Monthly Operating Rept for Jul 1985
ML20134F688
Person / Time
Site: Indian Point 
Issue date: 07/31/1985
From: Josiger W, Kelly L
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To:
NRC OFFICE OF ADMINISTRATION (ADM)
References
IP-LK-1988, NUDOCS 8508210219
Download: ML20134F688 (7)


Text

3 I

OPERATING DATA REPORT 50-286 DOCKET NO.

DATE 8-1-85 COMPLETED BY L Meliv TELEPHONE

'914) 739-8200 OPERATING STATUS Notes Indian Point No. 3 Nuclear Power Plant

1. Unit Name: _

July 1985

2. Reporting Period:

3025

3. Licensed Thermal Power (MWt):

1013

4. Nameplate Rating (Gross MWe):

965

5. Design Electrical RatingINet MWe):

1000

6. Maximum Dependable Capacity (Gross MWe):

965

7. Maximum Dependable Capacity (Net MWe):
8. If Changes Occur in Capacity Ratingi(Items Number 3 Through 7) Since Last Report. Give Reasons:
9. Power Level To which Restricted,if Any (Net MWe):
10. Reasons For Restrictions. If Any:

This Month Yr to.Date Cumulative 744 5087 78192

11. Hours in Reporting Period
12. Number Of Hours Reactor Was Critical 0

0 0

13. Reactor Reserve Shutdown Hours 3704 99 43552 93 0
14. Hours Generator On.Line 0

0 0

15. Unit Reserve Shutdown Hours 0

lo,235,662 115,940,609

16. Gross Thermal Energy Generated (MWH) 3,358,410 36.000.725 0
17. Gross Electrical Energy Generated (MWH) 3,229,876 34,515,992 O
18. Net Electrical Energy Generated (MWHn 72.8 55.7 0
19. Unit Service Factor 0

72.8 55.7 47.9 *

20. Unit Availability Factor 65.8 45.7 O
21. Unit Capacity Factor (Using MDC Net) 65.8 0

0 2.3 20.4

22. Unit Capacity Factor (Using DER Net)
23. Unit Forced Outage Rate
  • Weighted Average
24. Shutdowns Scheduled Over Next 6 Months IType. Date.and Duration of Eacht:

(Est. September 1985) 25 If Shut Down At End Of Report Period. Estimated Date of Startup:

Forecast Achieved 26 Units in Test Status (Prior to Commercial Operation):

INITIAL CRITICALITY INITIAL ELECTRICITY t rnturarl A1. OPERATION I

8508210219 B50731 e

PDR ADOCK 05000286 g Tk

(

R PDR

0 D

AVERAGE DAILY UNIT POhER LEVEL DOCKET NO.

50-286 Indian Point LWIT No. 3 DATE 8/1/85 COMPLETED BY 1

vol l "

TELEPHONE (914) 739-8200 MONT11 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)

MWe-Net) 0 g7 0

1 2

n 18 n

0 3

39 0

4 0

20 n

5 n

21 0

6 0

22 n

0 7

33 0

g n

24 9

9 0

25 0

10

'O 26 n

O 0

iI 37 0

12 2g 0

13 0

29 n

14 0

30 0

15 0

31 n

16 0

INSTRUCTIONS On this format, list the average daily umt power level in MWe Net for each day in the reporting month. Compute to the nearest whole megawatt.

(9177i

DOCKE1?!O.

fit -28 UNIT SilUTDOWNS /.ND POWER REDUCTIONS UNil NAME DATE n /1 /n R COMPLETED BY L

hi l "

REPORT MONTil Tuly lonR IELEPIIONE 914-739-82'00 5

E 5g 3

jY3 Licensee E,

ge Cause & Corrective o

No.

Dale Q

3g d

2 ~$

Event

7. 'g M

Action to l coori #

iE U 5O Preseni Recurrence y=

5 ug H

jj =!

U e

6 06 85-06-08 S

744 C

2 N/A ZZ ZZZZZZ Unit in a scheduled Cycle IV - V Refueling Outage.

I 2

3 4

F: Forced Reason:

Metin>d:

Exhibit F-Instructions S: Scheduled A Equipment Failure (Explain) 1-Manual for Pieparation of Data H-Maintenance of Test 2-Manual Scram.

