ML20134E432

From kanterella
Jump to navigation Jump to search
Primary Reactor Containment Integrated Leakage Rate Test Rept
ML20134E432
Person / Time
Site: Calvert Cliffs 
Issue date: 05/31/1985
From:
BECHTEL GROUP, INC.
To:
Shared Package
ML20134E414 List:
References
SU-084, SU-84, NUDOCS 8508200214
Download: ML20134E432 (52)


Text

. _ -- _ _ _.

l O

BALTIMORE GAS AND ELECTRIC COMPANY CALVERT CLIFFS NUCLEAR POWER PLANT UNIT 1 PRIMARY REACTOR CONTAINMENT INTEGRATED LEAKAGE RATE TEST REPORT O

MAY 1985 I

PREPARED BY BECHTEL POWER CORPORATION SAN FRANCISCO, CA i

O 8508200214 850005 DR ADOCK 05000317 p

PDR SU-084

O CONTENTS Section Pg INTRODUCTION 1

TEST SYNOPSIS 1

TEST DATA

SUMMARY

3 ANALYSIS AND INTERPRETATION 8

REFERENCES 10 APPENDICES A.

Description of Bechtel ILRT Computer Program B.

Pressurization and Stabilization Summary Data C.

ILRT Trend Report D.

ILRT Summary Data, Mass Point, and Total Time E.

Plots; Airmass, Temperature, Pressure, Vapor Pressure, and Leakage Rate F.

Verification Flow Sunanary and Data G.

ISG Calculations H.

Local Leakage Rate Test Evaluation 1.

Malfunctioning Sensor Plots O

SU-084

O EXECUTIVE

SUMMARY

A Primary Containment Integrated Leakage Rate Test (ILRT) was successfully completed at the Calvert Cliffs Nuclear Power Plant, Unit 1, on May 20, 1985. The test met the requirements set forth in 10CFR50, Appendix J.

l Listed below is the summary of the test results for both the mass point and total time data analysis techniques. The actual measured leakage (L,,) and the 95 percent upper confidence limit (UCL), in units of weight percent per day, are compared to the acceptance criteria.

Mass Point Test Result Acceptance Criteria ILRT Lam 0.032 0.150 ILRT UCL 0.035 0.150 Verification Test Lam 0.201 0.155 < Lam < 0. 25 5 Total Time ILRT Lam 0.025 0.150 ILRT UCL 0.069 0.150 Verification Test Lam 0.166 0.148 < Lam < 0. 248 The total local leakage rate measured for the eight penetrations not in the post-LOCA lineup during the ILRT was 0.002%/ day.

The chronological summary of events, summary of plant technical data, and discussion of test results are included in portions of this report.

O SU-084

I.

INTRODUCTION This report presents data, analysis, and conclusions pertaining to the Calvert Clif fs Nuclear Power Plant Unit 1 Integrated Leakage Rate Test (ILRT) performed in May 1985. The Integrated Leakage Rate Test (Type A) is performed periodically to demonstrate that the combined leakage through the reactor containment and those systems penetrating the containment does not exceed the allowable leakage rate specified in the Plant Technical Specifications.

The successful periodic Type A and supplemental verification tests were performed according to the requirements of the Calvert Cliffs Nuclear Power Plant, Unit 1, Technical Specifications and 10CFR50, Appendix J.

The Calvert Cliffs Type A test method is the Absolute Method described in ANSI N45.4-1972, " Leakage Rate Testing of Containment Structures for Nuclear Reactors" and ANSI /ANS 56.8-1981,

" Containment System Leakage Testing Requirements." The leakage rate was calculated using formulas from the above ANSI Standards and BN-TOP-1, Rev 1, " Testing Criteria for Integrated Leakage Rate Testing of Primary Containment Structures for Nuclear Power Plants." Type A and verification test durations were according to the criteria of BN-TOP-1.

A 95% upper confidence level was calculated for leakage rate data as required by Reference 6.

This is to ensure a 95% probability that the calculated leakage rate value is within the acceptance limits. All i

calculations were done with Bechtel's ILRT computer program described in Appendix A.

The temperature and pressure history and the containment air mass f

variations were plotted by the computer program and are contained in Appendix E.

1 II.

TEST SYNOPSIS Valve line-ups were conducted on all systems to e tablish post-accident conditions except for shutdown cooling, steam generator aanways and manholes and three penetrations necessary to conduct the ILRT. The inspection of the containment's accessible interior and exterior surfaces was conducted prior to pressurization. No evidence of structural deterioration was noted which would have affected containment integrity or leak tightness.

Containment pressurization commenced at 1:00 pm, May 18,1985. At 3:30 pm, pressurization was stopped to investigate an observed 100 inch water level decrease (approximately 3000 gal.) in the pressurizer. At 5:25 pm the pressurizer was refilled and pressurization restarted. At 7:45 pm the sumps were drained due to a high sump water level reading.

O-SU-084 1

O)

Test pressure of 50.5 psig was reached at 2:44 am, May 19,1985.

The i

pressurization line was vented and the containment coolers and fans s

were stopped in stages between 3:00 am and 6:40 am.

Containment pressure continued to increase due to increasing containment In order to satisfy procedural requirements on the test temperature.the upper limit on the test pressure was raised from 50.5

pressure, psig to 52.0 psig. The temperature stabilization criteria were satisfied during the four hours f rom 9:30 am to 1:30 pm.

Collection of data to determine the integrated leakage rate commenced at 1:30 pm, May 19,1985 and was completed at 11:30 pm.

The verifica-tion flow test was initiated at 0:30 am, May 20, 1985. The verifica-tion flow test was completed satisf actorily and depressurization of the containment commenced at 7:40 am, May 20, 1985. After the containment was completely depressurized at 10:30 pm, May 20,1985, a containment entry was made. Determination was made that no measurable water level changes requiring corrections to the measured leakage rate had occurred during the test. Summary of test phases were as follow:

Test Phase Time Duration hr.

Date Pressurization 1300 - 0244 14.73 May 18-19 Stabilization 0245 - 1315 10.5 May 19 ILRT 1330 - 2330 10.0 May 19

(

Verification Initiation 2345 - 0015 0.5 May 19-20 Verification Stabilization 0030 - 0130 1.0 May 20 Verification Test 0130 - 0630 5.0 May 20 During the test two temperature sensors were malfunctioning.

