ML20135C673

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs Re Surveillance Requirements of Control Room,Penetration Room & Containment Purge Filtration Systems
ML20135C673
Person / Time
Site: Farley  Southern Nuclear icon.png
Issue date: 02/24/1997
From:
SOUTHERN NUCLEAR OPERATING CO.
To:
Shared Package
ML20135C654 List:
References
NUDOCS 9703040210
Download: ML20135C673 (25)


Text

PLANT SYSTEMS

', EURVhILLANCE REQUIREMENTS (Continued) b.

At 1 mast once per 18 months or (1) after any structural maintenance on the HEPA filter or charcoal adsorber housings, or (2) following painting, fire or chemical release that could have contaminated the charcoal adsorbers or HEPA filters in any ventilation zone communicating with the system by:

1.

Verifying that the cleanup system satisfies the in-place testing acceptance criteria of greater than or equal to 99.5% filter efficiency while operating the system at a flow rate indicated in Note 1 and using the following test procedures:

(a)

A visual inspection of the control room emergency air cleanup system shall be made before each DOP test or activated. carbon adsorber section leak test in-accordance with ASME N510-1989*.

l (b)

An in-place DOP test for the HEPA filters shall be performed in accordance with Section 10 of ANSI N510-1980.

(c)

A charcoal adsorber section leak test with a gaseous halogenated hydrocarbon refrigerant shall be performed in accordance with Section 12 of ANSI N510-1980.

2.

Verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing efficiencies criteria given in Note 2

}

when tested with methyl iodide at 80*C and 70% relative

]

humidity.

l 3.

Verifying a system flow rate as indicated in Note 1 during i

system operation when tested in accordance with ASME N510-1989*.

c.

After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber operation by verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing efficiencies criteria given in Note 2 when tested with methyl iodide at 80*C and 70% relative humidity.

The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

FARLEY-UNIT 1 3/4 7-17 AMENDMENT NO.

9703040210 970224 PDR ADOCK 05000348 p

PM

.m PLANT SYSTEMS o

i

', SURVhILLANCE REQUIREMENTS (Continued) d.

At least once per 18 months by:

4 1.

Verifying that the pressure drop across the combined HEPA filters and charcoal adsorber banks is less than 6 inches Water Gauge while operating the system at a flow rate indicated in Note 1.

i 5

2.

Verifying that the filter train starts on a Safety Injection Actuation test signal.#

I 3.

Verifying that the system maintains the control room at a l

positive pressure of greater than or equal to 1/8 inch water gauge relative to the outside atmosphere during system operation.

4.

Verifying that the pressurization system heater dissipates

)

7.5i0.8kwwhentestedinaccordancewithASMEN510-1989*.l After each complete or partial replacement of a HEPA filter bank e.

by verifying that the HEPA filter banks remove greater than or equal to 99.5% of the DOP when they are tested in-place in i

accordance with Section 10 of ANSI N510-1980 while operating the l

system at a flow rate indicated in Note 1.

3 f.

After each complete or partial replacement of a charcoal adsorber bank by verifying that the charcoal adsorbers remove greater than or equal to 99.5% of a halogenated hydrocarbon refrigerant test gas when they are tested in-place in accordance with Section 12 of ANSI N510-1980 while operating the system at a flow rate indicated in Note 1.

Note 1.

a.

Control Room Recirculation Filter Unit 2000 cfm i 10%

b.

Control Room Filter Unit 1000 cfm i 104 l

c.

Control Room Pressurization Filter Unit 300 cfm i 10%

Note 2.

a.

Control Room Recirculation Filter Unit 2 994 3

b.

Control Room Filter Unit 2 994 l

I c.

Control Room Pressurization 2 99.825%

i I

1 j

  1. Surveillance Requirement 4.7.7.1.d.2 does not apply in MODES 5 and 6.
  • The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

FARLEY-UNIT 1 3/4 7-17a AMENDMENT NO.

i

~_

PLANT SYSTEMS e

' 3/4.7.8 PENETRATION ROOM FILTRATION SYSTEM LIMITING CONDITION FOR OPERATION 3.7.8 Two independent penetration room filtration systems shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, 3 and 4.

ACTION:

With one penetration room filtration system inoperable, restore the inoperable system'to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.7.8 Each penetration room filtration system shall be demonstrated OPERABLE:

At least once per 31 days on a STAGGERED TEST BASIS by initiating, a.

from the control room, the flow through the HEPA filters and charcoal adsorbers and verifying that the system has operated for at least 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> with the heaters on during the past 31 days.

b.

