Forwards Results of Recently Completed Inservice Insp of Steam Generator Tubes,Including Steam Generator Internal Location Ref Guide & List of Defects,Tube Identification, Defect Depth & Axial Location of Defect in Tube
ML20137R675
Person / Time
Site: San Onofre 
Issue date: 11/25/1985
From: Morgan H
SOUTHERN CALIFORNIA EDISON CO.
To: Martin J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
NUDOCS 8512060040
Download: ML20137R675 (29)


Text

-

t fE5 Southem Califomia Edison Company SAN ONOFRE NUCLEAR GENERATING STATION P. O. BOX 128 SAN CLEMENTE. CALIFORNIA 92672 H.E. MORGAN TELEPHONE ETATH3N MANAGEf, 17 t o) 368-824 9 November 25, 1985 J

U. S..tNuclear Regulatory Commission Office of Inspection and Enforcement Region V 1450 Maria Lane, Suite 210 Walnut Creek, California 94596-5368

~

Attention:

Mr. J. B. Martin, Regional Administrator '

Dear Sir:

t

Subject:

Docket No. 50-361 Special Report - Inservice Inspection of Steam Generator Tubes San Onofre Nuclear Generating Station, Unit 2 a

Reference:

Letter from M. O. Medford (Southern California Edison) to G. W. Knighton (Branch Chief, Licensing Branch No. 3, U.S. Nuclear Regulatory Commission), dated April 5, 1985, with the following enclosures:

(1) Metallurgical Defects in Steam Generator Tubes, San Onofre Unit 2, April 3, 1985 (2) Steam Generator Tubing Wear, San Onofre Unit 2, April 3, 1985 Pursuant to Section 6.9.2 of Appendix A, Technical Specifications to Facility Operating License NPF-10, this report is being submitted as required by Surveillance Requirement 4.4.4.5(b) associated with Limiting Condition for Operation (LCO) 3.4.4.

This Surveillance Requirement requires that a Special Report be prepared and submitted to the Commission within 12 months following the completion of each inservice inspection of steam generator tubes. The referenced letter forwarded two detailed reports of this inspection and associated analysis.

These reports addressed tube examinations and associated corrective actions.

.During the refueling outage, an inservice full length inspection of 100*s of the unplugged tubes in both steam generators was completed on January 27, 1985.

A total of 146 tubes were plugged in Steam Generator'E2d @ 3Wd 184 tubes were plugged in Steam Generator E-089.

As required by Surveillance Requirement 4.4.4.kbT(fWesGEtA0Nfsste recently completed inservice inspection are provided in the enclosures to this letter.

Enclosure (1) is a steam generator internal location reference guide. The eddy current defect / indication locations on various esilbsures are based upon this guide.

03Al33f 9512060040 851125 PDR ADOCK 05000361 0

PDR ii pSg/

o Mr. J. B. Martin Enclosures (2) through (5) provide the inservice inspection results for Steam Generator E-088.

Enclosure (2) provides a list of defects including tube identification, defect depth and the axial location of the defect in the tube. A defect is an eddy current testing indication greater than or equal to 44% of nominal tube wall thickness.

If a tube contains a defect, the tube is defective and must be plugged.

Enclosure (3) provides a list of eddy current indications less than 44% but greater than or equal to 20% of nominal tube v.all thickness.

Enclosure (4) provides a list of eddy current indications that were detectable, but quantifiable only as less than 20% of nominal tube wall thickness.

Enclosure (5) provides a list of tubes plugged after the completion of the inservice inspection.

If a tube was plugged because of an eddy current test indication in the tube, the depth of the eddy current indication is provided.

The location is provided only for batwing related indications.

Batwings are illustrated on Enclosure (1) and are i

interchangeably referred to as diagonal bars.

Enclosures (6) through (9) are listings for Steam Generator E-C39.

They are 3

i formatted identically with the corresponding list for Steam Geno ator E-088.

If you require any additional information, please so advise.

