.0 0.1 1.1 0.5 0.7 0.2 15.8 7.5 10.6 2.8 2.2 2

8.2-8.1 30 15 18 0

0 42.9 41.9 42.4 0.4 1.6 0.7 1.1 0.2 20.0 6.6 10.1 3.0

-9.1 3

8.2-8.1 15 15 15 0

0 43.4 42.5 42.9 0.3 1.6 0.0 1.0 0.4 11.8 0.0 7.8 3.2 7.1 4

8.2-8.1 15 15 15 0

0 43.9 43.3 43.6 0.2 1.3 0.2 0.9 0.3 9.6 1.6 7.1 2.0 4.8 5

8.2-8.1 623 15 243 4

0 44.8 41.9 43.3 0.9 1.6 0.0 0.4 0.5 248.3 0.0 12.7 50.3 -248.3 6

8.2-8.1 15 15 15 0

0 44.9 43.7 44.2 0.4 1.7 0.5 0.9 0.3 12.9 3.6 7.1 2.3

-5.0 7

8.2-8.1 15 15 15 0

0 44.5 43.6 44.0 0.3 1.5 0.1 0.7 0.3 11.1 0.5 5.3 2.4 7.4 8

8.2-7.9 15 15 15 0

0 45.2 43.8 44.5 0.6 1.7 0.0 0.8 0.5 12.5 0.0 6.0 4.0 4.9 9

8.2-8.0 15 15 15 0

0 44.7 44.1 44.3 0.2 1.6 0.8 1.2 0.2 11.7 6.0 9.0 1.3 2.0 10 8.2-8.0 15 15 15 0

0 44.1 43.4 43.7 0.2 1.7 0.9 1.2 0.2 12.7 6.6 9.0 1.5 4.8 11 8.2-8.1 15 15 15 0

0 45.0 43.6 44.1 0.5 1.9 0.8 1.2 0.3 14.6 6.0 9.0 2.4 6.0 12 8.2-8.1 638 15 525 4

0 44.6 42.6 43.2 0.5 1.5 0.0 0.2 0.4 188.8 0.0 8.7 38.5 -185.8 13 8.2-8.1 319 30 66 2

0 45.0 43.1 44.1 0.6 1.0 0.0 0.3 0.4 15.2 0.0 4.4 5.3

-9.8 14 8.2-8.1 30 30 30 0

0 44.6 43.6 44.1 0.3 0.8 0.0 0.3 0.3 11.9 0.0 4.3 3.8 5.6 15 8.2-8.1 30 30 30 0

0 45.3 43.7 44.4 0.6 0.9 0.0 0.5 0.3 13.6 0.0 7.4 3.8

-7.9 16 8.2-8.1 30 30 30 0

0 46.0 44.3 45.2 0.5 0.9 0.0 0.3 0.3 12.8 0.0 4.9 3.9

-8.6 17 8.2-8.1 334 30 106 2

0 46.4 44.3 45.4 0.6 1.4 0.0 0.3 0.4 20.6 0.0 3.9 5.7

-10.6 18 8.1-8.1 334 334 334 2

2 44.0 43.3 43.6 0.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19 8.2-8.0 638 30 359 4

0 44.7 43.0 43.5 0.6 1.2 0.0 0.2 0.4 17.8 0.0 3.6 5.9 12.7 20 8.1-8.0 30 30 30 0

0 45.8 44.3 45.0 0.6 1.3 0.0 0.6 0.4 19.5 0.0 8.4 5.8 8.9 21 8.2-8.0 30 30 30 0

0 46.9 45.2 45.9 0.6 1.3 0.1 0.6 0.3 19.5 2.0 9.5 5.2 9.0 22 8.1-8.0 30 30 30 0

0 47.0 45.2 46.1 0.5 1.1 0.0 0.3 U.4 16.7 0.0 5.1 6.1 4.7 23 8.1-8.0 30 30 30 0

0 47.0 45.4 46.2 0.5 0.8 0.0 0.2 0.3 11.5 0.0 3.6 3.8 11.3 24 8.1-8.0 30 30 30 0

0 46.1 45.1 45.5 0.3 0.7 0.0 0.3 0.2 10.5 0.0 5.2 2.4

-6.8 25 8.1-8.0 334 30 169 2

0 45.5 44.8 45.2 0.2 0.7 0.0 0.2 0.3 10.8 0.0 3.2 3.8

-6.4 26 8.2-8.1 486 334 353 3

2 46.9 44.7 45.4 0.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27 8.1-8.0 334 30 68 2