At least once per 18 months or (1) after any structural maintenance on the HEPA filter or charcoal adsorber housings, or (2) following painting, fire or chemical release that could have contaminated the charcoal adsorbers or HEPA filters in any ventilation zone communicating with the system by:

1.

Verifying that the cleanup system satisfies the in-place testing acceptance criteria of greater than or equal to 99.5% filter efficiency while operating the system at a flow rate of 5000 cfm i 10 percent and using the following test procedures:

(a)

A visual inspection of the penetration room filtration system shall be made before each DOP test or activated carbon adsorber section leak test in accordance with ASME N510-1989*.

l (b)

An in-place DOP test for the HEPA filters shall be performed in accordance with Section 10 of ANSI N510-1980.

(c)

A charcoal adsorber section leak test with a gaseous halogenated hydrocarbon refrigerant shall be performed in accordance with Section 12 of ANSI N510-1980.

  • The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

FARLEY-UNIT 1 3/4 7-18 AMENDMENT NO.

m--. _ _

.-.m.._.___.~..

PLANT SYSTEMS

, SURVIII. LANCE REQUIREMENTS (Continued)

- 2..

Verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in i'

accordance with Section 13 of ANSI N510-1980 meets the laboratory testing criterion of greater than or equal to 954 l

efficiency when tested with methyl iodide at 80'C and 70%

relative humidity.

3.

Verifying a system flow rate of 5000 cfm

  • 10% during system operation when touted in accordance with ASME N510-1989*.

l After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber operation by j.

c.

l verifying within 31 days after removal that a laboratory L

i analysis of a representative' carbon sample obtained in

(

accordance with Section 13 of ANSI N510-1980 meets the l

laboratory testing criterion of greater than or equal to 95%

I l'

efficiency when tested with methyl iodide at 80*C and 70%

relative humidity.

d.

At least once per 18 months by:

1.

Verifying that the pressure drop across the combined HEPA filters and charcoal adsorber banks of less than 6 inches Water Gauge while operating the system at a flow rate of 3

5000 cfm i 10%.

24 Verifying that the system starts on a Phase B Isolation test signal.

3.

Verifying that the heaters dissipate 25 1 2.5 kw when tested in accordance with ASME N510-1989*.

l e.

After each complete or partial replacement of a HEPA filter bank by verifying that the HEPA filter banks remove greater than or equal to 99.5% of the DOP when they are tested in-place in accordance with Section 10 of ANSI N510-1980 while operating the system at a flow rate of 5000 cfm i 104.

f.

After each complete or partial replacement of a charcoal adsorber bank by verifying that the charcoal adsorbers remove greater than or equal to 99.5% of a halogenated hydrocarbon refrigerant test gas when they are tested in-place in accordance

)

with Section 12 of ANSI N510-1980 while operating the system at a flow rate of 5000 cfm t lot.

1

  • The FNP. Final Sai' tty Ar.alysis Report identifies the relevant surveillance testing requirements.

l FARLEY-UNIT 1 3/4 7-19 AMENDMENT NO.

1

REFUELING OPERATIONS SURV$ILLANCE REQUIREMENTS (Continued) 1.

Verifying that the cleanup system satisfies the in-place testing acceptance criteria of greater than or equal to 99.5% filter efficiency while operating the main purge system and using the following test procedures:

(a)

A visual inspection of the containment purge exhaust filter system shall be made before each DOP test or activated carbon adsorber section leak test in l

accordance with ASME N510-1989*.

l (b)

An in-placo DOP test for the HEPA filters shall be performed in accordance with Section 10 of ANSI N510-1980.

(c)

A charcoal adsorber section leak test with a gaseous halogenated hydrocarbon refrigerant shall be performed I

in accordance with Section 12 of ANSI N510-1980.

2.

Verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing criterion of greater than or equal to 904 efficiency when tested with methyl iodide at 80*C and 70s relative humidity.

1-b.

After every 12 months of charcoal adsorber operation by verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in 1

accordance with section 13 of ANSI N510-1980 meets the laboratory testing criterion of greater than or equal to 90%

4 efficiency when tested with methyl iodide at 80*C and 70%

relative humidity.

3 c.

