ML20137N656

From kanterella
Jump to navigation Jump to search
Notifies That Replacement Svc Water Spray Water Pump W/O N Stamp Acceptable Provided Authorized Insp Agency Resurvey of Haywood Tyler Facility Acceptable & ASME Code Authorization & N Stamp Reinstated.Survey Results Requested
ML20137N656
Person / Time
Site: Hope Creek PSEG icon.png
Issue date: 11/21/1985
From: Butler W
Office of Nuclear Reactor Regulation
To: Mittl R
Public Service Enterprise Group
References
NUDOCS 8512040185
Download: ML20137N656 (6)


Text

.

y

[run 3m o

g g

UNITED STATES NUCLEAR REGULATORY COMMISSION

-  :; y W ASHINGTON, D. C. 20555

.....* NOV 21 1965 Oceket No. 50-354 Mr. R. L. Mitti, General Manager Nuclear Assurance and Regulation Public Service Electric & Gas Company P.O. Box 570, T22A Newark, New Jersey 07101

Dear Mr. Mitti:

SUEJECT: REPLACEMENT SERVICE UATER SPRAY WATER PUMPS We have completed our revicv. cf the Public Service Electric ar.d Gas Cenpany (PSE&G) request cated October 10, 1985 with respect to a replacement Service Water Spray Water Pump for Hope Creek.

The Service Water Spray Water Pur.ip was originally procured fron Hayt;oed Tyler and was ccnstructed to Section III, Class 3, of the ASME Boiler and Pressure Vessel Code including an "k" stanp. The replacement Service Water Spray Water Pump will also be precurce from Haywood Tyler and constructed to Section III, Class 3, cf the Ccce but without the "H" Stanp as their ASME Code Authorization and N-Type Stamp was revoked det tc relocation of the plant. In order to have the "h" Staap reinstated, Haywood Tyler is scheduled to be resurveyed in February 1986 by an Authorized Inspection Agency (AIA). If the results of the AIA resurvey are satisfactory, Heywood Tyler may again construct these pumps in accordance with the Code ircluding the "N" Stamp.

Tbc replacen;ent Service Water Spray Watcr Fump wculd be procured to rect all the requirener.ts of Section III, Class 3, of the ASME Code including all appropriate quality assurance requiremer,ts, with the exception of the "H" Stamp. The quality assurance requirements will be in conpliance with 10CFR Part 50, Appendix B. In addition, PSE&G will perform an appropriate vendor survey and provide an ASME type certifict. tion document certifying con.pliunce with all other related Section III requirements.

We find that the replacement Service Water Spray Water Pump without the "N" Starrp is acceptable provided the AIA resurvey of the Haywood Tyler f acility is acceptable and the ASME Code Authorization and "N" Stamp is reinstated. This approval is also contingent on the PSE&G commitment to provide an ASME type certification dccurent certifying compliance with all other related Section III requirements. In all other respects, the replacement Service Water Spray Water Pump shall be in confomance with Section III, Class 3 of the ASME Boiler and Pressure Vessel Code. l 8512040185 851121 PDR A

ADOCK 05000354 POR

+

_2 Pleast keep us infon>wd with respect to the results of the AIA resurvey of the Haywood Tyler facility. In the event the ASME Code Authorization and "N" Starrp are not reinstettd, we will require further aiscussion with PSE&G to detemine the adequacy of the replacement Service Water Spray Water Pumps.

Sincerely, Q

Walter R. Butler, Chief Licensing Branch No. 2 Division of Licensing cc: See next page

Please keep us informed with respect to the results of the AIA resurvey of the Haywood Tyler facility. In the event the ASME Code Authorization and "N" Stamp are not reinstated, we will require further discussion with PSEt.G to determine the adequacy of the replacement Service llater Spray Water Pumps.

Sincerely.

