Notice of Violation from Insp on 851007-11
ML20136G501
Person / Time
Site: River Bend 
Issue date: 11/05/1985
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML20136G493 List:
References
50-458-85-71, NUDOCS 8511220373
Download: ML20136G501 (1)


Text

c APPENDIX A NOTICE OF VIOLATION Gulf States Utilities Docket No.: 50-458 River Bend Station License No.: NPF-40 During an NRC inspection conducted on October 7-11, 1985, a violation of NRC requirements was identified. The violation involved failure of Surveillance Test Procedures (STPs) to meet Technical Specification requirements.

In accordance with the " General Statement of Policy and Procedure for NRC Enforce-ment Actions," 10 CFR Part 2, Appendix C (1985), the violation is listed below:

A.

10 CFR Part 50, Appendix B, Criterion V, requires that activities affecting quality be prescribed in procedures, drawings or instructions. Technical Specifications, for various instrument functions, require that these functions be set "less than or equal to" a specified value or " greater than or equal to" a specified value.

Contrary to the above, licensee procedures STP-051-4228 (Revision 0) and STP-051-4201 (Revision 3) required that the same functions be set "plus or minus" from a specified value, thus allowing them to be calibrated outside of the Technical Specification limits.

This is a Severity Level V violation (Supplement I)(50-458/8571-01).

Pursuant to the provisions of 10 CFR 2.201, Gulf States Utilities is hereby required to submit to this office within 30 days of the date of the letter transmitting this Notice, a written statement or explanation in reply, including for each violation:

(1) the reason for the violations if admitted, (2) the corrective steps which have been taken and the results achieved, (3) the corrective steps which will be taken to avoid further violations, and (4) the date when full compliance will be achieved. Where good cause is shown, consid-eration will be given to extending the response-time.

Dated at Arlington, Texas, Mt this 5/4 day of p

, 1985.