At least once per 18 months by verifying that the pressure drop across the combined HEPA filters and charcoal adsorber banks is less than 6 inches Water Gauge while operating the main purge system.

s 1

a i

I

  • The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

s 4

FARLEY-UNIT 1 3/4 9-17 AMENDMENT NO.

j s

i i

4 4

d k

i i

i Joseph M. Farley Nuclear Plant i

Control Room, Penetration Room, and Containment Purge Filtration Systems Surveillance Requirements Technical Speci6 cation Changes i

Unit 2 Technical Snecification Panes J

i 3

i i

j 7

l i

}

i j

i 3

s a

4 i

I I

l

. =..-

i 1

4 t

1 1

I

]

FNP Unit 2 i

Technical Speci6 cations Control Room, Penetration Room, and Containment Purge Filtration Systems Surveillance Requirements z.

Changed Panes Page#

Instructions t

I l

3/4 7-17 Replace i

3/4 7-17a Replace 3/4 7-18 Replace 3/4 7-19 Replace i

3/4 9-17 Replace l

I

~...

PLANT SYSTEMS l SURVEILLANCE REQUIREMENTS (Continued) b.

At least once per 18 months or (1) after any structural maintenance on the HEPA filter or charcoal adsorber housings, or (2) following painting, fire or chemical release that could have contaminated the charcoal adsorbers or HEPA filters in any ventilation zone communicating with the system by:

1.

Verifying that the cleanup system satisfies the in-place testing acceptance criteria of greater than or equal to 99.5% filter efficiency while operating the system at a flow rate indicated in Note 1 and using the following test procedures:

(a)

A visual inspection of the control room emergency air cleanup system shall be made before each DOP test or activated carbon adsorber section leak tect in accordance with ASME N510-1989*.

l l

(b)

An in-place DOP test for the HEPA filters shall be performed in accordance with section 10 of ANSI N510-1980.

(c)

A charcoal adsorber section leak test with a gaseous halogenated hydrocarbon refrigerant shall be performed in accordance with Section 12 of ANSI N510-1980.

2.

Verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the l

laboratory testing efficiencies criteria given in Note 2 when tested with methyl iodide at 80*C and 70% relative-humidity.

3.

Verifying a system flow rate as indicated in Note 1 during system operation when tested in accordance with ASME N510-1989*.

i c.

After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber operation by verifying within 31 days after removal that a laboratory i

analysis of a representative carbon sample obtained in j

accordance with Section 13 of ANSI N510-1980 meets the i

laboratory testing efficiencies criteria given in Note 2 when tested with methyl iodide at 80*C and 70% relative humidity.

  • The FNP Final Safety Analysi Report identifies the relevant surveillance testing requirements.

FARLEY-UNIT 2 3/4 7-17 AMENDMENT NO.

> - - = -.

~.. -

PLANT SYSTEMS SUR[EILLANCEREQUIREMENTS (Continued) l d.

At least once per 18 months by i

1.

Verifying that the pressure drop across the combined HEPA filters and charcoal adso'rber banks is less than 6 inches Water Gauge while operating the system at a flow rate indicated in Note 1.

2.

Verifying that the filter train starts on a safety Injection Actuation test signal.#

j i

3.

Verifying that the system maintains the control room at a positive pressure of greater than or equal to 1/8 inch water j

gauge relative to the outside atmosphere during system

]

operation.

4.

Verifying that the pressurization system heater dissipates 7.510.8kwwhentestedinaccordancewithASMEN510-1989*.l j

e.

After each complete or partial replacement of a HEPA filter bank j

by verifying that the HEPA filter banks remove greater than or equal to 99.5% of the DOP when they are tested in-place in accordance with Section 10 of ANSI N510-1980 while operating the system at a flow rate indicated in Note 1.

f.

After each complete or partial replacement of a charcoal adsorber bank by verifying that the charcoal adsorbers remove greater than or equal to 99.5% of a halogenated hydrocarbon refrigerant test j

gas when they are. tested in-place in accordance with section 12 of ANSI N510-1980 while operating the system at a flow rate indicated in Note 1.

1 Note 1.

a.

Control Room Recirculation Filter Unit 2000 cfm 2 10%

b.

Control Room Filter Unit 1000 cfm i 10%

c.

Control Room Pressurization Filter Unit 300 efm i 10%

Note 2.

a.

Control Room Recirculation Filter Unit 2 994 b.

Control Room Filter Unit 2 994 c.

Control Room Pressurization 2 99.825%

  1. surveillance Requtrement 4.7.7.1.d.2 does not apply in MODES 5 and 6.
  • The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

FARLEY-UNIT 2 3/4 7-17a AMENDMENT NO.

PLANT SYSTEMS

[ 211,:.8 PENETRATION ROOM FILTRATION SYSTEM LIMITING CONDITION FOR OPERATION 3.7.8 Two independent penetration room filtration systems shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, 3 and 4.

