Followup RO Re Inoperable Fire Doors Found During Routine Surveillance in Dec 1985.Eight Latching & Seven Closure Mechanism Failures Identified.Latches & Closure Mechanisms Will Be Upgraded
ML20137N888
Person / Time
Site: San Onofre  
Issue date: 01/14/1986
From: Morgan H
SOUTHERN CALIFORNIA EDISON CO.
To: Martin J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
NUDOCS 8602040273
Download: ML20137N888 (5)


Text

.

. ~.

N t,

Southem Califomia Edison Company c;

y, SAN ONOFRE NUCLEAR GE.NERATING STATION P O B01 120 y1 A

  • tg""

SAN CLEMENTL CALIFORNIA 92672 H E. MORGAN

.1

- a v ng s..ews f

j STATION M ANAGEf, 14)369 6241 January 14, 1986 g-

.n

[

i i

U.S. Nuclear Regulatory Commission j

Office of Inspection and Enforcement Region V 1450 Maria Lane, Suite 210 i

Walnut Creek, California 94596-5368 Attention:

Mr. J. B. Martin, Regional Administrator

Dear Sir:

1 k

Subject:

Docket Nos. 50-361 and 50-362 Follow-up Report, Inoperable Fire Doors - December 1985 San Onofre Nuclear Generating Station, Units 2 and 3

Reference:

Letter, H. E. Morgan (SCE) to J. B. Martin (NRC),

dated December 12, 1985 i

In accordance with our referenced letter, this submittal provides the follow-up report of fire-rated assemblies (specifically fire doors) found inoperable during routine surveillances in December 1985.

Fire doors found inoperable during the December routine surveillances are identified in the Attachment and include 8 latching mechanism failures and 7 closure mechanism failures. No doors were found blocked open in December.

As each of these deficiencies was identified, compensatory fire watches, pursuant to Technical Specification 3.7.9, Action Statement 'a', were established. We are continuing previously reported corrective actions to upgrade door latches and closure mechanisms.

8602040273 860114 ADOCK 050 g 1 PDR S

1 '

JEO/

n,,,-g-pa,g-e.,

Mr. J. B. Martin This monthly follow-up report and those sent previously provide updated information associated with an ongoing condition initially reported in 1983.

The f:;Uow-up report covering inoperable fire doors identified in January 1986 will be submitted by February 18, 1986.

If you require any additional information, please so advise.

Sincerely, Enclosure cc:

F. R. Huey (USNRC Senior Resident Inspector, Units 1, 2 and 3)

U. S. Nuclear Regulatory Commission Document Control Desk Institute of Nuclear Power Operations (INPO)

ATTACHMENT SOUTHERN CALIFORNIA EDIS0N COMPANY INOPERABLE FIRE DOORS FOR THE MONTH OF DECEMBER 1985 SAN ONOFRE NUCLEAR GENERATING STATION UNITS 2 AND 3, DOCKET NOS. 50-361 and 50-362 I.

Latching Mechanism Failures:

Number of doors inoperable - 8, as follows:

Door Number Inoperable Operable AR-301 10/24/35 AR-401 11/20/85 12/16/85 FH3-103 11/24/85 12/07/85 AC-416 11/28/85 FH3-304 12/07/85 12/12/85 AC-339 12/07/85 12/19/85 AC-114 12/09/85 AC-417 12/10/85 12/12/85.__

ATTACHMENT SOUTHERN CALIFORNIA EDISON COMPANY INOPERABLE FIRE DOORS FOR THE MONTH OF DECEMBER 1985 SAN ONOFRE NUCLEAR GENERATING STATION UNITS 2 AND 3, DOCKET NOS. 50-361 and 50-362 (Continued)

II.

Closure Mechanism Failures:

Number of doors inoperable -

7, as follows:

Door Number Inoperable Operable AC-417 12/06/85 12/12/85 FH3-304 12/10/85 12/12/85 AR-502 12/12/85 FH3-304 12/14/85 12/19/85 AC-442 12/26/85 FH3-304 12/26/85 12/27/85 AC-459 12/28/85

ATTACHMENT SOUTHERN CALIFORNIA EDISON COMPANY INOPERABLE FIRE DOORS FOR THE MONTH OF DECEMBER 1985 SAN ON0FRE NUCLEAR GENERATING STATION UNITS 2 AND 3, DOCKET NOS. 50-361 and 50-362 III. Doors Blocked Open:

Number of doors blocked open - None 4

7746u '