05000315/LER-1985-052, :on 851012,failure of Critical Control Room Power Inverter Resulted in Momentary Loss of 120-volt Regulated Control Room Power.Caused by Shorted Diode & Capacitor & Blown Fuses.Components Replaced

From kanterella
(Redirected from ML20136E628)
Jump to navigation Jump to search
:on 851012,failure of Critical Control Room Power Inverter Resulted in Momentary Loss of 120-volt Regulated Control Room Power.Caused by Shorted Diode & Capacitor & Blown Fuses.Components Replaced
ML20136E628
Person / Time
Site: Cook 
Issue date: 11/11/1985
From: Lauren Gibson
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
Shared Package
ML20136E625 List:
References
LER-85-052, LER-85-52, NUDOCS 8511210539
Download: ML20136E628 (1)


LER-1985-052, on 851012,failure of Critical Control Room Power Inverter Resulted in Momentary Loss of 120-volt Regulated Control Room Power.Caused by Shorted Diode & Capacitor & Blown Fuses.Components Replaced
Event date:
Report date:
3151985052R00 - NRC Website

text

.

NaC f eese Joe U 8. NUCLEAN KEIULATGKV COMus&SIQJO e

APFROVED OMS NC 3190-4104 LICENSEE EVENT REPORT (LER)

D.

C.

COOK NUCLEAR PLANT, UNIT 1 0 151010101311 15 1 l0Fl O ll ESF ACTUATION EVENT DATE (5)

LEn NuMeER est REPCAT DATE 171 OTMER FACILITIES INVOLVIO ISI MONTH OAV vtAn vEAR 58,0gh';* h a.,my goNyw gay vgan PacsLivv h4 Mas DocstET NUMSERt$l

)

0 1510101 0 1 I i 1l0 1l2 85 8 l5 0l5l2 0l 0 1l1 1 l1 8l5 o,stogo,o, ; ;

~

E TMis mEpomf is susMiTTED Punsuami 70 THE mEQUIREMENTS OP to CPR $: ICAere sae er neere et rne feareeva,s pH Ope n ATING "o"'

5 m azm 20.asi.,

1 es rmiaHNi 23.rimi w.a.i. Hum

.a wi.Hu es.rmH:H.i rs.m.

Ot 010 m aasi.HuiH a0.mi.im es73ieH H c g,ME g;allp,r,,,

nei 20 aostein Hiaap go.73teH2Hil 30.73teH2HvistHAl Jf6AJ 20 406 test 1Hivl 50.73teH2HH 98.734eH3Helillist 20 406teH1Bl.1 50.7 SteH2 Hand 30.73EeH2Hal LICEN8EE CONTACT FOR TMit LER (131 41ME TELEPMONE NuusEm

""t l 6 L.

S.

GIBSON-TECHNICAL ENGINEERING SUPERINTENDENT l

416 l51-1519 9 11 COMPLETE ONE LiNE Fon E ACM COMPONENT Fal(URE DEOCRISED IN TMtS REpomT 113:

h@

N REP y( AC-

"^N[ AC-m nTas E CLUSE Sy3 TEM COMPONENT yO *.P

CAUSE

SYSTEM COMPONENT y

pp X

E IC IINIVIT S l 215 10 Y

I I I I I l t I l l I I I I

I l i l I I EUPPLEMENTAL REPORT E XPECTED tiet MONTH DAY vtAR 155189 vee. eemooere fMPfCTED SugestSSIQAt CA Tf!

NO l

l l

AS$TR ACT #Lemer to f 400 meces to. sesses.saefery rarreen mare asece erse=certoa maes# Hei ON OCTOBER 12, 1985, AT 0111 HOURS, WHILE IN COLD SHUTDOWN (MODE 5),

FAILURE OF THE CRITICAL CONTROL ROOM POWER (CCRP) INVERTER (IEEE/INVT) RESULTED IN A MOMENTARY LOSS OF 120 VOLT REGULATED CONTROL ROOM POWER WHILE AN AUTOMATIC BUS TRANSFER SWITCH SHIFTED TO THE BACKUP UNREGULATED POWER SUPPLY.

THE MOMENTARY LOSS OF POWER RESULTED IN AN AUTOMATIC ENGINEERED SAFETY FEATURES ACTUATION.

THE CAUSE OF THE CCRP FAILURE COULD NOT BE CONCLUSIVELY DETERMINED.

INVESTIGATION REVEALED A SHORTED DIODE (IEEE/ RECT),

SHORTED CAPACITOR (IEEE/ CAP), AND TWO BLOWN FUSES (IEEE/FU).

THE FAILED COMPONENTS WERE REPLACED AS WERE OTHER DIODES, SILICON CONTROLLED RECTIFIERS,-AND CAPACITORS THAT HAD NOT FAILED BUT MAY HAVE SUFFERED DEGRADATION AS A RESULT OF THE INCIDENT.

THE ENGINEERED SAFETY FEATURES ACTUATION CONSISTED OF A CONTAINMENT PURGE ISOLATION SIGNAL.

BECAUSE PURGE IS NOT REQUIRED IN MODE 5, THE SIGNAL WAS BLOCKED WHICH PREVENTED ANY EQUIPMENT ACTUATION. IMMEDIATE ACTION WAS TAKEN BY OPERATIONS PERSONNEL TO RESTORE PURGE TO PRE-EVENT STATUS.

THE INVERTER WAS RETURNED TO SERVICE ON OCTOBER 16, 1985 AT 1416 HOURS.

PROPER FUNCTIONING OF AUTOMATIC TRANSFER TO ALTERNATE POWER ENSURED THERE WERE NO ADVERSE SAFETY CONSEQUENCES OR IMPLICATIONS.

ALL EQUIPMENT PERFORMED AS DESIGNED.

NO PREVIOUS OCCURRENCES ARE KNOWN.

8511210539 851111 ADOCK 050003 g PDR M