Sincerely, b

QW

Enclosures:

(1) Combustion Engineering Model 3410 Steam Generator Support Designation Guide and Illustrative Diagram (2) List of Tubing Defects, Steam Generator E-088 (3) List of Eddy Current Indications 20% - 43%, Steam Generator E-088 (4) List of Eddy Current Indications < 20%, Steam Generator E-088 (5) List of Tubes Plugged, Steam Generator E-088 (6) List of Tubing Defects, Steam Generator E-089 (7) List of Eddy Current Indications 20% - 43%, Steam Generator E-089 (8) List of Eddy Current Indications < 20%, Steam Generator E-089 (9) List of Tubes Plugged, Steam Generator E-089 F. R. Huey (USNRC Senior Resident Inspector, Units 1, 2 and 3) cc:

H. Rood (Project Manager, SONGS 2/3, USNRC, NRR)

U. S. Nuclear Regulatory Commission Document Control Desk Institute of Nuclear Power Operations (INPO)

- - - = - -

s Mr. J. B. Martin 3-cc:

F. R. Huey (USNRC Senior Resident Inspector, Units 1, 2 and 3)

H. Rood (Project Manager, SONGS 2/3, USNRC, NRR)

U. S. Nuclear Regulatory Commission Document Control Desk Institute of Nuclear Power Operations (INPO) s D

=

b e

M e

i ENCLOSURE (1)

Page 1 of 2 COMBUSTION ENGINEERING MODEL 3410 STEAM GENERATOR 1LLUSTRATIVE DIAGRAM

(

VERTICAL HOT / COLD LEG i

i SUPPORTS VM OUTERMOST VC2 TUBE (

V,H,2 VH1 VH3 VC3 VC1

~~

~~

I OC I

l OH t

\\

S C10 g==

H10 s 8

H9 C9 H8

-%o /

C8 f

I INNERMOST k

u g

8

(

H6 C6 HOT LEG COLD LEG SUPPORTS SUPPORTS H5 C5 I

I H4 C4 H3 C3 e

i H2 C2 SHROUD HI C1

\\

f TUBESHEET HTS CTS O

E 9 ;;;

I

-i

i ENCLOSURE (1)

Page 2 of 2 COMBUSTION ENGINEERING MODEL 3410 STEAM GENERATOR SUPPORT DESIGNATION GUIDE CIARIFICATION OF ROWS CONTACTING SUPPORIS ABOVE 71H TSP SUPPORT ROWS DESIGNATION 1 - 24 DH, DC 25 - 48 DH, VM, DC 49 - 50 H8, DH, W, DC, C8 51 - 82 VIG, H8, Dil, W, DC, C8, VC3 83 VH2, MG, H8, DH, VM, DC, C8, VC3, VC2 84 - 114 H9, VH2, VIG, H8, DH, VM, DC, C8, VC3, VC2, C9 l

115 - 119 VH1,H9,VH2,VH3,H8,DH,VM,DC,C8,NC3,VC2,C9,VC1 120 - 147 1110, Wil, H9, VH2, VIG, H8, DH, VM, DC, C8, VC3, VC2, C9, VC1, C10

  • NOTE:

For purposes of this report, vertical support locations as reported on DDA4 printouts are defined as follows:

Vertical supports are increnented by one starting with the Hot g Side.

Example:

Row DDA4 Support Designation 25 VI VM 60 V1 MG 80 V3 VC3 118 V4 VM 125 V6 VC2

/

p ENCLOSURE (2)

I Page 1 of.1 l

l l

LIST OF TUBING DEFECTS, STEAM GENERATOR 88 R0W.

LINE PERCENT LOCATION 51 29 61 C3+2.4 106 28 45 C4+16.3 70 58 62 C8+38.4 41 71 94 HTS +7.9 109 103 50 '

C1+14.6 96.