Temperature sensor 13, located in ill steam generator cavity indicated a decreasing temperature starting at 9:30 am on May 19.

Since all other temperature sensors indicated an increase in temperature, sensor 13 was judged to be malfunctioning and its volume fraction assigned to temperature sensor 6, located in #12 steam generator cavity. Tempera-ture sensor 14 consistently indicated temperatures approximately 6 to 7'F lower than adjacent sensors which was inconsistent with the tem-Sensor 14 was judged to be malfunctioning and its perature survey.

volume fraction assigned to temperature sensor 12, located at the same elevation. The reassigned volume fractions were used to calculate the containnent dry air mass during the entire test. Plots of temperature sensors 13 and 14 are in Appendix I.

v SU-084 2

l III. TEST DATA

SUMMARY

A.

Plant Information Owner:

Baltimore Gas and Electric Company Plant:

Calvert Cliffs Nuclear Power Plant Unit 1 Location:

Lusby, Maryland Containment Type:

Post-tensioned concrete Data Test Completed:

May 20,1985 Docket No.:

50317 B.

Technical Data 1.

Containment Net Free Air Volume 2,000,000 cu. ft.

2.

Design Pressu:e 50 psig 3.

Design Temperature 276*F 4.

Calculated Peak Accident 50 psig pressure Pa 5.

Containment ILRT Average 60-120*F Temperature Limits

()

C.

Type A Test Result 1.

Test Method Absolute 2.

Leakage Rate Data Analysis Total Time per BN-TOP-1 and Techniques Mass Point per ANSI /ANS 56.8-1981 3.

Test Pressure 50.0 psig + 2.0*

- 0.0 4.

Maximum Allowable Leakage Rate, 0.2%/ day La, per Technical Specification 5.

75% of La 0.15%/ day D.

Type A Test Results Integrated Leakage Rate From Regression At Upper 95%

Line, %/ day (Lam) Confidence Limit a.

Mass Point Analysis 0.032 0.035 b.

Total Time Analysis 0.025 0.069 O

  • The upper bound on test pressure was increased f rom 50.5 to 52.0 psig to allow for increasing pressure due to increasing containment temperature.

SU-084 3

d

)

E.

Verification Test 1.

Imposed flow rate (Li) 10.75 scfm (0.173%/ day) 2.

Verification Test Results Leakage Rate, %/ day a.

Mass Point Analysis 0.201 b.

Total Time Analysis 0.166 3.

Verification Test Limits Test Limit, %/ day a.

Mass Point Analysis (1) Upper Limit 0.255 (Li + Lam + 0.25 La)

(2) Lower Limit 0.155 (Li + Lam - 0.25 La) b.

Total Time Analysis (1) Upper Limit 0.248 (2) Lower Limit 0.148 F.

Report Printouts The Report Printouts of the Type A and Verification Test calculations are provided for the Mass Point and Total Time Analysis (Appendices C through F). Stabilization data is also provided (Appendix B).

G.

Local Leakage Rate Test Results - Type B and C Tests 1.

LLRT Results - The Type B and C leakage tests were conducted prior to the Type A test. The total as left LLRT measurement for Unit 1 was 28,354.03 secm.

This value converts to 0.016%/ day which is less than the technical specification limit of.12%/ day. An evaluation of "as lef t" compared to "as found" data is contained in Appendix H.

s SU-084 4

('s

(,)

2.

During the ILRT the following penetrations were not in the post accident position. The following is the local leakage rate measurement for these penetrations.

Penetration System As Left, SCCM 7A ILRT Instrumentation 20.4 7B ILRT Instrumentation 494 41 Shutdown Cooling Return 2376 50 ILRT Pressurization 362 11 SG Manway 11-1 59.7 11 SG Manhole 11-2 192 12 SG Manway 12-1 98.2 12 SG Manhole 12-2 62.8 Total:

3655.1 seem

%/ day:

.002%/ day 3.

Periodic Type B and Type C Test Results Since Last ILRT Outage Date LLRT Acceptance Criteria 10/3/83 29,886.94

.6 La = 207,700 scem 4.

10CFR50, Appendix J, paragraph V.B.3 requires that leakage test results from Type A, B, and C tests that failed to meet O,

the acceptance criterla of III.A.5(b), III.B.3 and III.C.3, respectively, shall te reported in a separate accompanying summary report that includes an analysis and interpretation of the test data, the least-squares fit analysis of the test data, the instrumentation error analysis, and the structural condition of the containment or components, if any, which contributed to the failure in meeting the acceptance criteria. Since the tests meet the acceptance criteria no further analysis is submitted. Instruments used during local leakage rate testing are calibrated as follows: j; 1% full scale for flowmeters, and + 0.1% full scale for temperature and pressure gauges. Field checks of flowmeters are performed prior to each test to check calibration.

H.

Integrated Leakage Rate Measurement System The following instrument system was used:

De sc ription Data 1.

Absolute Pressure 2 Precision Pressure Gages Range:

0-100 psia Mensor Model 10100 Accuracy:

0.02% F.S.

Sensitivity:

0.001 psia 1

l

(

Repeatability:

0.001 psia

\\

Calibration Date:

2/26/85 SU-084 5

)

Description Data y

2.

Drybulb Temperature 18 Temperature Sensors Range:

32-120*F Volumetrics 100 ohm Accuracy:

0.20*F Platinum RTD, part no.

Sensitivity:

0.0l*F VSTD-347 Repeatability:

0.0l*F Calibration Date:

2/23/85 3.

Dewpoint Temperature 6 Dewpoint Sensors Range:

40-100*F EG&G Model 660 Chilled Accuracy:

0.54*F Mirror Hygrometers Sensitivity:

0.10' F Repeatability:

0.l*F Calibration Date:

2/25/85 4.

Flowmeters 2 Mass Flowmeters Range:

0-10 scfm (1) TSI Model 2013 0-20 scfm (2) Model 2014 Accuracy:

1% F.S.