0 47.9 45.2 46.5 0.9 0.6 0.0 0.2 0.2 8.8 0.0 2.6 3.1

-8.8 28 8.1-8.0 30 30 30 0

0 47.4 46.4 47.0 0.3 0.7 0.1 0.4 0.2 10.8 1.7 6.2 2.5

-8.4 29 8.1-7.9 30 30 30 0

0 46.7 46.0 46.4 0.2 0.7 0.0 0.4 0.2 9.8 0.2 6.4 2.4 9.0 30 8.1-8.0 30 30 30 0

0 48.7 46.7 47.4 0.8 0.9 0.0 0.3 0.3 13.2 0.0 4.4 4.2

-8.0 MON 8.2-7.9 638 15 91 4

0 48.7 41.7 44.7 1.4 1.9 0.0 0.5 0.5 248.3 0.0 6.1 12.4 -248.3 PH RANGE = LOWEST AND HIGHEST PM AT DISCHARGE STRUCTURE (PH UNITS)

FLOW RANGE = LOWEST AND HIGHEST FLOW FROM DISCHARGE STRUCTURE (10**3 GAL / MIN)

CIRC PUMP = LOWEST AND HIGHEST NUMBER OF CIRC PUMPS OPERATING MAX TEMP = MAXIIRJM TEMPERATURE AT DISCHARGE STRUCTURE (DEG F)

MIN TEMP = MFNIMUM TEMPERATURE AT DISCHARGE STRUCTURE (DEG F)

AVG TEMP = AVERAGE TEMPERATURE AT DISCHARGE STRUCTURE (DEG F)

SDEV TEMP = STANDARD DEVIATION OF TEMPERATURE AT DISCHARGE STRUCTURE (DEG F)

MAX DEL T = MAXIMUM TEMPERATURE INCREASE BETWEEN IMTAKE AND DISCMARGE (DEG F)

Cl3 DEL T = MINIMUM TEMPERATURE INCREASE BETWEEN INTAKE AND DISCHARGE (DEG F)

AVG DEL T = AVERAGE TEW ERATURE INCREASE BETWEEN INTAKE AND DISCHARGE (DEG F)

SDEV DEL T = STANDARD DEVIATION OF TEMPERATURE INCREASE BETWEEN INTAKE AND DISCHARGE (DEG F)

MAX HL = MAXIMUM HEAT LOAD OF DISCHARGE WATER (10**6 BTU /HR)

MIN HL = MINIMUM HEAT LOAD OF DISCHARGE WATER (10**6 8TU/HR)

AVG NL = AVERAGE HEAT LOAD OF DISCHARGE WATER (10**6 BTU /HR)

SD HL = STANDARD DEVIATION OF HEAT LOAD OF DISCHARGE WATER (10**6 8TU/NR) i MRC HL = MAXIMUM RATE OF CHANGE OF HEAT LOAD (HL FOR QUARTER HOUR T MINUS hL FOR QUARTER HOUR T-1/ QUARTER HOUR) (10**6 BTU /HR**2)

        • MEANS MISSING OR INSUFFICIENT DATA (LESS THAN 12 HRS / DAY OF VALID HOURLY DATA; LESS THAN 360 HRS / MONTH OF VALID HOURLY DATA)

TABLE 1, Page 8 I $

ONE STATION / UNIT 3 140NTMLY WATER QUALITY DATA StpetARY / DISCHARGE SERIAL NUMBER 001C i

EXCEPil0K REPORT FOR stAXINim TEfqPERATURE DIFFERENCE FRON UNIT 3 INTAKE TO UNIT 3 DISCHARGE GREATER THAN 24 DEG F e

NOME i

EXCEPTION REPORT FOR NAXINUN DISCHARGE TEMPERATURE AT UNIT 3 DISCHARGE GREATER THAN 98 DEG F NOME r

EXCEPTION REPORT FOR PM AT UNIT 3 DISCHARGE LESS TMAM 6.0 OR GREATER THAN 9.0 PM UNITS NONE r

i 1

I t

5 I

TABLE 2 MP.aaTONE STATION DMR Attached Reporting Month: ADril 1997 The following reporting will be done to accurately reflect the l

permit:

i 1)

Loadings and concentrations within permit limits will not be reported as an exceedance where the DMR forms lists incorrect i

values.