110 66 C2+22.2 49 127 48 H3+20.4 1

175 69 HTS +5.0 2

174 48 HTS +4.8 29 73 49 DC 33 77 52 DH l

35 77 48 DH 34 78 50 DC 44 80 45 V1 39 83 53 V1 39-91 48 DH 37

.95 52 DC 32 100 71 DH 31 101 45 DH 27 105 63 DH 32 76 46 DC 37 93 48 DC 38 82 55 DH I

I I

b-

E 8

o ENCLOSURE (3)

Page 1 of 3 I

LIST OF EDDY CURRENT INDICATIONS 20% - 43%

STEAM GENERATOR 88 ROW LINE PERCENT LOCATION 24 70 37 DH 27 71 24 DC 29 73 38 DH 31 75 39 DH 24 DC 34 76 40 DH 20 DC 34 78 43 DH 35 79 40 DH 36 80 31 DH 22 DC 36 78 22 DC 37 79 41 VM 37 81 26 DC DC 38 82 23 37 83 42 DH 41 83 35 DH 39 85 27 DH 20 DC 39 87 31 DC 27 DH 45 87 23 DH 20 DH 38 88 23 DC 20 Dl!

39 89 22 DC 38 90 28 DH 39 91 20 DC 40 86 31 DH 38 94 43 DC 37 95 31 DC 20 DH 27 DH 39 95 28 DC 20 DH 41 95 37 DC 43 95 26 DC

s

.)

C 3

o ENCLOSURE (3)'

1 Page 2 of 3 s

5 1

LIST OF EDDY CURRENT INDICATIONS 20% - 43%

STEAM GENERATOR 88 (CONTINUED)'

[

t R0W LINE PERCENT LOCATION 88 28 25 H9+0 84 28 37 C6+14.8 l

99 31 22 C1+25.4 53 45 26 H2+11.8 68 46 26 HTS +25.8

^

20 C7+2.2 i

97 49 34 C5+31.2 i

52 50 21 H5+6 I

88 54 23 C3+ t,5.1 137 69 23 VC3+10.9 I

139 75 23 C3+17.5 20 C2+11.2 20 C3+19 20 C3+20.7 143 71 37 C3+15.5 66 28 29 H3+22.5 93 85 23 C7+7 I

87 95 41 C6+8.2 28 C7+10.5 24

,C6+17.2

~

20 C6428.3 '

20 C6+J0.3 p'

l 104 96 21 VMMO.1 41 105 33 Cl+6.8 141 109 22 VC2+2.5 88

'112 33 C8&29.2 133 117 23 C3+21.8 i

129 121 35 H1+13.8 49 127 33 H3+20.6 1,'

73 125 27 C7+20.5 c

42 122 22 H2+14.4 l

124 128 29 VM+12.1 82 136 22 H5+t7.2 s

86 158 21 H6+'i 7. 7 WA 9, -

k l,

1 i

s l

k

ENCLOSURE (3)

Pagn 3 of 3

,s -

+

^

LIST OF EDDY CURRENT INDICATIONS 20% - 43%

STEAM GENERATOR 88 (CONTINUED)

R0W IINE PERCENT LOCATION 49r 95 28 DH 20 DC s

i 37 93 25 DH 39 93 25 DH 41 93 40 DH 40 92 24 DH 38 92 37 DH 40 96 28 DC 20 DH 36 96 40 DH 35 97 39 DC 38 DH 33 99 38 DH ii 26 DC "e

28 104 35 DC

,ep 20 DH 33 101 36 DH 31 103 35 DH h

I t

~

l I,' i

/

O

ENCLOSURE (4)

Page 1 of 2 g

LIST OF EDDY CURRENT INDICATIONS LESS THAN 20%

STEAM GENERATOR 88 ROW LINE LOCATION 3

5 C2+21.5 fi 43 19 C4+30.8 64 26 HTS +25.9 a

58 26' C8+7.3 27

, 33 H4+1.8 i

88 34 C3+15.6 111 35 C3+8.1 I

85 37 H4+9.1 t

106 38 C6+17.7 65 41 C1+22.2 113.

41 C6+33.7

'p 55 45 C1+6.7 48 48 H5+10.4 96 50 C2+8.5 41 51 H2+22.6 43 51 H2+22.7 116 52 H3+32.5 98 52 C7+9.3 82 52 CTS +13.3 11 53 C5+20.4 115 53 C7+3.1 C6+34.1 C6+30.2 5

53 H3+21.5 52 60.

C2+32.4 p.