Sensitivity:

1% F.S.

Repeatability:

0.1 scfm

,,()

Calibration Date:

3/5/85 5.

Overall Instrumentation Selection Guide (ISG) Value (f rom ANSI /ANS 56.8-1981, Appendix G) based on ILRT instrumentation and ten hour minimum test duration = 0.0067%/ day.

( Calcula-tions Appendix G).

6.

Drybulb and Dewpoint Temperature Sensor Volume Fractions -

Table 1.

I.

Information Retained at Plant The following information is available for review at the Facility:

1.

Listing of all containment penetrations, including the total number of like penetrations, penetration size and function.

2.

Systems lineup (at time of test).

3.

A continuous, sequential log of events during the test.

4 Documentation of instrumentation calibration and standards.

5.

The working copy of test procedure that would include signature sign-off of procedural steps.

/

\\

6.

The procedure and all data from local leakage rate testing of penetrations and valves.

SU-084 6

((

7.

The Quality Assurance audit plan that was used to monitor ILRT.

8.

A listing of all test exceptions including changes in containment system boundaries instituted by licensee to conclude successful testing.

9.

Description of method of leak rate verification of instrument measuring system (superimposed leakage), with calibration information on flowmeters along with calculations that were used to measure the verification leakage rate.

O O-SU-084 7

IV.

ANALYSIS AND INTERPRETATION The Integrated Leakage Rate Test results at the upper 95% confidence level, are Lam = 0.035%/ day (Mass Point analysis) and 0.069%/ day (Total Time analysis). The local leakage rate for penetrations not in post-LOCA lineup is 0.002%/ day. The sums of the ILRT upper 95%

confidence level and LLRT leakage rates, Lam = 0.037%/ day (Mass Point analysis) and 0.071%/ day (Total Time analysis) satisfy the acceptance criterion. The acceptance criterion is Lam < 0.75 La = 0.150%/ day, at Pa = 50 psig (-0 psi, +2.0 psi).

I O

O SU-084 8

G TABLE 1 b

DRYBULB AND DEWPOINT TEMPERATURE SENSOR LOCATIONS Volume Volume TE Elevation Azimuths Distance Fractions Fractions Reference No.

Tag No.

(ft)

(degrees) From Center Original Reassigned Drawing 1 0-TE -5500 175 0

0

.081

.081 E-292 2 0-TE-5501 160 180 33

.081

.081 E-292 3 0-TE-5502 145 0

33

.081

.081 E-292 4 0-TE-5503 130 90 48

.073

.073 E-292 5 0-TE-5508 115 0

0

.073

.073 E-292 6 0-TE-5511 50 230 50

.021

.043 E-290 7 0-TE-5513 104 180 32

.073

.073 E-275-2 8 0-TE-5504 104 0

30

.073

.073 E-292 9 0-TE-5505 75 20 48

.058

.058 E-292 10 0-TE-5506 65 0

0

.042

.042 E-292 11 0-TE-5517 16 180 45

.044

.044 E-298 12 0-TE-5507 50 140 44

.044

.088 E-295-1

  • 13 0-TE-5509 50 85 40

.022

.000 E-295-1

  • 14 0-TE-5510 50 320 50

.044

.000 E-295-2 15 0-TE-5512 75 220 44 058 058 E-295-2

~ ' ' ~ " ' '

'~

CJ 17 0-TE-5515 16 0

48

.044

.044 E-289 18 0-TE-5516 16 270 25

.044

.044 E-289 DEWCELLS Volume Volume AE Elevation Azimuths Distance Fractions Fractions Reference No.

Tag No.

(ft)

(degrees) From Center Original Reassigned Drawing 1 0-AE-5518 154 0

33

.231

.231 E-292 2 0-AE-5519 119 180 33

.231

.231 E-292 3 0-AE-5520 75 350 48

.231

.231 E-292 4 0-AE-5521 50 320 40

.131

.131 E-292-2 5 0-AE-5522 16 0

30

.088

.088 E-289 6 0-AE-5523 16 180 45

.088

.088 E-289

  • Malfunctioning sensors - not used for leakage rate calculations.

O SU-084 9

l V.

REFERENCES l

1.

Calvert Cliffs, Unit 1, Plant Technical Specifications.

2.

Calvert Cliffs Procedure STP M-662-1, Integrated Leakage Rate Test, Unit 1 Containment.

3.

10CFR50, Appendix J, " Reactor Containment Leakage Testing for Water Cooled Power Reactors."

4 ANSI N45.4-1972, " Leakage Rate Testing of Containment Structures for Nuclear Reactors."

5.

ANSI /ANS 56.8-1981, " Containment System Leakage Testing Requirements."

6.

Bechtel Topical Report BN-TOP-1, " Testing Criteria for Integrated Leakage Rate Testing of Primary Containment Structures for Nuclear Power Plants." Rev.1, February 1972.

!O

.V SU-084 10 a

.. _.. _. ~

O APPENDIX A i

DESCRIPTION OF BECHTEL ILRT COMPUTER PROGRAM l

O O

APPENDIX A DESCRIPTION OF BECHTEL ILRT COMPUTER PROGRAM A.

Program and Report Description 1.

The Bechtel ILRT computer program is used to determine the inte-grated leakage rate of a nuclear primary containment structure.

The program is used to compute leakage rate based on input values of time, free air volume, containment atmosphere total pressure, drybulb temperature, and dewpoint temperature (water vapor pressure).

Leakage rate is computed using the Absolute Method as defined in ANSI /ANS 56.8-1981, " Containment System Leakage Testing Requirements" and BN-TOP-1, Rev 1, " Testing Criteria for Integrated Leakage Rate Testing of Primary Containment Structures for Nuclear Power Plants".

The program is designed to allow the user to evaluate containment leakage rate test results at the jobsite during containment leakage testing. Current leakage rate values may be obtained at any time during the testing period using one of two computational methods, yielding three different report printouts.

2.

