Amend 89 to License DPR-3,revising Tech Spec Surveillance Interval for Second Level (Degraded Grid Voltage) Undervoltage Protection
ML20137Z613
Person / Time
Site: Yankee Rowe
(DPR-03-A-089, DPR-3-A-89)
Issue date: 11/30/1985
From: Lear G
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20137Z605 List:
References
NUDOCS 8512110353
Download: ML20137Z613 (5)


Text

f[

UNITED STATES NUCLEAR REGULATORY COMMISSION o

E WASHINGTON, D. C. 20555

(

%...../

YANKEE ATOMIC ELECTRIC COMPANY YANKEE NUCLEAR POWER STATION.

DOCKET NO. 50-29 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 89 License No. DPR-3 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment by Yankee Atomic Electric Company (the licensee) dated October 16, 1985 complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; 8.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public; and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

8512110353 851130 ADOCK 05000029 PDR PDR P

I

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment and Paragraph 2.C.(2) of Facility Operating License No. OPR-3 is hereby amended to read as follows:

(2) Technical Specifications The Technical Specifications contained in Appendix A as revised through Amendment No.89, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION

%. l kh George E Lear.. Director PWR Project Directorate #1 Division of PWR Licensing-A

Attachment:

Changes to the Technical Specifications Date of Issuance: November 30, 1985

)

ATTACHMENT TO LICENSE AMENDMENT N0.89 FACILITY OPERATING LICENSE NO. DPR-3 DOCKET NO. 50-29 Revise Appendix A Technical Specifications by removing the pages identified below and inserting the enclosed pages. The revised pages are identified by the captioned amendment number and contain marginal lines indicating the area of change.

REMOVE INSERT 3/4 3-ISA 3/4 3-15A 3/4 3-16 3/4 3-16

.i i

y i

g TABLE 4.3-2 (continuedl i.

N ENGINEERED SAFECUARDS SYSTEM INSTRUMENTATION SURVEILLANCE REOUIREMENTS M

E m

CHANNEL MODES IN WHICH CHANNEL CHANNEL FUNCTIONAL SURVEILLANCE FUNCTIONAL UNIT CHECK CALIBRATION TEST REQUIRED 2.

CONTAINMENT ISOLATION (Continued) c.,

Actuation Channel B S

NA M(4) 1, 2, 3, 4 S*

1)

High Containment S

R(3)

M(3) 1,2,3,4,$*

Pressure Sensor j

2)

Safety Injection l

M (All Safety Injection Surveillance Requirements) 3.

MAIN STEAM ISOLATION Y

i i -

U a.

Low Steam Line Pressure S

R(3)

M(3) 1, 2 l

j b.

Automatic Trip Logic NA NA Q

1,I 2 c.

Manual Initiation NA NA R

1, 2 d.

High Containment Pressure NA NA R

1, 2

~

4.

LOSS OF POWER I

480 Volt Emergency Bus NA R

M 1,2,3 a

i E.

Degraded Voltage E

  • o g

s 4

4 i.

TABLE 4.3-2 (Continued) s TABLE WOTATION (1) When shut down with main coolant pressure < 1000 psig, if not performed within the previous 31 days.

(2) When shut down longer than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, if not performed in the previous 31 days.

(3) The test shall include exercising the sensor by applying either a vacuum or pressure to the appropriate side of the sensor.

(4) When in COLD EHUTDOWN with main coolant pressure 4 300 psig, if not performed within the previous 31 days.

Not required in this WODE with main coolant pressure < 300 psig.

Not required in this MODE with main coolant pressure < 1700 psig.

1 4

YANEEE-ROWE 3/4 3-16 Amendment No.

, 89

.. -