71 61 VM+3.6 0

i113 61 H3+6.2 114-62 C6+30.2 54 62 H1+17.3 i

45 63 C6+7.6 111 67 C1+10.9 77 67 CTS +6.1 35 75 VM

.39 77','

DC 49 77 DH 119 77 VM 37 29 VM 39 79 DC q,

40 82 DH 136 64 C4+16.9 38 84 DC

ENCLOSURE (4)

Page 2 of 2 LIST OF EDDY CURRENT INDICATIONS LESS THAN 20%

STEAM GENERATOR 88 (CONTINUED)

ROW LINE LOCATION 108 84 H9+7.7 40 86 DH 38 86 DH 41 87 DH

-119 91' H7+10.9

.125 91 H2+21.8 i

115 -

93 C7+19.9

. 127-93 HTS +8.6 46 92 DH 34-98 DH 93 105 H6+16.3

' 115.

103 VH1+10.9 44 120 H4+20.5

=

H4+17 8-120' H4+10 30 122 H2+8 15

- 121 C4+6.2 39 129 H3+29.3 100' 126 HTS +1.6 117 135 C3+5.4 93-137 Vl+9.9-54 136 H1+29.4 13 145 CTS 4

64' 150 H3+17.3 54 150 C4+27.3 84 154 C5+7.1 1-169 C2+3.8 4

174 HTS +12.9 g-+.-e p

w

-up

_.,.,._-,.-,.4 y

p.

p

- m

--e.-wyy e

' ENCLOSURE'(5)

a Page 1 of 4 LIST OF TUBES PLUGGED STEAM GENERATOR 88 R0W LINE REASON 1'

~167 PM 1

175 69%

2 174 48%

5 161 PM 23 69 PM 23 107 PM 24 70 37%

24 106 PM 25.

69 PM

'25 107 PM 26' 70 PM 26 106 PM 27 69 PM 27 71 24% (BW) 27.

105 63%

27 107 PM e

28 70 PM 28 72 PM 28 104

-35% (BWW) 28 106 PM 1

29 71 PM 29

.73 49%

29 103 PM 29 105 PM 30 72 PM 30 74 PM -

30 102.

PM 30 104 PM 31 73 PM 31 75 39% (BWW) 31 101 45%

31 103 35% (BWW)

-32 74 PM 32 76 46%

32

'100 71%

32 102 PM 32 104 PM

~33 75 PM 33 77 52%

33 99 38% (BWW)

(BWW) = Batwing Wear PM

= Preventive Maintenance

ENCLOSURE (5)

Page 2 of 4 a

LIST OF TUBES PLUGGED STEAM GENERATOR 88 (CONTINUED)

ROW LINE REASON 33 101 36% (BW)

'33 103 PM 34 76 40% (BW) 34 78 50%

34 98

<20% (BW) 34 100 PM 34 102 PM 35 75-

<20% (BW) 35 77 48%

35 79 40% (BW) 35 97 39% (BW) t-35 99 PM 35 101 PM

'36 76 PM 36 78 22% (BW) 36 80 31% (BW) 36 96 40% (BW)-

36 98 PM 37 77 PM i

37 79 41%

37 81 26% (BW) 37 83 42% (BW) 37 93 48%

37 95 52%

37' 97 PM 38 78 PM 38 80 PM 38 82 55%

.38 84

<20% (BW) 38 86

<20% (BW)

P

~38 88 23% (BW) 38 90 28% (BW) 38 92 37% (BW) 38 94 43% (BW) 38 96 PM 39 79

<20% (BW) 39

'81 PM 39-83 53%

39 85 27% (BW) 39 87 31% (BW) f '.

