ML20137Q941

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 851223-860103
ML20137Q941
Person / Time
Site: Hope Creek 
Issue date: 01/31/1986
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20137Q938 List:
References
50-354-85-65, NUDOCS 8602070135
Download: ML20137Q941 (1)


Text

._

--_.=

i i

i' i

APPENDIX'A NOTICE OF VIOLATION i

Public Service Electric & Gas Company Docket No.

50-354 Hope Creek Generating Station License No. CPPR-120 i

During an inspection from December 23, 1985 to January 3, 1986, and in accord-ance with the NRC Enforcement Policy (10 CFR 2, Appendix C).

The following l

violation was identified:

I 10 CFR 50, Appendix J Section III. A.1.(b) requires that closure of con-tainment isolation valves shall be accomplished by normal operation for the performance of Type A integrated containment leak rate tests.

Contrary to the above, on January 2, 1986, during the performance of a Type A integrated containment leak rate test, closure of containeent iso-i lation valve No. KL-001 (HV-5148), was not accomplished by its normal mode of motor operation, in that the valve was hand operated to the closed position. This was evidenced by the valve clutch lever being observed in the manual position following completion of the test.

This is a Severity Level V violation.

(Supplement I) l Pursuant to the provisions of 10 CFR 2.201, Public Service Electric & Gas Com-pany is hereby required to submit to this office within thirty days of the date 3

of the letter which transmitted this Notice, a written statement or explanation in reply, including: (1) the corrective steps which have been taken and the re-sults achieved including corrections, if any, to the ILRT results; (2) correc-tive steps which will be taken to avoid further violations; and (3) the date when full compliance will be achieved. Where good cause is shown, consideration

]

will be given to extending this response time.

i i

l i

l l

l Ol,jgf,j334 96000/0135 i