In the first printout, the Total Time Report, leakage rate is com-puted from initial values of free air volume, containment atmosphere

('

~

drybulb te'mperature and partial pressure of dry air, the latest

(

values of the same parameters, and elapsed time. These individually computed leakage rates are statistically averaged using linear re-gression by the method of least squares. The Total Time Method is the computational technique upon which the short duration test criteria of BN-TOP-1, Rev 1, " Testing Criteria for Integrated Leakage Rate Testing of Primary Containment Structures for Nuclear Power Plant," are based.

3.

The second printout is the Mass Point Report and is based on the Mass Point Analysis Technique described in ANSI /ANS 56.8-1981,

" Containment System Leakage Testing Requirements." The mass of dry air in the containment is computed at each data point (time) using the Equation of State, from current values of containment atmos phe re drybulb temperature and partial pressure of dry air.

Contained mass is " plotted" versus time and a regression line is fit to the data using the method of least squares. Leakage rate is determined from the statistically derived slope and intercept of the regression line.

4.

The third printout, the Trend Report, is a summary of leakage rate values based on Total time and Mass Point computations presented as a function of number of data points and elapsed time (test dura-t io n ). The Trend Report provides all leakage rate values required for comparision to the acceptance criteria of BN-TOP-1 for conduct of a short duration test.

()

5.

The program is written in a high level language and is designed for use on a micro-computer with direct data input from the data acquisition system.

Brief descriptions of program use, formulae A-1

O) used for leakage rate computations, and program logic are provided

(,

in the following paragraphs.

B.

Explanation of Program The Bechtel ILRT computer program is written, for use by experi-1.

enced ILRT personnel, to determine containment integrated leakage rates based on the Absolute Method described in ANSI /ANS 56.8-I 1981 and BN-TOP-1.

2.

Information loaded into the program prior to or at the start of the test:

a.

Number of containment atmosphere drybulb temperature sensors, dewpoint temperature (water vapor pressure) sensors and pressure gages to be used in leakage rate computations for the specific test b.

Volume f ractions assigned to each of the above sensors c.

Calibration data for above sensors d.

Test title e.

Test pressure c.

g.

Maximum allowable leakage rate at test pressure and 3.

Data received f rom the data acquistion system during the test, used to compute leakage rates:

a.

Time and date b.

Cont ainment atmosphere drybulb temperatures c.

Containment atmosphere pressure (s) d.

Cont ainment atmosphere dewpoint temperatures Containment free air volume.

e.

4.

After all data at a given time are received, a Summary of Measured Data report (refer to " Program Logic," Paragraph D, " Data" option command) is printed.

5.

If drybulb and dewpoint temperature sensors should fail during the the data from the sensor (s) are not used. The volume frac-

test, tions for the remaining sensors are recomputed and reloaded into the program for use in ensuing leakage rate computations.

Ois-/

b A-2

i C.

Leakage Rate Formulae 1.

Computation using the Total Time Method:

a.

Measured leakage rate, from data:

(1) l pvt i = W RTt 1

b (2)

PVi i = W RTi i

2400 (W1-W) i (3)

L

=

1 ati 1 W

and substituting equations (1) and Solving for Wi and Wi (2) into (3) yields:

TPV1ii) 2400 [1 -

i (4)

L

=

i TPVi1ij ati

(

where, W1, Wi = Weight of contained mass of dry air at times ti and ti respectively, Ibm.

T,Ti = Containment atmosphere drybulb temperature at times 1

et and ti respectively, "R.

P,Pi= Partial pressure of the dry air component of the con-1 tainment atmosphere at times ti and ti respectively, psia.

V,Vi = Containment free air volume at times ti and ti res ec-t tively, (constant or variable during the test), ft ch ti, ti = Time at ist and i data points respectively, hours.

Ati = Elapsed time from ti to ti, hours.

R = Specific gas constant for air = 53.35 f t.lbf/lbm.*R.

= Measured leakage rate computed during time interval Li ti to ti, wt.%/ day.

In order to reduce truncation error, the computer program uses the following equivalent formulation:

-2400 aW1 W1 6ti A-3

where, c

Wi-Wi AWi

=

W1 W1 APaVi ATi AVi api i

+

+

0 PV1i T1 P1 V1

=

o 1+

Ti apt =Pi-P1 AVi=Vi-V1 ATi=Ti-T1 b.

Calculated leakage rate from regression analysis, (5)

L = a + baty where:

L = Calculated leakage rate, wt.%/ day, as determined from the regression line.

(6) a = (ELt - brat )/N i

N(EL a ti) - (EL )(Zati) i i

(7) b=

N(Ea t ') - (Ia ti)2 i

N = Number of data points N

E=E i=1 c.

Calculated leakage rate at the 95% confidence level.

(8)

L95 = a + b atg + S_

L where:

L95 - Calculated leakage rate at the 95% confidence level, wt.%/ day, at elapsed timeatN-O A-4

j For StN < 24 g)/(N-2)]1/2 x [1 + 1 + (a t -a t ) /

(9a) 2 - AIL - BEL at 0 025;N-2 [(IL1 g

i S_

=t N

(ra t 2 - (ra tt)2f3)jl/2 1

1 where, to.025;N-2 = 1.95996 + 2.37226 + 2.82250 ;

N-2 (N-2)4 For atN 1 24 2 - aEL1 - BEL a ti)/(N-2)]l/2 x [1,(3 g _ g)2/

(9b)

S_ = t0 025;N-2 [(ELt i

L N

(Ea t 2 _ (g ti)273)j W g

l.6449(N-2)2 + 3.5283(N-2) + 0.85602 where, t0 025;N-2 =

(N-2)2 + 1.2209(N-2) - 1.5162 Ea ti N

2.

Computation using the Mass Point Method a.

Contained mass of dry air from data:

Wi = 144 P,V 4 (10)

RTi where:

4 All symbols as previously defined.

b.

Calculated leakage rate from regression analysis, W = a + b a t b

(11)

_L = -2400 -

a where:

L

= Calculated leakage rate, wt.%/ day, as determined from the regression line.

O A-5

(12)

= (EW -bEati)/N a

i N(EW a t ) - ( EW )( ES ti) i i i

N(Eati ) - (ESti)2 2

th i = Total elapsed time at time of i data point, hours at N = Number of data points th i

data point, Ibm, as computed from g = Contained mass of dry air at W

equation (10).