Eintoy Sheets for lxensee C Refueling 3-Automatic Scram.

liven Repmi (1.1 RI file (NllRI G-D Regulatory Restriction 4 Other (Explam) 0161) li-Operator Tsaining & License Examination F-Administ rative 5

G Operational Estos (Explain) l%hibit 11-Same Source (9/77) ll-01her ( Explain)

MONTHLY MAINTENANCE CATEGORY I REPORT JULY 1985 MONTH WR#

DATE EQUIPMENT MALFUNCTION CORRECTIVE ACTION 6465 7/1/85

  1. 32 Aux. Boiler Feed Pump Trap blowdown valve leaks by Replaced valve Turbine Main Steam Trap, MST-64 6429 7/2/85 Containment Pressure Relief Valves sluggish Cleaned solenoid valve Valves, PCV-1191 and 1192 5624 7/11/85 IVSWS Fill Valve Fill valve leaks Replaced valve diaphram 1455 5729 7/11//85 Component Cooling Water Body to bonnet leak Replaced diaphragm Valve 798 6795 7/12/85 Bit Tank Recire. Flow Flow indicator Replaced BIT flow rotameter Indicator, FI-916 leaks 4896 7/18/85
  1. 32 Instrument Air Solenoid valve leaks Replaced solenofd valve Compressor, Load / Unload Solenoid Valve 5702 7/18/85 CVCS Excess Let Down Solenoid valve leaks replaced solenoid valve Valve, 213A 6821 7/19/85
  1. 31 and #32 Instrument Air Heat exchanger fouled Cleaned heat exchanger tube:s Closed Cooling Heat Exchangers 6679 7/20/85
  1. 31 Instrument Air Solenoid valve leaks Replaced solenoid valve Compressor air Load / Unload Solenoid Valve e

MONTHLY I & C CATEGORY I REPORT JULY 1985 MONTH WR#

DATE EQUIPMENT MALFUNCTION CORRECTIVE ACTION 4344 7 /4 /8.3

  1. 31 Steam Generator Bottom impulse line to Cleared line Wide Range Level transmitter clogged Transmitter,LT-417D 4331 7/6/85 Auxiliary Feedwater Flow Air leakage from valve Replaced pipe fitting Control Valve, FCV-406A positioner 3238 7/13/85 Rod Position Indicator, Improper power supply Replaced, repaired Power Supplies #1,2,3,4 output and adjusted power supplies.

4370 7/13/85 Plant Vent Radiciodine Monitor reads high Recalibrated drawer Monitoring System, assembly.

Channel I 4301 7/24/85 V.C. Weld Channel Pressure CCR indication Repaired light Controller PC-1150S-248 not functioning socket contacts 4304 7/24/85 V.C. Weld Channel Pressure CCR indication Repaired light socket Controllers, PC-1150S-215 not functioning contacts.

4405 7/24/85

  1. 31 Boric Acid Transfer Redundant circuit had no Repaired loose wire Pump Electrical Heat Trace indication e

e W

Summary of Operating Experience July 1985 Indian Point Unit 3 remained shutdown for the cycle 4/5 refueling outage for the entire reporting period.

3

~

f n

J

4..

1 Indian Fbint 3 Nuclear Ibwer Plant PO. Box 215 Buchanan, New York 10511 914 739.8200

  1. > NewYorkPower "f=Ain;;';,-

1sf Authority August 13, 1985 IP-IK-1988 Docket No. 50-286 License No. DPR-64 Director, Office of Inspection and Enforcement U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Attention: Document Control Desk

Dear Sir:

Enclosed you will find twelve copies of the monthly operating report relating to Indian Point 3 Nuclear Power Plant for the month of July, 1985.

Very truly yours,

$Y0 w K Wil-1 A J iger ident ger IK/jm Enclosures (12 Copies) cc:

Dr. 'Ihomas E. Murley, Regional Administrator Region 1 U. S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, Pennsylvania 19406 IP3 Resident Inspectors' Office George Wilverding (SRC), WPO J. C. Brons, WPO S. V. Fuller,IEO W. R. Yario,1EO INIO Records Center Suite 1500 1100 Circle 75 Parkway Atlanta, Georgia 30339 l