ACTION:

With one penetration room filtration system inoperable, restors the inoperable system to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS i

4.7.8 Each penetration room filtration system shall be demonstrated OPERABLE:

At least once per 31 days on a STAGCERED TEST BASIS by initiating, a.

from the control room, the flow through the HEPA filters and charcoal adsorbers and verifying that the system has operated for st least 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> with the heaters on during the past 31 days.

a b.

At least once per 18 months or (1) after any structural maintenance on the HEPA filter or charcoal adsorber housings, or (2) following painting, fire or chemical release that could have contaminated the charcoal adsorbers or HEPA filters in any ventilation zone communicating with the system by:

1.

Verifying that the cleanup system satisfies the in-place testing acceptance criteria of greater than or equal to 99.5% filter efficiency while operating the system at a flow rate of 5000 cfm i 10 percent and using the following test procedures:

(a)

A visual inspection of the penetration room filtration system shall be made before each DOP test or activated carbon adsorber section leak test in accordance with ASME N510-1989*.

l (b)

An in-place DOP test for the HEPA filters shall be performed in accordance with Section 10 of ANSI N510-1980.

(c)

A charcoal adsorber section leak test with a gaseous halogenated hydrocarbon refrigerant shall be performed in accordance with Section 12 of ANSI N510-1980.

  • The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

FARLEY-UNIT 2 3/4 7-18 AMENDMENT NO.

l t

PLANT SYSTEMS l

f

' DURVIILLANCE REQUIREMENTS (Continued) 2.

Verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with section 13 of ANSI N510-1980 meets the laboratory testing criterion of greater than or equal to 95%

efficiency when tested with methyl iodide at 80*C and 70%

relative humidity.

3.

Verifying a system flow rate of 5000 cfm i 10% during system operation when tested in accordance with ASME N510-1989*.

l l

After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber operation by verifying 5

c.

within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI F510-1980 meets the laboratory testing criteria of i

greater thar4 er equal to'95% efficiency when tested with methyl iodide at 83*C and 70% relative humidity.

d.

At least once per 18 months by:

.1.

Verifying that the pressure drop across the combined HEPA filters and charcoal adsorber banks of less than 6 inches Water Gauge while operating the system at a flow rate of

)

5000 cfm i 10%.

2.

Verifying that the system starts on a Phase B Isolation test

']

signal.

u 3.

Verifying that the heaters dissipate 25 1 2.5 kw when tested in accordance with ASME N510-1989*.

l e.

After each complete or partial replacement of a HEPA filter bank by verifying that the HEPA filter banks remove greater than or equal to 99.5% of the DOP when they are tested in-place in accordance with Section 10 of ANSI N510-1980 while operating the system at a flow rate of 5000 cfm i 104.

l i

f.

After each complete or partial replacement of a charcoal adsorber bank by verifying that the charcoal adsorbers remove greater than or equal to 99.5% of a halogenated hydrocarbon refrigerant test gas when they are tested in-place in accordance

~

with Section 12 of ANSI N510-1980 while operating the system at a flow rate of 5000 cfm i 10%.

  • The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

FARLEY-UNIT 2 3/4 7-19 AMENDMENT NO.

j i

f l

REFUELING OPERATIONS

$ KURkEILLANCE REQUIREMENTS (Continued)

L a

1.

Verifying that the cleanup system satisfies the in-place testing acceptance criteria of greater than or equal to 4

99.5% filter efficiency while operating the main purge system and using the following test procedures:

(a)

A visual inspection of the containment purge exhaust filter system shall be made before each DOP test or a

activated carbon adsorber section leak test in.

accordance with ASME N510-1989*.

l i

(b)

An in-place DOP test for the HEPA filters shall be performed in accordance with Section 10 of ANSI N510-1980.

i 1

(c)

A charcoal adsorber section leak test with a gasecus j

halogenated hydrocarbon refrigerant shall be performed in accordance with section 12 of ANSI N510-1980.

l 2.

Verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in l

accordance with Section 13 of ANSI N510-1980 meets the laboratory testing criterion of greater than or equal to

}

904 efficiency when tested with methyl iodide at 80*C and

{

70% relative humidity.

I j

b.

After every 12 months of charcoal adsorber operation by verifying within 31 days after removal that a laboratory

}

analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the I

i; laboratory testing criterion of greater than or equal to 904 efficiency when tested with methyl iodide at 80*C and 70%

[

relative humidity.

l c.

At least once per 18 months by verifying that the pressure drop across the combined HEPA filters and charcoal adsorber banks is less than 6 inches Water Gauge while operating the main purge.