E (BW) = Batwing Wear

-PM

= Preventive Maintenance g-

-fi-

^- --

ENCLOSURE (5)

Page 3 of 4 LIST OF TUBES PLUGGED STEAM GENERATOR 88 (CONTINUED)

ROW LINE REASON 39 89 22% (BWW) 39-91 48%

39 93 25% (BW) 39 95 28% (BW) 39 97 PM 40 20 PM 40 66 PM 40 78 PM 40 80 PM 40 82

<20% (BW) 40 84 PM 40 86 31% (BW)

-40 88 PM 1

40 90 PM 40 92 24% (BW) 40 94 PM 40 96 28% (BW) 41 71-94%

41 79 PM 41 81 PM 41 83 35% (BW) 41 85-PM 41 87

<20% (BW) 41 89 PM 41 91 PM 41 93 40% ( BW) -

41 95 37% (BW) 41 97 PM 42 78 PM 42 82 P:t 42 84 PM 42 86 PM

.42 88 PM 42 90 PM 42 92 PM 42 94 PM 42 96-PM 43 83 PM 43-85 PM 43 87 PM (BW) = Batwing Wear PM

= Preventive Maintenance

ENCLOSURE (5)

Page 4 of 4 LIST OF. TUBES PLUGCED STEAM GENERATOR 88 (CONTINUED)

ROW LINE REASON 143 89 PM' 43 91 PM 43 93 PM 43 95 26% (BW)

.44 80 45%

44 94 PM 44; 96 PM 45 87 23% (BW)

~45 95 PM

'46 80 PM 47 157

-PM 49 95 28% (BW)

~49 127 48%

51 29 61%

54 70 PM 56 168 px 58 112 pM 70 58 62% 122 PM 95 51 PM 96 110

.66%

96' 118 PM 98 80 PM

-106

~28

- 45%

109 103 50%

128 46 PM (BW) = Batwing Wear

_ PM

= Preventive Maintenance t-

m-5*-

ENCLOSURE (6)

'Page 1 of I LIST OF TUBING DEFECTS STEAM GENERATOR 89 ROW LINE PERCENT LOCATION 34 78 48 DH

-39 79 51 DC 37 81 48 DC 38 82 61 DH 39 83 57 DC 37 83 54 DC 38 84 69 DH 58 DC 38 86 48 DH 39-87 48 DH 39 89 64 DH 38 90 45 DC 60 DH

-39 91 95 DC 41 91 44 DH

.38 92 47 DH 37 93 47 DC 37 95 56 DH 35 97 48 DH

.34 98 48 DC 33 99 46 DH 31 101 59 DH 49 DC 32 102

-48 DH 29 103 51 DH 57 113 46 C3+14.1-

- 105 53 61 C4+1.6

. 141 69 71 H4+0 59 C4+27.1 97 103 54 C3+8.2 132 98

49 C4+23.3 139 81 74 C5+25.3 45 C5+22.6 14 30 47 C3+24.8 70 50 68 Hl+28.1 48 Hl+20.2 108 72 46 H6+30.4 48 168 62 H7+8.1 51 vg,7.9 57 VM f

u_

Jo,

ENCLOSURE (7)~

Page 1 of 4 d

LIST OF EDDY CURRENT INDICATIONS 20% - 43%

STEAM GENERATOR 89 f,'

. ROW LINE PERCENT LOCATION 28 72 23 DC 44 72 35 DH J29 73 22 DC 20 DH

-32 76 40 DC 20 DH r

34 76 35 DC 34~

78 28 DH 20 DC i:

36 78 38 DC 35' 79 21 DH-31 DC 36 80 43 DC 23 DH 38 '

80 24 DC 40-80 38 DC 37 81 42 DH

. 39 -

.81 33 DC 38,

82 20 DC

+

37 83

-33 DH 39-83 22 DH 39 85 39 DC 39 87 28 DC 38 88 40

.DH 40 88 2:2 DH 42 88 41 DH 44 98 8 38 DH 46' 88 23 DH 41 89 26 DH 40 90 31

\\M 20 DH 39 91 22 DH 43 91 25 DH

'49.

91 24 DH 23 DC 38 92 22 DC 37 93 20 DC t

-ne-

=

1 ENCLOSURE (7)

Page 2 of 4 LIST OF EDDY CURRENT INDICATIONS 20% - 43%

STEAM GENERATOR 89 (CONTINUED)

ROW -

LINE PERCENT LOCATION 45 93 38 DH 46 94 33 DH 38 '.

