B-143 ACCIDENT SEQUENCE PRECURSOR PROGRAM EVENT ANALYSIS LER No.:

Event

Description:

Date of Event:

Plant:

254/90-003 Two EDGs out of service February 13, 1990 Quad Cities 1 Summary Both Quad Cities 1 emergency diesel generators (EDGs) were inoperable for approximately 25 h while the plant was operating at 99% power on February 13, 1990.

The "swing"~ EDG, #1/2, was out of service for scheduled maintenance, and the other EDG, #1, failed its second daily Technical Specification required operability test.

The conditional core damage probability estimated for this event is 3.7 x 10-6. The relative significance of this event compared to other postulated events at Quad Cities 1 is shown below.

Event Description On February 12, 1990, EDG #1/2 was taken out of service for scheduled maintenance while the plant was at nearly 100% power. When an EDG is repaired with the plant at power, Technical Specifications require the other source of emergency power for the plant, in this case EDG #1, to be demonstrated operable every day.

The first demonstration at 2145 h on February 12, 1990, was successful; however, during the second test at 1945 h on the following day, EDG #1 tripped on overspeed. A second demonstration was attempted about 45 min later, but the EDG tripped again on overspeed. The operator then went to "lower" on the governor adjustment switch, and a third demonstration was tried. This time the EDG started and was subsequently run for

B-144 2 h, at which time the EDG control switch was placed in automatic. EDG #1 was then declared operable. There were no component failures nor was any other safety system unavailable during this time. The elapsed time from the first overspeed trip until the EDG control switch was placed in automatic was 3.2 h. Note that this time includes a 2-h demonstration run.

Additional Event-Related Information Quad Cities 1 has two EDGs available for emergency loads. EDG #1 is used only by Unit 1; however, EDG #1/2 is designated a "swing" emergency power source and is capable of supplying emergency loads for either Unit 1 or Unit 2. Quad Cities 1 has two systems of 4.16-ky auxiliary buses consisting of three buses each. EDG #1 supplies emergency power for one bus in one system while EDG #1/2 supplies emergency power for one bus in the other system. Additionally, EDG #1/2 can supply emergency power to another bus in a similar system for Quad Cities 2.

Quad Cities 1 has two independent sources of offsite power. Normally, five separate sources of 345-ky power feed the reserve auxiliary transformer (RAT-12) via a ring bus in the switchyard, which in turn feeds 4. 16-ky buses 12 and 14. Bus 14 supplies 4.16-ky vital bus 14-1. Alternatively, five sources of 345-ky power supply the 4.16-ky Unit 2 vital bus 24-1 via the Unit 2 RAT-22, which in turn is cross-tied with bus 14-1.

The emergency supply for bus 14-1 is EDG #1. The other Quad Cities 1 vital 4.16-kY bus, 13-1, is supplied by bus 13, which along with bus 11, is supplied by the Quad Cities 1 main generator via the unit auxiliary transformer (UAT-11). The common Unit 1 and Unit 2 EDG (EDG #1/2 or swing EDG) provides emergency backup power to bus 13-1. With this arrangement, the auxiliary power for Unit I is supplied by UAT-l 1 and RAT-12 with the loads equally divided between them.

ASP Modeling Assumptions and Approach This event has been modeled with both the EDGs unavailable for 25.2 h and with a nonrecovery probability of 0.34. This 25.2-h period includes 22 h from the end of the first (successful) demonstration run until the attempted second run on the next day, plus 3.2 h for adjustments and a 2-h demonstration run. This time period assumes the overspeed. trip switch adjustment failed during the previous successful test. If, instead, it failed over time (a standby stress-related failure), the exposure time associated with the event would be 14.2 h, and the overall event significance would be approximately 60%

of that calculated herein. Had a loss of offsite power (LOOP) occurred during the demonstration run prior to returning the EDG to service, it is also possible that the EDG could have powered required loads through manual operator action.

B-145 Analysis Results The conditional probability of severe core damage for this event is 3.7 x 10-6. The dominant sequence associated with the event (highlighted on the following event tree),

involves a postulated loss of offsite power with failure to recover emergency power and failure to recover offsite power prior to battery depletion.

B-146 LODS f

EPE ORJ Me PW OR cC 6V PS~6~

c

~

50 DO kNM.

P AMS MOM MO STE N

ATE A0 OCmE DSAMAG OK 41 GOEDMAGE OK OK DA0m IMAGE OK 44 GKm DAMIAGE 45 GORE DAMAGE OK 464 CR DAMAGE 47 COREDAMAGE 46 0COR DAMAGE OK

4.