N I=E i=1 Inorder to reduce truncation error, the computer program uses the following equivalent formulation:

4 If AWi b

I a=

W 1 + (I

-_ E a t ) / N 1

i W1 W1 g

v AWi AWi N (I ati) - E I at t W

W 1

1 b=

W N(Eitg ) _ (gge )2 2

i f

AWi

where, is as previously defined.

i W1 i

Calculated leakage rate at the 95% confidence level.

c.

-2400 (10)

II95 =

(b - S )

b a

where:

the 95% confidence level, wt.%/ day.

595 = calculated leakage rate at O

A-6

~, - - _ _..-

i i

i O e/<2 b " *0 025;N-2 [NIa t 2 _ (g gi) @

W s

g i

0 025;N-2, 1.6449(N-2)2 + 3.5283 (N-2)2 + 0.85602 where, t 4

(N-2)2 + 1.2209 (N-2) - 1.5162 2 1/2 3

(t

- (a + b a ti)l s -) [W 1

i N-2 J(1 E(AW /W )2 _ [g(gg fg ))2/N -

'~

=W i 1 i l 1

N-2 i - E6 W /W )(Zatt)/N]2 1/2 II(aW /W ) at i t i t i

r(a ci ) - (I a c )2/N

,j Z

1 l

4 i O

~

1 h

4 i

O l

l s

A-7 l

4

(

O V

D.

Program Logic 1.

The Bechtel ILRT computer program logic flow is controlled by a set of user options. The user options and a brief description of their associated function are presented below.

OPTION COMMAND FUNCTION Af ter starting the program execution, the user either enters the name of the file containing previously entered data or initializes a new data file.

DATA Enables user to enter raw data. When the system requests values of time, volume, temperature, pressure and vapor pressure, the user enters the appropriate data. After completing the data entry, a summary is printed out.

The user then verifies that the data were entered correctly.

If errors are detected, the user will then be given the opportunity to correct the errors. After the user verifies that the data were entered correctly, a Corrected Data Summary Report of time, data, average temperature, partial pressure of dry air, and water vapor pressure is printed.

TREND A Trend Report is printed.

()

TOTAL A Total Time Report is printed.

MASS A Mass Point Report is printed.

TERM Enables user to sign-off temporarily or permanently.

All data is saved on a file for restarting.

CORR Enables user to correct previously entered data.

A LIST A Summary Data Report is printed.

READ Enable the computer to receive the next set of data from the data acquisition system directly.

PLOT Enables user to plot summary data, individual sensor data or air mass versus time.

DELETE Enables user to delete a data point.

INSERT Enables user to reinstate a previously deleted data point.

VOLFRA Enable user to change volume fractions.

O-A-8

.,m

k

"3 OPTION Q-COMMAND FUNCTION TIME Enable the user to specify the time interval for a report or plot.

VERF Enable the user to input imposed leakage rate and calcaluted ILRT leakage rates at start of verification test.

E.

COMPUTER REPORT AND DATA PRINTOUT MASS POINT REPORT The Mass Point Report presents leakage rate data (wt%/ day) as deter-mined by the Mass Point Method.

The " Calculated Leakage Rate" is the valce determined from the regression analysis. The " Containment Air Mass" values are the masses of dry air in the containment (Ibm).

These air masses, determined from the Equation of State, are used in the regression analysis.

TOIAL TIME REPORT The Total Time Report presents data leakage rate (we%/ day) as deter-

[

mined by the Total Time Method. The " Calculated Leakage Race" is the value determined from the regression analysis. The " Measured Leakage N~s Rates" are the leakage rate values determined using Total Time calcu-These values of leakage rate are used in the regression lat io ns.

analysis.

TREND REPORT The Trend Report presents leakage rates as determined by the Mass Point and Total Time methods in percent of the initial contained mass of dry air per day (wt%/ day), versus elapsed time (hours) and number l

of data points.

SUMMARY

DATA REPORT P

presents the actual data used to calculate The Summary Data report leakage rates by the various methods described in the " Computer Program" The six column headings are TIME, DATE, TEMP, section of this report.

PRESSURE, VPRS, and VOLUME and contain data defined as follows:

Time in 24-hour notations (hours and minutes).

1.

TIME:

Calendar date (month and day).

2.

DATE:

Containment weighted-average drybulb temperature in

(

3.

TEMP:

absolute units, degrees Rankine (*R).

A-9

I 4

PRESSURE:

Partial pressure of the dry air component of the con-t\\ '#

tainment atmosphere in absolute units (psla).

5.

VPRS:

Partial pressure of water vapor of the containment atmosphere in absolute units (psia).

6.

VOLUME:

Containment free air volume (cu. ft.).

F.

SUMMARY

OF MEASURED DATA AND

SUMMARY

OF CORRECTED DATA The Summary of Measured Data presents the individual containment atmosphere drybulb temperatures, dewpoint temperatures, absolute total pressure and f ree air volume measured at the time and date.

1.

TEMP 1 through TEMP N are the drybulb temperatures, where N = No. o f RTD' s. The values in the right-hand column are temperatures (*F), multiplied by 100, as read from the data acquisition system (DAS). The values in the left-hand column are the corrected temperatures expressed in absolute units

(*R).

PRES 1 through PRES N are the total pressures, absolute, were N = No.

2.

of pressure sensors. The right-hand value, in parentheses, is a number in counts as read from the DAS. This count value is converted to a value in psia by the computer via the instrument's calibration

/'N

(,g) table, counts versus psia. The left-hand column is the absolute total pressure, psia.

3.

VPRS 1 through VPRS N are the dewpoint temperatures (water vapor pressures), where N = No. of dewpoint sensors.

The values in the right-hand column are temperatures (*F), multi-plied by 100 as read from the DAS. The values in the left-hand column are the water vapor pressures (psia) from the steam tables for saturated steam corresponding to the dewpoint (saturation) temperatures in the center colu=n.

The Summary of Corrected Data presents corrected temperature and pressure values and calculated air mass determined as follows:

1.

TEMPERATURE (*R) is the volume weighted average containment atmosphere drybulb temperature derived from TEMP 1 through TEMP N.

2.