Originni Signn! by llalter R. Butler, Chief Licensing Branch No. 2 Division of Licensing cc: See next page DISTRIBUTION Docket File NRC PDR FfC System Local PDR NSIC LB#2 Reading Eliy1 ton DWagner Dewey, OELD ACRS (16)

JParticw E0rirres EJordan RKirkwood LB727bLM LB#2/DL/BC DWagner: Ib WButler 11/p:/85 11/g485

...__m . . . .. __. . . . J

1o . .

f7 '

.i.

Please keep us infomed with respect to the results of the AIA resurvey of the Haywood Tyler facility. In the event the ASME Code Authorization and "h" Stamp are not reinstated, we will require further discussion with PSEt.C to detemine the adequacy of the replacement Service Water Spray hater Pumps.

Sincerely.

Oririnal SigncJ by Uciter R. Butler, Chief Licensing Branch No. 2 Division of Licensing cc: See next page DISTRIBUTION Docket File l hRC PDR FrC System Loct.1 POR NSIC LB*2 Reading EHylten DWagner Dewey, OELL ACRS(16)

JFarticw PGrires EJordan RKirkwood 1

') '

LBTE/bdM LB#2/DL/BC DWagner:Ib WButler 11/p:/85 11g485

Mr. R. L. Mitti Public Service Electric & Gas Co. Here Crcek Generating Station cc:

Gregory Mirer Susan C. Remis Richard Hubbard Division of Public Interest Advocacy Dale Bridenbaugh New Jersey State Cepartrnent of NHB Technical Associates the Public Advocate 1723 Hamilton Avenue, Suite K Richard J. Hughts Justice Comples San Jose, California 95125 CN-850 Trenton, New Jersey 08625 Troy B. Conner, Jr. Esquirt Office of Legal Counsel Conner & Wetterhahn Department of Natural Resources 1747 Pennsylvania Avenue N.W. and Environmental Control Washington, D.C. 20006 89 Kings Highway P.O. Box 1401 Dover, Delaware 19903 Richard Fryling. Jr.. Escuirc Nr. K. W. Burrowes, Project Engineer Associatt. Ger.eral Solicitur bec.htcl Fcur Corporation Fbblic Service Electric & Gas Company 50 Beale Street F. O. Pr> E70 TSE P. O. Box 3965 Newark, New Jersey 07101 San Francisco, Califorr.ta 94119 Mr. J. M. Ashley Fesictnt inspector Senior Licensing Er.gir.cer U.S.N.R.C. c/o Public Service Electric & Gas Co. !

P. O. Box 241 Bethesda Office Center, Suit 550 I Hancocks Ericse, f ew Jersey 0803b 4520 East-West Highway bethesde, Maryland 20814 Richard F. Engel Deputy Atterr.cr Cerrral Mr. A. E. Giardino Division of Law lianager - Quality Assurence ESC Environmental Protection Section Fublic Service Electric & Gas Co.

Richard J. Hughes Justice Complex P. O. Box A Ch-112P Hancocks bridst, hew Jersey 08038 Trenton, I;cu Jersey 08625 Mr. Robert J. Touhey, ifr. Anthony J. Pietrofitta Acting Director General Manager DhREC - Division of Fc+er Production Engineering Envircr.r;tntal Control Atlantic Electric 89 Kings Highway 1199 Black Horse Pike P. O. Box 1401 Pleasantville, New Jersey 06232 Dover, Delaware 19903 Regional Administrator, Region i Mr. R. 5. Salvesen U. S. liuclear Regulatory Comission General Manager Here Creek Operation 631 Park Avenue Fublic Service Electric & Gas Co. King cf Prussia, Pennsylvania 19406 F.O. Box A Hancocks Bridge, titw Jersey 08038

~

Public Service Electric & Gas Co. Hope Creek Generating Station ec:

Mr. B. A. Preston Public Service Electric & Gas Co.

Hope Creek Site MC12Y Licensing Trailer 12LI Foot of Button wood Road Hancock's Bridge, New Jersey 08038 Ms. Rebecca Green New Jersey Bureau of Radiation Protection 380 Scotch Road Trenton, hew Jersey 08628 i

1 l

l 1

!