DOW D2AMAGE OK OK 5

0CM DAMAGE 52 GORE DAMAGE OK

_4DAm MAGE 55 0COR DAMAGE OK as 56 DOW DAMAGE OK DOW0C DAMAGE D"

Os 5

_0C DAMAGE OK COREm DAMAGE 64 CO DAMAGE 15 0CW DAMAGE 67 COW DAMUO 5

0CM DAMAGE 66 Cm DAMAGE 67 0COR DAMAGE

  • 3 00% DAMAGE 66 Ar DomiantCoreDamge Squeces or ER 24/9-as

B-147 CONDITIONAL CORE DAMAGE PROBABILITY CALCULATIONS Event Identifier:

254/90-003 Event

Description:

Two ED~s out of service Event Date:

02/13/90 Plant:

Quad Cities 1 UNAVAILABILITY, DURATION-25.2 NON-RECOVERABLE INITIATING EVENT PROBABILITIES LOOP SEQUENCE CONDITIONAL PROBABILITY SUMS End State/Initiator 2.2E-04 Probability CD LOOP Total ATWS 3.7E-06 3.7E-06 O.OE+OO O.OE+00 LOOP Total SEQUENCE CONDITIONAL PROBABILITIES (PROBABILITY ORDER)

Sequence End State 83 loop EMERG.POWER -rx.shutdown/ep ep.rec CD 97 loop E14ERG.POWER rx.shutdown ATWS 98 loop -EMERG.POWER rx.shutdown ATWS non-recovery credit for edited case SEQUENCE CONDITIONAL PROBABILITIES (SEQUENCE ORDER)

Sequence End State 98 loop -EMERO.POWER rx.shutdown ATWS 83 loop EMERG.POWER -rx.shutdown/ep ep.rec CD 97 loop EMERG.POWER rx.shutdown ATWS non-recovery credit for edited case Note:

For unavailabilities, conditional probability values are differential values added risk due to failures associated with an event.

Parenthetical values indicate compared to a similar period without the existing failures.

SEQUENCE MODEL:

c:\\asp\\1989\\bwrcseal.cmp BRANiCH MODEL:

c:\\asp\\1989\\quadcitl.sll PROBABILITY FILE:

c:\\asp\\1989\\bwr-csll.pro No Recovery Limit BRANCH FREQUENCIES/PROBABILITIES P rob 3.6E-06 2.2E-09 2.2E-09 Prob 2.2E-09 3.6BE-06 2.2E-09 N Rec**

1.8E-01 l.SE-01 3.5E-01 N Rec**

3.5E-01 1.8E-01 1.BE-01 which reflect the a reduction in risk Event Identifier: 254/90-003

B-148 Branch trans loop loca rx.shutdown rx. shutdown/ep pcs/trans arv.chall/trans.-scram arv.chall/loop.-scram srv.close EMERG. POWER Branch Model:

l.OF.2 Train 1 Cond Prob:

Train 2 Cond Prob:

ep *rec fw/pcs.trans fw/pcs.loca hpci rcic crd srv.ads lpcs lpci (rhr) /lpcs rhr (sdc) rhr (sdc) /-lpci rhr (sdc) /lpci rhr (spcool) /rhr (sdc) rhr(spcool) /-lpci.rhr(sdc) rhr(spcool) /lpci.rhr(sdc) rhrsw System Non-Recov Opr Fail l.4E-04 1.6E-05 3.3E-06 3.OE-05 3.5E-04 1.7E-01 1.OE+00 1.OE+00 l.OE-02 2.9E-03 > l.OE+00 5.OE-02 > Unavailable 5.7E-02 > Failed 4.9E-02 2.9E-01 4.OE-02 2.9E-02 6.OE-02 1.OE-02 3.7E-03 3.0 E-03 1.OE-03 2.1E-02 2.OE-02 1.OE+00 2.OE-03 2.OE-03 9.3E-02 2.OE-02 l.0E+00

5. 3E-01
5. CE-01 l.OE+00
1. OE+00
1. OE+.00
1. OE+00 l.OE+00
1. OE+00 B.OE-01 > 3.4E-01 l.OE+00 3.4E-01 3.4E-01
7. OE-0l
7. DE-0l
1. OE+00 7.1E-01 3.4E-01 7.1lE-01
3. 4E-01
3. 4E-01 1.OE+00 3.4E-01 3.4E-01 1.OE+00
3. E-01
1. OE-02
1. OE-02
1. OE-03 l.OE-03 1.OE-03 2.OE-03
  • branch model file
    • forced Minarick 08-06-1991 17:31:26 Event Identifier: 254/90-003