CORRECTED PRESSURE f psia) is the partial pressure of the dry air component of the containment atmosphere, absolute.

The solume weighted average containment atmosphere water vcpor pressure is subtracted from the volume weighted average total pressure, yielding the partial pressure of the dry air.

3.

VAPOR PRESSURE (psia) is the volume weighted average contain-atmosphere vater vapor pressure, absolute derived from fN()

ment VPRS 1 through VPRS N.

A-10

4.

VOLUME (cu. ft.) is the containment free air volume.

5.

CONTAINMENT AIR MASS (lba) is the calculated mass of dry air in the containment. The mass of dry air is calculated using the containment free air volume and the above TEMPERATURE and l

CORRRECTED PRESSURE of the dry air.

i O

k O

1 A-ll

__a m.m._

-.--._w._

aa.m.-wem mAa._

ma im.--

ar-.ua 4.___

u.

AhhM24--_A.

_u-a-_--e-3 42 i

I@

i i

APPENDIX B j

I PRESSURIZATION AND STABILIZATION

SUMMARY

DATA i

4 4

t E

1 4

1 L

J t

1 l

ll I

i L

i r

l e--,em----,.---

_.., -,wac,

_,n-,

mr e

v--

.mte-=

PRESSURIZATION CALVERT CLIFF 5 - UMIT 1 ILRT

SUMMARY

DATA 2000000.

=

.200 VOLUME

=

ALMAX

.000 VRATET

.000 VRATEM TIME DATE TEMP PRESSURE VPRS VOLUME 1300 518 533.975 14.1159

.2823.

2000000.

1315 518 536.428 15.0083

.2863 2000000.

1330 518 537.315 15.7861

.2866 2000000.

1345 518 538.152 16.8280

.2874 2000000.

1400 518 538.642 17.9541

.2889 2000000.

1415 518 538.776 19.0683

.2885 2000000.

1430 518 539.014 20.2592

.2875 2000000.

1445 518 539.026 21.4598

.2871 2000000.

1500 518 539.000 22.6594

.2854 2000000.

1515 518 538.953 23.8577

.2859 2000000.

1530 518 538.489 24.8620

.2856 2000000.

1545 518 536.103 24.7467

.2835 2000000.

1600 518 535.353 24.6993

.2868 2000000.

1615 518 534.915 24.6719

.2893 2000000.

1630 518 534.541 24.6528

.2916 2000000.

1645 518 534.320 24.6403

.2928 2000000.

1700 518 534.116 24.6325

.2932 2000000.

1715 518 533.918 24.6250

.2943 2000000.

1730 518 534.576 24.9483

.2972 2000000.

1745 518 536.017 25.9970

.2981 2000000.

1800 518 536.232 26.8289

.2992 2000000.

1815 518 536.317 27.5040

.2996 2000000.

I 1830 518 536.980 28.5827 3004 2000000.

1845 518 537.378 29.7501

.3014 2000000.

1900 518 537.542 30.9243

.3021 2000000.

1915 518 537.607 32.0990

.3014 2000000.

1930 518 537.648 33.2755

.3022 2000000.

1945 518 537.575 34.4033

.3031 2000000.

.I 2000 518 537.507 35.5741

.3041 2000000.

I 2015 518 537.348 36.7148

.3041 2000000.

2030 518 537.174 37.8148

.3045 2000000.

2045 518 537.243 39.0155

.3056 2000000.

2100 518 537.273 40.1853

.3059 2000000.

2115 518 537.555 41.3867

.3074 2000000.

2130 518 537.586 42.5785

.3076 2000000.

2145 518 537.323 43.6967

.3085 2000000.

2200 518 537.063 44.7936

.3098 2000000.

2215 518 536.956 45.9585

.3102 2000000.

y 2230 518 536.860 47.1453

.3104 2000000.

2245 518 536.790 48.2920

.3117 2000000.

Y_

2300 518 536.698 49.3890

.3146 2000000.

2315 518 536.645 50.4994

.3146 2000000.

2330 518 536.515 51.6043

.3149 2000000.

2345 518 536.479 52.7082

.3166 2000000.

O 519 536.421 53.8200

.3164 2000000.

15 519 536.354 54.9303

.3173 2000000.

30 519 536.261 56.0341

.3171 2000000.

45 519 536.212 57.1350

.3178 2000000.

100 519 536.125 58.2352

.3196 2000000.

115 519 536.047 59.3282

.3213 2000000.

130 519 535.938 60.4231

.3221 2000000.

145 519 535.839 61.5146

.3234 2000000.

200 519 535.743 62.6034

.3239 2000000.

215 519 535.610 59.8726

.3255 2000000.

230 519 535.347 64.6239

.3250 2000000.

B-1

i STABILIZATION CALVERT CLIFFS - UNIT 1 ILRT

SUMMARY

DATA

.200 VOLUME =

2000000.

ALMAX

=

.205 VRATET =

.198 VRATEM

=

TIME DATE TEMP PRESSURE VPRS VOLUME 245 519 534.619 64.7862

.3243 2000000.

300 519 533.894 64.6880

.3245 2000000.

315 519 535.073 64.8181

.3269 2000000.

330 519 533.953 64.6446

.3295 2000000.

345 519 533.341 64.5506

.3333 2000000.

400 519 532.998 64.4927

.3350 2000000.

415 519 532.471 64.4533

.3344 2000000.

430 519 532.805 64.4839

.3330 2000000.

445 519 532.885 64.4957

.3335 2000000.

500 519 532.936 64.5014

.3327 2000000.

515 519 532.960 64.5044

.3321 2000000.

530 519 533.511 64.5678

.3328 2000000.

545 519 533.752 64.5933

.3329 2000000.

600 519 533.827 64.6087

.3329 2000000.

615 519 533.924 64.6157

.3323 2000000.

630 519 533.954 64.6186

.3318 2000000.

700 519 535.029 64.7479

.3331 2000000.

715 519 535.460 64.7963

.3344 2000000.

O 730 519 535.768 64.8316

.3356 2000000.

745 519 536.020 64.8601

.3366 2000000.

800 519 536.248 64.8848

.3376 2000000.

815 519 536.438 64.9049

.3386 2000000.