4 system.

T 1

t i

l

  • The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

i i

J FARLEY-UNIT 2 3/4 9-17 AMENDMENT NO.

4 1

1 1

i 3

1 Joseph M. Farley Nuclear Plant Control Room, Penetration Room, and Containment Purge Filtration Systems Surveillance Requirements Technical Specification Changes i

Units 1&2 Marked-Un Technical Specification Panes I

j I

N d

. - ~ - -... - -. -

- _ -. =

l j

i l

Joseph M. Farley Nuclear Plant i

Control Room, Penetration Room, and Containment Purge Filtration Systems l

Surveillance Requirements Technical Specification Changes Unit 1 Marked-Un Technical Specification Panes 1

l i

f i

J l

l l

PLANT SYSTEMS i

$ SLfRVbILLANCE REQUIREMENTS (Continued) b.

At least once per 18 months or (1) after any structural j

maintenance on the HEPA filter or charcoal adsorber housings, or j

(2) following painting, fire or chemical release that could have contaminated the charcoal adsorbers or HEPA filters in any ventilation zone communicating with the system by:

1.

Verifying that the cleanup system satisfies the in-place

{

testing acceptance criteria of greater than or equal to 99.5% filter efficiency while operating the system at a flow rate indicated in Note 1 and using the following test procedures:

(a)

A visual inspection of the control room emergency air cleanup system shall be made before each DOP test or activated carbon adsorber section leak test in accordance with C :ti:n 5 cf.'2?CIASME N510-194GI989*.

l (b)

An in-place DOP test for the HEPA filters shall be performed in accordance with Section 10 of ANSI N510-1980.

(c)

A charcoal adsorber section leak test with a gaseous halogenated hydrocarbon refrigerant shall be performed in accordance with Section 12 of ANSI N510-1980.

2.

Verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing efficiencies criteria given in Note 2 4

when tested with methyl iodide at 80*C and 70% relative humidity.

3.

Verifying a system flow rate as indicated in Note 1 during system operation when tested in accordance with C::ti:n 0 Of ASME ANGE-N510-446GI989*.

c.

After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber operation by verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing efficiencies criteria given in Note 2 when tested with methyl iodide at 80*C and 70% relative humidity.

  • The FNP Final Safety Analysis Report identifies the relevant surveillance cesting requirements.

FARLEY-UNIT 1 3/4 7-17 AMENDMENT NO.

PLANT SYSTEMS

.$ StIRVhhILLANCE REQUIREMENTS (Continued) i d.

At least once per 18 months by:

1.

Verifying that the pressure drop across the combined HEPA filters and charcoal adsorber banks is less than 6 inches Water Gauge while operating the system at a flow rate indicated in Note 1.

2.

Verifying that the filter train starts on a Safety Injection Actuation test signal.#

1 3.

Verifying that the system maintains the control room at a i

positive pressure of greater than or equal to 1/8 inch water gauge relative to the outside atmosphere during system operation.

t 4.

Verifying that the pressurization system heater dissipates 7.5 t 0.8 kw when tested in accordance with C::ti:n it Of 4

i ASME ANG4--N510--l-9842989*.

i e.

After each complete or partial replacement of a HEPA filter bank by verifying that the HEPA filter banks remove greater than or equal to 99.5% of the DOP when they are tested in-place in I

accordance with Section 10 of ANSI N510-1980 while operating the system at a flow rate indicated in Note 1.

f.

After each complete or partial replacement of a charcoal adsorber bank by verifying that the charcoal adsorbers remove greater than or equal to 99.5% of a halogenated hydrocarbon refrigerant test i

gas when they are tested in-place in accordance with Section 12 of ANSI N510-1980 while operating the system at a flow rate indicated in Note 1.

Note 1.

a.

Control Room Recirculation Filter Unit 2000 cfm i 10%

b.

Control Room Filter Unit 1000 cfm i 10%

c.

Control Room Pressurization Filter Uhit 300 cfm 2 10%

Note 2.

a.

Control Room Recirculation Filter Unit 2 99%

b.

Control Room Filter Unit 2 99%

c.

Control Room Pressurization 2 99.825%

  1. Surveillance Requirement 4.7.7.1.d.2 does not apply in MODES 5 and 6.
  • The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

FARLEY-UNIT 1 3/4 7-17a AMENDMENT NO.

l

PLANT SYSTEMS

.3/'4.k9 PENETRATION ROOM FILTRATION SYSTEM LIMITING CONDITION FOR OPERATION 3.7.8 Two independent penetration room filtration systems shall be OPERABLE.