94 33 DH 37 DC 37' 95 32 DH

-36 96 37

-IK:

~44 96 33 VM 96 35 DH 33 99-32 DC

,29 103 20 DC I

27 105

-31 DH 9

(

l

.gs

ENCLOSURE (7)

Page 3 of 4 LIST OF EDDY CURRENT INDICATIONS 20% - 43%

STEAM GENERATOR 89 (CONTINUED)

ROW LINE PERCENT LOCATION i

121 45 32 VC2 132 62 21 VH3 70 82 34 H8+2.4 141 109 29 VH3 28 VC3 25 VC2 133 113 27 VH3 81 127 26 VC3 84 144 22 VH2 48 168 34 DC 20 VM 1

61 33 C5+20.8 2

6 36 C2+18.4 11 111 43 C6-C5 12 20 32 C5-C4 12 124 37 H4-H5 13 167 22 C6-C5 17-117 24 H3-H4 18 32 21 CTS 20 116 22 C2-C1 27 71 38 C7-C6 33 39 24 H2-H3 37 55 22 C2-C1 39 167 36 C3-C2 40 18 24 C3-C2 40 140 26 C5-C4 40 160 37 C4 41 33 43 C1+25.9 46 8

27 C3+22.0 46 8

22 C3+17.7 48 118 40 C6-C5 j

32 C7-C6 51 73 27 C7-C6 54 78 24 H4-H5 59 95 27 C7 60 52 32 C3-C2 66 58 27 H6-H7 68 124 22 H6-H7 70 50 34 H1-H2 70 98 35 C3-C2

,e o

ENCLOSURE (7)

Page 4 of 4 LIST OF EDDY CURRENT INDICATIONS 20% - 43%

STEAM GENERATOR 89 (CONTINUED)

ROW LINE PERCENT LOCATION 70 106 39 H2-H3 73 133 25 H3-H4 74 54 26 H4-H5 76 154 28 HTS-H1 78 88 43 H3-H4 79 157 25 HS-H6 28 H5-H6 92 58 22 H2-H3 101 105 38 DH 107 131 35 HTS-H1 108 42 27 DH 108 78 22 H6-H7 114 104 27 H6-H7 118-84 35 H7

'119 79 23 H4-HS 123 57 38 Cl-CTS 123 77 24 H6-H7 124 62 24 C10-C9 124 114 27 Cl-CTS 125 91 36 H3-H4 125 95 33 C7 126 52 21 C7-C6 126 132 24 HTS-H1 131 115 22 C7-C6 139 81 32 C6-C5 20 C7-C6 141 69 29 H3-H4 26 H4-H5 141 83 22 C4-C3 147 81 38 C5-C4 4

ENCLOSURE (8)

Page 1 of 4 LIST OF EDDY CURRENT INDICATIONS LESS THAN 20%

STEAM CENERATOR 89 ROW LINE LOCATION 34 6

VM 70 16 VH3 77 47 VH3+4.6 129 49 VH1+6.1 59 51 VM+12.5 103 55 VM+9.7 70 58 VM+5.3 82 60 VH3 VH3+11.2 123 65 VC3+10.2 143 67 DH 33 77 DC

'138 80 VU2+9.8 40

'86 DH 39.

93 DH 77 93 DC 40 94 DC 95 115 VC3+5.0 122 116 VM+7.I 92 116 VH3+1.9 127 123 DH 88 140 VM+5.6 50 90 DH 46 92 C2+8.5 51 83 C2+9.8 7'

7 H6+24.6 30 168 C3+3.4 70 160 C6+30.8 69 159 C7+6.2 86 152 H4+17.5 73 147 CTS +16.6 76 144-C3+3.1 62 144 H4+19.1 H4+16.1

-99 141 H4+32.9-73 139 C5+9.3 C5+14.5 86 138 C2+17.7 80 138 C7+25.1 43-137 H7+17.1 1

_ _____j

}

s *

-ENCLOSURE (8)

Page 2 of 4 LIST OF EDDY CURRENT INDICATIONS LESS TIIAN 20%

STEAM GENERATOR 89 (CONTINUED)

