Discusses 851006 Field Insp of Fire Door Frames Mfg by Fenestra Corp.Products Complied W/Requirements.Field Alterations Made to Frames Listed
ML20137W027
Person / Time
Site: Palo Verde  
Issue date: 10/22/1985
From: Ciangiola P, Kort K
UNDERWRITERS LABORATORY, INC.
To: Fiorelli G
NRC
References
85FNFIB330, R2552, NUDOCS 8512100154
Download: ML20137W027 (2)


Text

"

w UNDERWRITERS LABORATORIES INC.

j 3 p.

=

= =.c== =. o

. au,.o..

a an independent, not-for-prof t organi5 tion testingfoY pElic sble'ty October 22, 1985 Nuclear Regulatory Commission Mr. Gaston Fiorelli P. O. Box 239 Arlington, AZ 85322 Our

Reference:

R2552, 85FNFIB330 Subjects Field Inspection Of (7) Fire Door Frames Installed At The Palo Verde Power Plant

Dear Sir,

Please be advised that on October 5 and 6, 1985 our Inspector visited the above location for the purpose of making a field inspection on fire door frames manufactured by the Fencstra Corporation of Erie, Pennsylvania.

Our Inspector revealed that the subject products complied with our requirements and our Listing Marks were allowed to be

' applied to the products.

also noted several field alterations made to Our Inspector the frames by the Bechtel Construction under the orders of the Palo Verde Security Staff.

The field alterations that were performed are not authorized por UL specifications but based on the fact that the frames complied with UL require-ments when they left the manufacturer, the frames were allowed.

to be labeled.

The alterations which took place are outlined below.

1.

Field installed 1-1/2 in, metal conduit closure in the hallway face of the strike jamb.

2.

Field installation of a Listed magnetic coil manu-factured by Flair Electric, Inc. which was installed by means of a 1-1/4 in diameter plastic button in one rabbot of the header.

These alterations are of a particular fire protection concern as the possibility exists that should the frame be exposed to a fire condition, the unauthorized alterations may provide a means for flame penetration into the wall assembly.

8512100154 851022 PDR ADOCK 05000528 G

PDR Look For The @Usting or Classification Mark On The Product

=a.. % swas, t

u.c,.

Winamus=

N

- 2 W TL1l$0 9g

/

ERS LABORATORIES INC.

R2552 Pago 2

/

October 22, 1985 The frames that were inspected were all located in the Auxiliary and Turbine buildings, Elevation 51 ft - 6 in.,

Level C.

The following are the door opening numbers which received labels.

Door Opening Serial No.

AC04 L-855306 AC05 L-855307 AC06 L-855305 AC09 L-855303 AC10 L-855301 AC13 L-855302 AC16 L-855304 If you have any questions or comments on the above, please contact the undersigned.

Very truly yours, Reviewed by:

f W

g KEVIN KORT (Ext. 3301)

PATRICK M. CI LA Engineering Assistant, Engineering G Leader Follow-Up Services Follow-Up Services KKtej

')b! Mr. Perry Westmoreland Bechtel Construction, Inc.

P. O. Box 49 i

Palo Verde, AZ 85343 I