APPLICABILTTY:

MODES 1, 2,

3 and 4.

ACTION:

With one penetration room filtration system inoperable, restore the inoperable system to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS j

1 4.7.8 Each penetration room filtration system shall be demonstrated OPERABLE:

j a.

At least once per 31 days on a STAGGERED TEST BASIS by initiating, from the control room, the flow through the HEPA filters and I

charcoal adsorbers and verifying that the system has operated for at least 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> with the heaters on during the past 31 days.

b.

At least once per 18 months or (1) af ter a%f structural maintenance on the HEPA filter or charcoal adsorber housings, or (2) following painting, fire or chemical release that could have contaminated the charcoal adsorbers or HEPA filters in any ventilation zone communicating with the system by:

1.

Verifying that the cleanup system satisfies the iniplace testing acceptance criteria of greater than or equal to 99.5% filter efficiency while operating the system at a flow rate of 5000 cfm i 10 percent and using the following test procedures:

)

(a)

A visual inspection of the penetration room filtration system shall be made before each DOP test or activated carbon adsorber section leak test in accordance with

ti;.. 5 'cf ASME AN64-N510-H941989*.

l (b)

An in-place DOP test for the HEPA filters shall be performed in accordance with Section 10 of ANSI N510-1980.

(c)

A charcs:1 adsorber section leak test with a gaseous halogenated hydrocarbon refrigerant shall be performed in accordance with Section 12 of ANSI N510-1980.

  • The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

FARLEY-UNIT 1 3/4 7-18 AMENDMENT NO.

,,sL

.+.

e o

PLANT SYSTEMS

..StiftVbILLANCE REQUIREMENTS (Continued) 2.

Verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing criterion of greater than or equal to 95%

efficiency when tested with methyl iodide at 80*C and 70%

relative humidity.

3.

Verifying a system flow rate of 5000 cfm ;

e during system operation when tested in accordance with E

- n 0 Of ASME ANG4-N510 -44841989 *.

c.

After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber operation by verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing criterion of greater than or equal to 95%

efficiency when tested with methyl iodide at 80*C and 70%

relative humidity.

d.

At least once per 18 months by:

1.

Verifying that the pressure drop across the combined HEPA filters and charcoal adsorber banks of less than 6 inches Water Gauge while operating the system at a flow rate of l

5000 cfm i 10%.

2.

Ve-ifying that the system starts on a Phase B Isolation test signal.

3.

Verifying that the heaters dissipate 25 1 2.5 kw when tested in accordance with 0;;ti;n M ;f ASME ANG4-N510-49692989*.

l e.

After each complete or partial replacement of a HEPA filter bank by verifying that the HEPA filter banks remove greater than or equal to 99.5% of the DOP when they are tested in-place in accordance with Section 10 of ANSI N510-1980 while operating the system at a flow rate of 5000 cfm i 10%.

f.

After each complete or partial replacement of a charcoal adsorber bank by verifying that the charcoal adsorbers remove greater than or equal to 99.5% of a halogenated hydrocarbon refrigerant test gas when they are tested in-place in accordance with Section 12 of ANSI N510-1980 while operating the system at a flow rate of 5000 cfm i 10%.

  • The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

FARLEY-UNIT 1 3/4 7-19 AMENDMENT NO.

PEFUELTNG OPERATIONM

< a SURVEILLANCE REQUIRea4ENTS (Continued) d 1.

Verifying that the cleanup system satisfies the in-place testing acceptance criteria of greater than or equal to 99.5% filter efficiency while operating the main purge system and using the following test procedures:

(a)

A visual inspection of the containment purge exhaust filter system shall be made before each DOP test or activated carbon adsorber section leak test in accordance with 0;; tic: 5 Of ASME ANGI-N510-44842989*. l (b)

An in-place DOP test for the HEPA filters shall be performed in a ccordance with Section 10 of ANSI N510-1980.

(c)

A charcoal adsorber section leak test with a gaseous halogenated hydrocarbon refrigerant shall be performed in accordance with Section 12 of ANSI N510-1980.

2.

Verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing criterion of greater than or equal to 90% efficiency when tested with methyl iodide at 80*C and 70% relative humidity, b.

After every 12 months of charcoal adsorber operation by verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing criterion of greater than or equal to 90%

efficiency when tested with methyl iodide at 80*C and 70%

relative humidity.

c.