830 519 536.621 64.9232

.3400 2000000.

845 519 536.760 64.9401

.3408 2000000.

900 519 536.885 64.9554

.3417 2000000.

915 519 537.004 64.9689

.3425 2000000.

930 519 537.089 64.9822

.3435 2000000.

945 519 537.179 64.9937

.3443 2000000.

1000 519 537.273 65.0040

.3459 2000000.

1015 519 537.353 65.0133

.3464 2000000.

1030 519 537.449 65.0249

.3467 2000000.

1045 519 537.531 65.0347

.3472 2000000.

1100 519 537.589 65.0446

.3472 2000000.

u 1115 519 537.674 65.0534

.3477 2000000.

1130 519 537.732 65.0623

.3476 2000000.

1145 519 537.807 65.0701

.3477 2000000.

1200 519 537.853 65.0777

.3479 2000000.

1215 519 537.915 65.0848

.3482 2000000.

1230 519 537.964 65.0916

.3484 2000000.

1245 519 538.013 65.0975

.3483 2000000.

1300 519 538.057 65.1044

.3489 2000000.

1315 519 538.126 65.1091

.3491 2000000.

1330 519 538.167 65.1157

.3494 2000000.

B-2

..~

STABILIZATION l

CALVERT CLIFFS - UNIT 1 ILRT O

TEMPERATURE STABILIZATION FROM A STARTING TIME AND DATE OF:

930 519 1985 TIME TEMP ANSI BN-TOP-1 (HOURS)

(OR)

AVE AT AVE AT DIFF AVE AT (4 HRS)

(1HR)

(2 HRS)

.00 537.09

.25 537.18

.50 537.27

.75 537.35 1.00 537.45 1.25 537.53 1.50 537.59 1.75 537.67

.322=

l 2.00 537.73 2.25 537.81

.314*

2.50 537.85

.290*

2.75 537.91

.281=

3.00 537.96

.258*

3.25 538.01

.241=

3.50 538.06

.234*

3.75 538.13

.226*

4.00 538.17

.269

.203

.07*

.109=

O

  • INDICATES TEMPERATURE STABILIZATION HAS BEEN SATISFIED 1

4 O

B-3

a

,t.-A-m.w.-

_a

-ma.~a+a n-A ALwa. nan.

-L-R, m-.J

.a-4

.A_---aa a-

-,m.

4-m-pa- - - - -. -

-+

-s d

i J

i n

9 i

5 APPENDIX C t

1 ILRT TREND REPORT I

.f i

i i

]

l i

i il

.J I

i l

i l

t i

1 l@

I l

[

-. ~, - - -

ILRT CALVERT CLIFFS - UNIT 1 ILRT TREND REPORT TIME AND DATE AT START OF TEST: 1330 519 1985 NO.

END TOTAL TIME ANALYSIS MASS POINT ANALYSIS PTS TIME MEAS. CALCULATED UCL CALCULATED UCL 4

1415

.046

.062

.435

.055

.175 5

1430

.096

.076

.264

.080

.144 6

1445

.004

.028

.174

.023

.102 7

1500

.055

.031

.156

.034

.088 8

1515

.043

.027

.134

.033

.072 9

1530

.035

.023

.116

.029

.059 10 1545

.035

.020

.105

.027

.051 11 1600

.018

.012

.089

.019

.040 12 1615

.029

.011

.084

.019

.036 13 1630

.017

.007

.075

.014

.029 14 1645

.036

.009

.077

.018

.032 15 1700

.028

.008

.074

.019

.030 l

16 1715

.028

.008

.073

.019

.029 17 1730

.034

.010

.074

.022

.031 l

18 1745

.044

.014

.078

.026

.036 19 1800

.036

.015

.078

.028

.037 l

20 1815

.045

.018

.081

.032

.040 21 1830

.036

.019

.080

.032

.040 l

22 1845

.049

.022

.083

.036

.044 l

23 1900

.034

.022

.082

.035

.042 24 1915

.041

.023

.082

.036

.043 25 1930

.031

.023

.080

.035

.041 l

l 26 1945

.037

.023

.080

.035

.041 27 2000

.041

.025

.080

.036

.042 l

28 2015

.038

.025

.080

.037

.042 l

29 2030

.033

.025

.078

.036

.041 30 2045

.028

.024

.076

.034

.039 31 2100

.028

.024

.075

.033

.038 32 2115

.036

.024

.074

.033

.038 33 2130

.033

.024

.073

.033

.037 34 2145

.030

.024

.072

.032

.036 35 2200

.043

.025

.07?

.034

.038 36 2215

.030

.025

. O '2

.033

.037 37 2230

.040

.025

. C',t

.034

.038 38 2245

.032

. 0 2',

.r L

.033

.037 39 2300

.028

.02S

. vN

.033

.036 40 2315

.032

.025

.069

.032

.036 41 2330

.032

.025

.069

.032

.035 O

C-1

O APPENDIX D ILRT

SUMMARY

DATA, MASS POINT, AND TOTAL TIME I

O O

l 4

ILRT C:)

l CALVERT CLIFFS - UNIT 1 ILRT

SUMMARY

DATA h

.200 VOLUME =

2000000.

ALMAX

=

VRATET =

.198 VRATEM =.205 TIME DATE TEMP PRESSURE VPRS VOLUME 1330 519 538.167 65.1157

.3494 2000000.

1345 519 538.220 65.1214

.3491 2000000.

i l

1400 519 538.270 65.1265

.3494 2000000.

1415 519 538.310 65.1321

.3498 2000000.

1430 519 538.363 65.1369

.3499 2000000.

1445 519 538.386 65.1421

.3501 2000000.

1500 519 538.440 G5.1465

.3501 2000000.

I 1515 519 538.477 65.1512

.3504 2000000.

1530 519 538.514 65.1558

.3507 2000000.

l 1545 519 538.550 65.1600

.3509 2000000.

1600 519 538.580 65.1644

.3509 2000000.

1615 519 538.619 65.1682

.3510 2000000.

i 1630 519 538.640 65.1715

.3512 2000000.

1645 519 538.685 65.1753

.3514 2000000.