2)

Parameter blanks not required by the permit will be marked N/A.

i 3)

Parameter reporting not shown on the DMR forms, but required by l

the permit will be listed in this attachment.

DSN 001 Flow is permitted as maximum 2,738,000,000 gpd. However, this flow is an average flow value which was defined in the previous permit. The renewed permit changed flow nomenclature to maximum and as such flow will exceed the limit in most months.

This problem is being addressed through permit modification, and is not being reported as an exceedance.

DSN 001A Flow is permitted as maximum 604,800,000 gpd.

However, this flow is an average flow value which was defined in the previous permit. The renewed permit changed flow nomenclature to maximum and as such flow will exceed the limit in most months.

This problem is being addressed through permit I

modification, and is not being reported as an exceedance.

DSN 001A-4 The following parameters are not included on the DMR forms:

Boric acid:

Code 9 mg/l (weekly grab, 574 mg/l max)

Boric acid:

Code 9 kg/ day (weekly grab, 7.6 kg/ day max)

DSN 00 3 Flow is permitted as maximum 820,000,000 gpd.

However, this flow is an average flow value which was defined in the previous permit. The renewed permit changed flow nomenclature to maximum and as such flow will exceed the limit in most l

months.

This problem is being addressed through permit modification, and is not being reported as an exceedance.

DSN 001B-1 The following parameters are not included on the DMR forms:

Ethanolamine:

No Discharae mg/l (weekly grab, 10.0 mg/l max)

I l

i i

Millstono DMR Tcblo 2 Page 2 DSN 001B-1(a)

The following parameters are not included on the DMR forms:

I Ethanolamine:

5 mg/l (daily grab, 5.0 mg/l max)

DSN 001B-2 The DMR form has an average TSS limit of 30.0 mg/1.

This is not in the permit.

DSN 001B-2 (b)

The following parameters are not included on the DMR forms:

Nitric acid:

_gg Discharoe mg/l (daily comp.)

Permanganate:

No Discharoe mg/l (daily comp.)

DSN 001B-3 The DMR form has an average TSS limit of 15. 0 mg/1, and a maximum TSS limit of 30.0 mg/1.

This is inconsistant with the permit which has only a maximum TSS limit of 22.5 mg/1.

DSN 001B-6 The following parameters are not included on the DMR forms:

Ethanolamine:

0.097 kg/ batch (weekly grab, 230 kg max)

DSN 001B-7 The DMR form has a maximum chlorine loading limit of 5.46 kg/ day.

This is inconsistant with the permit which does not have a chlorine loading limit.

DSN 001B-8 The following parameters are not included on the DMR forms:

Ethanolamine:

No Discharce mg/l (daily grab, 230 mg/l max)

DSN 001C Flow is permitted as maximum 1,313,200,000 gpd. However, this flow is an average flow value which was defined in the previous permit. The renewed permit changed flow nomenclature to maximum and as such flow will exceed the limit in most months.

This problem is being addressed through permit modification, and is not being reported as an exceedance.

A reporting block for Pimenhales oromelas toxicity testing is on the DMR form but is not required by the pennit.

_m.

Milletons DMR Table 2 Page 3 DSN 001C-1 The following parameters are not included on the DMR forms:

s Ethanolamine:

No Discharae mg/l (15.0 mg/l max)

DSN 001C-1(a) l The following parameters are not included on the DMR forms:

1 Ethanolamine:

No Discharae mg/l (5.0 mg/l max) i DSN 001C-6 The following parameters are not included on the DMR forms:

l Ethanolamine:

0.24 kg/ batch (300.0 kg/ batch max)

DSN 001C-6(a)

The following parameters are not included on the DMR forms:

Nitric acid:

No Discharae mg/l (daily comp.)

l Permanganate:

No Discharae mg/l (daily comp.)

1 i

DSN 001C-8 The following parameters are not included on the DMR forms:

j Ethanolamine:

No Discharae mg/l (3.0 mg/l max)

~i i

DSN 006 Two sets of forms have been supplied for this discharge.