At least once per 18 months by verifyir3 that the pressure drop across the combined HEPA filters and charcoal adsorber banks is less than 6 inches Water Gauge while operating the main purge system.

l

  • The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

4

(

FARLEY-UNIT 1 3/4 9-17 AMENDMENT NO.

Joseph M. Farley Nuclear Plant Control Room, Penetration Room, and Containment Purge Filtration Systems Surveillance Requirements Technical Specification Changes Unit 2 Marked Un Technical Specification Pares

~.

i PLANT SYSTEMS

\\

,!SURV21LLANCE REQUIREMENTS. - _

(Cont.nued) b.

At least once per 18 months or (1) after any structural maintenance on the HEPA filter or charcoal adsorber housings, or (2) following painting, fire or chemical release that could have contaminated the charcoal adsorbers or HEPA filters in any ventilation zone communicating with the system by:

1.

Verifying that the cleanup system satisfies the in-place testing acceptance criteria of greater than or equal to 99.5% filter efficiency while operating the system at a flow rate indicated in Note 1 and using the following test procedures:

(a)

A visual inspection of the control room emergency air cleanup system shall be made before each DOP test or activated carbon adsorber section leak test in accordance with C;;ti n 5 Of ASME ANGE--N510-446G1989*.

l (b)

An in-place DOP test for thc HEPA filters shall be performed in accordance with Section 10 of ANSI N510-j 1980.

(c)

A charcoal adsorber section leak test with a gaseous halogenated hydrocarbon refrigerant shall be performed i

in accordance with Section 12 of ANSI N510-1980.

2.

Verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing efficiencies criteria given in Note 2 i

when tested with methyl iodide at 80*C and 70% relative

)

humidity.

3.

Verifying a system flow rate as indicated in Note 1 during system operation when tested in accordance with 0;;ti:n 0 of ASME ANGE--N510-k9601989*.

I c.

After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber operation by I

verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing efficiencies criteria'given in Note 2 when tested with methyl iodide at 80*C and 70% relative humidity.

l

  • The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

j FARLEY-UNIT 2 3/4 7-17 AMENDMENT NO.

e.. e PLANT SYSTEMS SOVEILLANCE REQUIREMENTS (Continued) d.

At least once per 18 months by:

1.

Verifying that the pressure drop across the combined HEPA filters and charcoal adsorber banks is less than 6 inches Water Gauge while operating the system at a flow rate 1

indicated in Note 1.

2.

Verifying that the filter train starts on a safety Injection Actuation test sigval.#

3.

Verifying that the system maintains the control room at a positive pressure of greater than or equal to 1/8 inch water gauge relative to the outside atmosphere during system operation.

4.

Verifying that the pressurization system heater dissipates 7.5 1 0.8 kw when tested in accordance with C;;ti 10 Of ASME ANG5-N510- A4941989 *.

i i

e.

After each complete or partial replacement of a HEPA filter bank l

by verifying that the HEPA filter banks remove greater than or equal to 99.5% of the DOP when they are tested in-place in

{

accordance with Section 10 of ANSI N510-1980 while operating the system at a flow rate indicated in Note 1.

f.

After each complete or partial replacement of a charcoal adsorber bank by verifying that the charcoal adsorbers remove greater than or equal to 99.5% of a halogenated hydrocarbon refrigerant test gas when they are tested in-place in accordance with Section 12 of ANSI N510-1980 while operating the system at a flow rate indicated in Note 1.

Note 1.

a.

Control Room Recirculation Filter Unit 2000 cfm i 10%

b.

Control Room Filter Unit 1000 cfm i 10%

i c.

Control Room Pressurization Filter Unit 300 cfm i 10%

Note 2.

a.

Control Room Recirculation Filter Unit 2 99%

b.

Control Room Filter Unit 2 99%

c.

Control Room Pressurization 2 99.825%

i

  1. Surveillance Requirement 4.7.7.1.d.2 does not apply in MODES 5 and 6.
  • The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

FARLEY-UNIT 2 3/4 7-17a AMENDMENT NO.

, s.

  • PLANT SYSTEMS A 2/_1. *e P. 9 PENETRATION ROOM FILTRATION SYSTEM LIMITING CONDITION FOR OPERATION 3.7.8 Two independent penetration room filtration systems shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, 3 and 4.

ACTION:

With one penetration room filtration system inoperable, restore the inoperable system to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.7.8 Each penetration room filtration system shall be demonstrated OPERABLE:

At least once per 31 days on a STAGGERED TEST BASIS by initiating, a.

from the control room, the flow through the HEPA filters and charcoal adsorbers and verifying that the system has operated for at least 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> with the heaters on during the past 31 days.

b.