ROW LINE LOCATION 119 135 C3+18.5 115 133 C7+24.3 85 129 H6+14.3 46 124 C2+11.7 127 123 H8+26.0*

48 118 C7+9.9 137 117 C5+7.9 17 117 H6 122 116 C9+8.4*

123 115 C7+28.8 101 113 H2+20.4 70-112 C3+2.9 120 110 C5+26.8 70 110 H8+16.6 115 109 C4+30.4 101 105 H7+26.9 30 10 C4+4.5 C3+35.4 16 12 H4,6.6 49 15 H3+2.4 80 16 C5+6. 7 70 16 H8+4.5*

20 16 C1+22.8 15' 17 C5+34.0 37 21 H4+29.5 29 23 C2 10 24 H5+6.3 35 29 H2+27.8 H2+25.0 59 29 H3+33.5 105 29 H2+29.3 H5+12.4 84 30 H7+26.7

-47 31 C4+18.0 7

33 C4+29,1 84 34 H3+16.0 44 34 H4+4.2 115 35 C4+30.6 16 38 C4+8.5 Multiple Indications

o ENCLOSURE (8)

Page 3 of 4 LIST OF EDDY CURRENT INDICATIONS LESS THAN 20%

STEAM GENERATOR 89 (CONTINUED) f ROW LINE LOCATION 112 40 H5+20.1 H5+23.1 H6+25.2 H6+4.9 94 40 C4+24.4 116 42 H4+18.2 52 46 C6+8.5 13 47 C2+8.3 61 47 C5+8.3 115 47 H4+21.6 121 47 H6+13.6 H6+10.0 48 48 H4+34.4 121 49 C5+4.7 59 51 H6+28.8*

34 52 H2+31.9 91 57 C5+25.7 130 58 HTS +14.1 66 58 C8+8.7 34 58 H6+14.9 37 59 H1+13.8 121 59 CTS +21.3 114 60 CTS +16.0 111-63 H8+7.5 119 63 C4+17.9 129 63 H9+29.0 HS-H6 108 64 C8+7.3 92 64 H3+8.2 117 65 HTS +24.0 126 66 C3+17.1 69 69 C1+21.3 110 70 H5+31.1 108 84 H8+23.5 H9+21.3 95 121.

H5+16.9 70 108 H8+9.5 H8+8.1 H8+5.1

  • Multiple Indications

(

ENCLOSURE (8)

-Page 4 of 4 LIST 0F EDDY CURRENT INDICATIONS LESS THAN 20%

STEAM GENERATOR 89 (CONTINUED)

ROW LINE LOCATION 86 106 H7+21.7 139 105 H6+12.1 108 80 H4+33.2 130 102 C7+17.7 114 98 C1+19.2 117 95 C3+31.6 C4+0.8 108 81 H8+23.5 H9+21.3 139 85 H6+5.3 135 98 H7+14.9 H7+32.0 124-94 Hl+29.6 HTS +22.3 3-3 C5+15.7 77-91-C7+15.6 t

4 138 HT3+26.6 9

17 C3+11.8 28 42 H6+9.0 15 43 C3+37.1 117 61 C8+18.7

~

C8+9.2 C8+10.5 J-1 93 91 C6+25.1 C6+23.2 L

ci.

  • e,.:

ENCLOSURE (9)

Page 1-of 5 LIST OF TUBES PLUGGED STEAM GENERATOR 89 ROW LINE REASON 3

41 PM 6'

4 PM 6

34 PM 9

37 PM 12 36 PM' 12 126 PM 13 19 PM 13 27 PM 14 -

30 47%

14 36 PM 14 60 PM 14 164 PM 18 18 PM 18 32-

'21%

18 36 PM 20 12 PM 23 27

-PM 23 69 PM 23 107 PM 24 70 PM 24 106 PM i

25 69 PM 25 107 PM 26 70 PM 26 106 PM 27 69 PM 27 71 38% (BW) y 27 105

' 31% (BW) 27 107 PM 28 12 PM 28 70 PM 28 72 23% (BW) 28 104 PM 28 106 PM 29 71 PM 29 73 22% (BW)

(BW) = Batwing Wear PM

+ Preventive Maintenance

,is..:..