Toxicity testing for Pimephales oromelas is on the DMR form, but is not required on by the permit.

i

~ _ _ - -.

- _~..

l-TABLE 3 April 1997 Millstone DSN 006 additional TRC data Week 1 Week 2 Week 3 Week 4 Week 5 I

l

<0.02

<0.02 0.03 0.04

<0.02 l

<0.02

<0.02 0.02 0.03

<0.02 i

<0.02

<0.02 0.02 0.02 0.02 l

<0.02 0,02 0.02 0.02

<0.02

<0.02

<0.02 0.02 0.02 0.04 0.05

<0.02 0.09 0.02 0.07 i

i DSN 001C-5 additional TRC data 1

l Week 1 Week 2 Week 3 Week 4 Week 5 0.13 0.13 0.10 0.15 0.13 0.13 0.12 0.14 0.17 0.16 0.12 0.14 0.13 0.16 0.14 0.14 0.14 0.13 0.18 0.15 0.13 0.13 0.14 0.13 0.13 0.13 0.13 0.13 0.16 0.16 0.15 0.14 0.13 0.13 0.14 0.12 0.16 l

l l

l l

l

4 TABLE 4 l

April 1997 1

DSN 001B-9 Addit (nal Data Date Volume Hydrazine Temperature 4/1/97 3440

<0.350 72 l

4/2/97 1116

<0.350 70 4/3/97 7652

<0.350 74 4/4/97 540

<0.350 72 4/5/97 324

<0.350 71 4/7/97 352

<0.350 70 4/8/97 784

<0.350 71 4/9/97 644

<0.350 69 4/12/97 2680

<0.350 66 4/14/97 1200

<0.350 67 4/15/97 368

<0.350 67 4/16/97 144

<0.350 70 4/24/97 1836

<0.350 50 4/25/97 1008

<0.350 68 DSN 0018-6 Additional Data Date Volume pij TSS 4/14/97 16400 7.31 7.0 4/15/97 18300 6.50 1.0 4/16/97 15200 6.87 4.0 DSN 001 A-2 Additional Data Date Volume TSS TSS Lo@

4/1/97 11100 0.1 0.0042 4/2/97 10750 9.4 0.3829 4/4/97 8050 3.8 0.1159 4/5/97 9250 2.8 0.0981 4/9/97 10950 2.0 0.083 l

4/14/97 10750 1.2 0.0488 4/19/97 10250 1.4 0.0543 4/26/97 9900 0.7 0.0262

/,

e 6

TaWe 5 April 1997 addRional discharoe data 1

pjN 001C-6b

)

pate Temperature Gallons per dav Hydrazine. mall l

4/1/97 190 3070 38 N2/97 195 3270 33

)

N3/97 195 1260 38 N497 195 1740 64 4597 195 1310 33

)

N6/97 180 1140 44 j

N7/97 175 1260 38 4597 175 1210 43 4997

80 1350 43

)

N10/97 190 1430 41 N11/97 180 1460 43 l

N12/97 185 1440 49

- N13/97 185 1630 34 N1N97 185 1290 32 N15/97 180 1230 28 N16/97 190 1190 37 N17/97 180 1090 30 N18/97 180 1140 47 N19/97 180 1180 43 N2097 180 1060 50 N21/97 180 1210 66 N22/97 180 1180 62 N23/97 180 1370 46 N2497 175 1420 42 N25/97 180 1330 36 4/26/97 180 1340 30 477/97 180 1260 50 N28/97 190 1290 40 4"2R97 170 1290 56 N30/97 175 1250 40 DSN 001C-2 pote ConductivRy Gallonstatch pH go_ric M Uthium Source t

4 5/97 0.9 3978 8.45 2.12

<0.1 Boron Test Tank N12/97 20.7 17849 5.60 533.3

<0.1 Weste Test Tank N12,97 15.1 18481 4.37 230.1 Weste Test Tank N18/97 24 8 18490 4.36 788 6

<0.1 Weste Test Tank 4"25/97 54 18901 4.78 654.2

<0.1 Weste Test Tank N25/97 5.9 19110 4.64 489.5

<0.1 Weste Test TarW N27/97 3.5 16800 4 96 354.2

<0.1 Weste Test Tank

<