At least once per 18 months or (1) after any structural maintenance on the HEPA filter or charcoal adsorber housings, or (2) following painting, fire or chemical release that could have contaminated the charcoal adsorbers or HEPA filters in any ventilation zone communicating with the system by:

1.

Verifying that the cleanup system satisfies the in-place I

testing acceptance criteria of greater than or equal to 99.5% filter efficiency while operating the system at a flow rate of 5000 cfm i 10 percent and using the following test procedures:

(a)

A visual inspection of the penetration room filtration system shall be made before each DOP test or activated carbon adsorber section' leak test in accordance with

ti
:. I ;f ASME ANG4-N510-Mi401989*.

l (b)

An in-place DOP test for the HEPA filters shall be performed in accordance with Section 10 of ANSI N510-1980.

(c)

A charcoal adsorber section leak test with a gaseous halogenated hydrocarbon refrigerant shall be performed in accordance with Secticn 12 of ANSI N510-1980.

The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

FARLEY-UNIT 2 3/4 7-18 AMENDMENT NO.

PLANT SYSTEMS

.eSL*1VIILLANCE REQUIREMENTS (Continued) 2.

Verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing criterion of greater than or equal to 95%

efficiency when tested with methyl iodide at 80*C and 70%

relative humidity.

3.

Verifying a system flow rate of 5000 cfm i 10% during system operation when tested in accordance with C::ti:n S ;f ASME ANGE-N510 9692989 *.

After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber operation by verifying c.

within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing criteria of greater than or equal to 95% efficiency when tested with methyl iodide at 80*C and 70% relative humidity.

4 d.

At least once per 18 months by:

1.

Verifying that the pressure drop across the combined HEPA 4

filters and charcoal adsorber banks of less than 6 inches water Gauge while operating the system at a flow rate of 5000 cfm i 10%.

I 2.

Veritying that the system starts on a 9hase B Isolation test sigral.

3.

Verifying that the heaters dissipate 25 i 2.5 kw when tested in accordance with 0;;ti;; 10 ;f ASME ANGE-N510-498G2989*.

l e.

After each complete or partial replacement of a HEPA filter bank by verifying that the HEPA filter banks remove greater than or equal to 99.5% of the DOP when they are tested in-place in accordance 'with Section 10 of ANSI N510-1980 while operating the system at a flow rate of 5000 cfm i 10%.

f.

After each complete or partial replacement of a charcoal adsorber bank by verifying that the charcoal adsorbers remove greater than or equal to 99.5% of a halogenated hydrocarbon refrigerant test gas when they are tested in-place in accordance with Section 12 of ANSI N510-1980 while operating the system at a flow rate of 5000 cfm i 10%.

The FNP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

FARLEY-UNIT 2 3/4 7-19 AMENDMENT NO.

i REPUEY,TNG OPERATIONE

,,., a

  • +. <

'SIRV2ILLANCE REQUIREMENTS (Continued) i 1.

Verifying that the cleanup system satisfies the in-place testing acceptance criteria of greater than or equal to i

99.5% filter efficiency while operating the main purge system and using the following test procedures:

J (a)

A visual inspection of the containment purge exhaust filter system shall be made before each DOP test or activated carbon adsorber section leak test in accordance with S;;ti:n 5 cf ASME ANGE-N510-19642989*. l 1

(b)

An in-place DOP test for the HEPA filters shall be performed in accordance with Section 10 of ANSI N510-1980.

1 (c)

A charcoal adsorber section leak test with a gaseous halogenated hydrocarbon refrigerant shall be performed in accordance with Section 12 of ANSI N510-1980.

2.

Verifying within 31 days after removal that a laboratory analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing criterion of greater than or equal to 90% efficiency when tested with methyl iodide at 80*C and 70% relative humidity.

b.

After every 12 months of charcoal adsorber operation by verifying within 31 days after removal that a laboratory J

analysis of a representative carbon sample obtained in accordance with Section 13 of ANSI N510-1980 meets the laboratory testing criterion of greater than or equal to 90%

efficiency whsn tested with methyl iodide at 80*C and 70%

relative humidity.

I c.

At least once per 18 months by veritying that the pressure drop across the combined HEPA filters and charcoal adsorber banks is less than 6 inches Water Gauge while operating the main purge system.

I

  • The FWP Final Safety Analysis Report identifies the relevant surveillance testing requirements.

1 FARLEY-UNIT 2 3/4 9-17 AMENDMENT NO.