ENCLOSURE (9)

Page 2 of 5 LIST OF TUBES PLUGGED

. STEAM GENERATOR 89 (CONTINUED)

R0W LINE REASON

' 29 103 51% (BW) 29 105 PM

~ 30 72 PM 30 74 PM 30 102 PM 30 104 PM 31 73 PM 31 75 PM

^ 31.

101 59% (BW)31-103 PM 32-74 PM 32 76 40% (BW)

-- 32 100 PM

-32 102 48% (BW) 33 75 PM 33' 77

<20% (BW) 33' 99 46% (BW) 33 101 PM 33 103 PM 34 76 35% (BW) 34 78 48% (BW) 34 98 48% (BW) v 34 100 PM 34 102 PM 35 77 PM

-35 79 31% (BW) 35 97 48% (BW) 35 99 PM i

36 78 38% (BW) 36 80 43% (BW) 36 96 37% (BW) 36-98 PM L

37 77 PM 37 79 PM 37 81 48% (BW) 37 83 54% (BW) 37 93 47% (BW)

(BW) = Batwing Wear -

PM'

= Preventive Maintenance

o ae o ENCLOSURE (9)

Page 3 of 5 LIST OF TUBES PLUGGED STEAM GENERATOR 89 (CONTINUED)

R0W LINE REASON 37 95 56% (BW) 37 97 PM 38 78 PM 38 80 24% (BW) 38 82 61% (BW)

-38 84 69% (BW) 38 86 48% (BW) 38 88 40% (BW) 38 90 45% (BW) 38 92 47% (BW) 38 94 33% (BW) 38 96 PM 39 79 51% ' ( BW) 39 81 33% (BW) 39 83 57% (BW) 39 85 39% (BW) 39-87 48% (BW) 39 89 64% (BW) 39,

91 95% (BW) 39 '

93 (20% (BW) 39 95 FM 39 97 PM 39 167 36%

40 40 PM 40 78 PM 40 80 38% (BW) 40 82 PM 40 84 PM 40 86.

<20% (BW) 40-

-88 22% (BW) 40 90 31% (BW) 40 92 PM 40 94 (20% (BW) 40 96 PM 41 79 PM 41 81 PM 41-83 PM (BW) = Batwing Wear

-PM

= Preventive Maintenance

e i.

ENCLOSURE (9)

Page 4 of 5 LIST OF TUBES PLUGGED STEAM GENERATOR 89 (CONTINUED)

(

ROW LINE REASON t

41-85 PM 41 87 PM 41 89 26% (BW) 41 91 44% (BW) 41 93 PM 41 95 PM 42 80 PM 42 82 22% (BW) 42 84 PM 86 PM 42 42 88 41% (BW) 42 90 PM 42 92 PM 42 94 PM 42 96 PM 43 85 PM 43 87 PM 43 89 PM 43 91 25% (BW) 44 88 38% (BW) 44 90 PM 44 92 PM 44 33% (BW) 45 87 PM

'45 89 PM 45 91 PM 45 93 38% (BW) 46 80 PM 46 88 23% (BW) 46 94 33% (BW) 46 96 35% (BW) 47 85 PM 47 87 PM

'47 89 PM 48 88 PM 48 168 62%

49 91 24% (BW) i

- (BW) = Batwing Wear PM

= Preventive Maintenance

g-i-w o.

-ENCLOSURE (9)'

Page 5 of 5 LIST OF TUBES PLUGGED STEAM GENERATOR 89 (CONTINUED)

ROW -

LINE REASON 51 59 PM 51 81 PM 51 111 PM

'57-113 46%

.61.

145 PM 62:

62 PM 65 105 PM 65 145 PM 70 18 PM 70 50 68%

81

.69 PM

-83 59 PM 90 54 PM 97 27

.. PM 97 103 54%

101 125 PM 104 80 PM 105--

53 61%

105 81 PM 107 131 35%

108 72 46%

-109 83 PM 112 90 PM 113 33 PM 116 66 PM 119 95 Pet 120 78 PM 121 65 PM 122 60 PM 126 54 PM 129-

-63 PM

-132 98 49%

135 109 PM 138 62 PM 138-98 PM 139 81 74%

141 69 71%

(BW) = Batwing Wear PM

-= Preventive Maintenance

_