IR 05000289/1997001

From kanterella
(Redirected from ML20140B725)
Jump to navigation Jump to search
Forwards Insp Rept 50-289/97-01 on 970303-0427.Apparent Violations Being Considered for Escalated Enforcement Action IAW NUREG-1600
ML20140B725
Person / Time
Site: Crane Constellation icon.png
Issue date: 05/29/1997
From: Hehl C
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Langenbach J
GENERAL PUBLIC UTILITIES CORP.
Shared Package
ML20140B728 List:
References
RTR-NUREG-1600 50-289-97-03, 50-289-97-3, EA-97-256, NUDOCS 9706060301
Download: ML20140B725 (4)


Text

May 29, 1997

SUBJECT:

NRC INSPECTION REPORT NO. 50-289/97-03

'

Dear Mr. Langenbach:

On April 27,1997, the NRC completed an inspection at your Three Mile Island 1 reactor facility. The enclosed report presents the results of that inspection.

'

l

,

We noted continued excellent response from operators, supervision, and management for several operational challenges that occurred during the inspection period. In addition, the i

support to the operational organization from radiological control, engineering, and j

maintenance personnel for these events was excellent and timely. In particular, the

'

operations response and evaluation of the reactor coolant drain tank in-leakage was thorough and resulted in determining the source location in a short period of time.

l Based on the results of this inspection, two apparent violations were identified and are being considered for escalated enforcement action in accordance with the " General

/

Statement of Policy and Procedure for NRC Enforcement Actions" (Enforcement Policy),

/

NUREG-1600. First, your staff identified that during the period of about March 17,1986 until March 23,1997, there was not reasonable assurance that the reactor building I

emergency cooling fans, AH-E-1 A,1B, & 1C would have functioned under post-LOCA

,

'

environment conditions because their motors were not environmentally qualified. There was a smalllength of exposed metal between the heat shrink tubing and the spark plug porcelain connector to the motor. In addition, the inspectors concluded that your process for and the timeliness of addressing corrective actions for the condition of AH E-1B & 1C upon identifying the condition of AH-E-1 A was weak.

l The circumstances surrounding these apparent violations, the significance of the issues, j

and the need for lasting and effective corrective action were discussed with members of your staff at the inspection exit meeting on May 1,1997, and later at an enforcement conference involving other issues on May 22,1997. In a telephone conversation between

'

you and Mr. Peter W. Eselgroth of my staff on May 28,1997, Mr. Eselgroth stated that it is not necessary to conduct a predecisional enforcement conference in order to enable the NRC to make an enforcement decision and you stated that you also did not consider such

{

,

a conference to be necessary.

j 060002 N!

_

9706060301 970529 PDR ADOCK 05000289 O

PDR v

i

. _. _. _ _ _. _. _.

.. _.

_._.

.

__

__ _ _ _ _ _.. _. _. _ _ _ _ _... _ _ _... _ _... _ _.

t I

ll'

!

!

!

l Because these are apparent violations no Notice of Violation is presently being issued for

!

these inspection findings, in addition, please be advised that the number and

-

l characterization of apparent violations described in the enclosed inspection report may

[

change as a result of further NRC review.

!

You will be advised by separate correspondence of the results of our deliberations on this matter. No response regarding the apparent violationn is required at this time.

l In accordance with 10 CFR 2.790 of the NRC's " Rules of Practice," a copy of this letter f

and its enclosures will be placed in the NRC Public Document Room (PDR).

l

Sincerely,

.

l Original Signed By-l I

Charles W. Hehl, Director Division of Reactor Projects

!

Docket No.: 50-289

!

License No.: DPR-50

\\

(

l I

t Enclosure: NRC Inspection Report No. 50-289/97-03 cc w/ encl:

!

E. L. Blake, Shaw, Pittman, Potts and Trowbridge (Legal Counsel for GPUN)

'

l J. C. Fornicola, Director, Licensing and Regulatory Affairs B. A. Mehler, PDMS Manager TMI-Alert (TMIA)

i J. S. Wetmore, Manager, TMI Regulatory Affairs l

Commonwealth of Pennsylvania

!

l l

!

!

!

I

.

,y

.-

m..u, n..r, 'ssrlmLg3 tr>.Ta vtW-A:FW4Ar wn?At cisnMt tr

wavse A=:to u. =.. n. s.

_

!'

.

i

!

.

Distrimtion w/ancl:

Regiop i Docket Room (wkh concurrences)

i Nuclear Safety information Center (NSIC)

PUBlic

;

NRC 13esident inspector l!'

W. Axelson, ORA l

P. Esilgroth, DRP D. H4verkamp, DRP J. Nidk, DRP

,

!

C. O'baniell, DRP D. Scronci, PA0 t

Distribution w/ enol (VIA E-MAIL);

W. Dun,OEDO

,

P. Mileno, NRR, PDl-3 i

B. Bu'ckley, PM, NRR, PDI-3 L. Thpnus, NRR/PDNP i

S, W6iss, NRR/PDNP R. Correia, NRR F. Talbot, NRR l

Inspehtlon Program Branch, NRR (IPAS)

DOCDESK

t i

'

!

l

,

I

i.

i.

!

l.

.

DOCUMENT NMME: G:\\ BRANCH 7\\TMi\\TMl97-03, INS

,.

.

..J.

-

-,..-e,,

..

e__.

-c.,,,

-,,s.

.,.n-.

OFFICE RifDM g l l Rl/D M g/

l$

Rl/DgP l_

l f

NAME

"0%FV pee W Whey l

.

DATE 05/21737 05/3/97 06hf197 05/ 197 05/ /97

OFFICIAL RECORD CDPY

' Con,currence by Telephone 5/28/97

,

!

-

'

i

!

i

.

TOTAL P.02

- - -

v w

emw+

rM

,

.

...

-

-

.

..

~ _ -

-. _.

. -.

.

__ -

.

.

l'

.

.

.

Distribution w/ encl:

Region I Docket Room (with concurrences)

'

Nuclear Safety Information Center (NSIC)

PUBLIC NRC Resident inspector i

W. Axelson, ORA

l P. Eselgroth, DRP D. Haverkamp, DRP J. Nick, DRP C. O'Daniell, DRP D. Screnci, PAO Distribution w/ encl (VIA E-MAIL):

,

W. Dean, OEDO

!

P. Milano, NRR, PDI-3 I

B. Buckley, PM, NRR, PDI-3 i

L. Thonus, NRR/PDNP S. Weiss, NRR/PDNP R. Correia, NRR i

F. Talbot, NRR Inspection Program Branch, NRR (IPAS)

DOCDESK

'

,

i j

I i

i l

!

DOCUMENT NAME: C;\\ BRANCH 7\\TMi\\TM197-03.lNS r ceia e copy or thi. o.c. n.nt, inaces. In the boa: "C" = Copy without ettechment/ enclosure

  • E" = Copy with attachment / enclosure

"N" = No copy

.

_

OFFICE Rl/9RP Rl/DRP Rl/DRP l

l j

NAME Wyans'

PEselgroth*

WHehl DATE

')S/28/97 05/ /97 05/ /97 05/ /97 05/ /97 I

OFFICIAL RECORD COPY

' Concurrence by Telephone 5/28/97

'

1