April 22, 1979 To:
Sen Rusche
SUBJECT:
CARBON ADSORBERS IN AUXILI,ARY BUILDING U-2, "B" TRAIN On 4/22, I discussed with L. Kovach the events of 4/21 when the U-2 "B" Auxiliary Building charcoal adsorbers were wetted when the,' deluge valve was opened.
Kovach has recommended that the trays be removed from the system in the next 4-5 days and that the carbon be removed from the trays.
Because of the low phi 5.5, he recommends tte t the trays.
be dropped in 1% ootassium nitrate, reused with water and air dried to prevent corrosio,n of the stainless steel trays.
I pass this information on to you for your consideration.
J. T. Collins 4
'/