1700 519 538.710 65.1788

.3513 2000000.

1715 519 538.734 65.1815

.3516 2000000.

1730 519 538.771 65.1850

.3515 2000000.

O

~

1745 519 538.796 65.1868

.3522 2000000.

1800 519 538.813 65.1895

.3524 2000000.

I 1815 519 538.855 65.1931

.3523 2000000.

l 1830 519 538.864 65.1952

.3526 2000000.

]

1845 519 538.902 65.1976

.3531 2000000.

1900 519 538.915 65.2012

.3526 2000000.

1915 519 538.943 65.2032

.3530 2000000.

1930 519 538.960 65.2066

.3536 2000000.

i l

1945 519 538.990 65.2090

.3531 2000000.

I 2000 519 539.016 65.2112

.3529 2000000.

2015 519 539.038 65.2141

.3535 2000000.

2030 519 539.049 65.2162

.3532 2000000.

2045 519 539.068 65.2193

.3532 2000000.

j 2100 519 539.087 65.2213

.3536 2000000.

2115 519 539.117 65.2230

.3539 2000000.

2130 519 539.135 65.2257

.3541 2000000.

2145 519 539.152 65.2282

.3541 2000000.

2200 519 539.194 65.2299

.3543 2000000.

2215 519 539.190 65.2323

.3544 2000000.

l 2230 519 539.229 65.2344

.3547 2000000.

2245 519 539.238 65.2373

.3549 2000000.

l 2300 519 539.254 65.2400

.3546 2000000.

2315 519 539.279 65.2418

.3548 2000000.

2330 519 539.298 65.2439

.3551 2000000.

D-1

,_,,...___,.,.,_.--,,_,,.m_-_._,._,_,-,

ILP!I CALVERT CLIFFS - UNIT 1 ILRT LEAKAGE RATE (WEIGHT PERCENT / DAY)

MASS POINT ANALYSIS TIME AND DATE AT START OF TEST: 1330 519 1985 TEST DURATION: 10.00 HOURS TIME TEMP PRESSURE CTMT. AIR MASS LOSS AVERAGE MASS (R)

(PSIA)

MASS (LBM)

(LBM)

LOSS (LBM/HR) 1330 538.167 65.1157 653172.

1345 538.220 65.1214 653164.

7.5 29.9 1400 538.270 65.1265 653155.

9.6 34.1 1415 538.310 65.1321 653162.

-7.6 12.5 1430 538.363 65.1369 653145.

16.7 26.1 1445 538.386 65.1421 653170.

-24.9 1.0 1500 538.440 65.1465 653149.

21.3 15.1 1515 538.477 65.1512 653151.

-2.2 11.6 1530 538.514 65.1558 653153.

-1.3 9.5 1545 538.550 65.1600 653150.

2.2 9.4 1600 538.580 65.1644 653159.

-8.8 5.0 1615 538.619 65.1682 653150.

8.9 7.8 1630 538.640 65.1715 653158.

-7.7 4.6 1645 538.685 65.1753 653140.

17.7 9.7 1700 538.710 65.1788 653145.

-5.2 7.5 1715 538.734 65.1815 653143.

2.0 7.5 1730 538.771 65.1850 653134.

9.1 9.3 1745 538.796 65.1868 653121.

13.3 11.9 1800 538.813 65.1895 653127.

-6.3 9.9 1815 538.855 65.1931 653113.

14.1 12.3 O-1830 538.864 65.1952 653123.

-9.9 9.7 1845 538.902 65.1976 653102.

21.2 13.3 1900 538.915 65.2012 653121.

-19.6 9.1 1915 538.943 65.2032 653107.

14.2 11.2 1930 538.960 65.2066 653121.

-13.8 8.4 1945 538.990 65.2090 653108.

12.8 10.1 2000 539.016 65.2112 653099.

9.6 11.2 2015 539.038 65.2141 653101.

-2.5 10.4 2030 539.049 65.2162 653110.

-8.4 8.9 2045 539.068 65.2193 653117.

-7.5 7.5 2100 539.087 65.2213 653114.

2.8 7.7 2115 539.117 65.2230 653095.

19.2 9.9 2130 539.135 65.2257 653100.

-5.2 8.9 2145 539.152 65.2282 653105.

-4.9 8.1 2200 539.194 65.2299 653071.

34.0 11.8 2215 539.190 65.2323 653099.

-28.1 8.3 2230 539.229 65.2344 653074.

24.7 10.8 2245 539.238 65.2373 653092.

-17.0 8.7 2300 539.254 65.2400 653099.

-7.6 7.6 2315 539.279 65.2418 653087.

11.8 8.6 2330 539.298 65.2439 653085.

2.3 8.7 FREE AIR VOLUME USED (CU. FT.)

=2000000.

REGRESSION LINE

= 653168.

INTERCEPT (LBM)

O,

-8.7

=

SLOPE (LBM/HR)

.200

=

MAXIMUM ALLOWABLE LEAKAGE RATE

.150 754 OF MAXIMUM ALLOWABLE LEAKAGE RATE

=

.035

=

THE UPPER 952 CONFIDENCE LIMIT

.032

=

THE CALCULATED LEAKAGE RATE D-2

.. =

ILRT CALVERT CLIFFS - UNIT 1 ILRT

. O LEAKAGE RATE (WEIGHT PERCENT / DAY)

TOTAL TIME ANALYSIS TIME AND DATE AT START OF TEST: 1330 519 1985 TEST DURATION: 10.00 HOURS TIME TEMP PRESSURE MEASURED (R)

(PSIA)

LEAKAGE RATE 1330 538.167 65.1157 1

1345 538.220 65.1214

.110 1400 538.270 65.1265

.225 l

1415 538.310 65.1321

.046 1430 538.363 65.1369

.096 l-1445 538.386 65.1421

.004 1500 538.440 65.1465

.055 1515 538.477 65.1512

.043 1530 538.514 65.1558

.035 1545 538.550 65.1600

.035 1600 538.580 65.1644

.018 1615 538.619 65.1682

.029 1630 538.640 65.1715

.017 1645 538.685 65.1753

.036 1700 538.710 65.1788

.028 1715 538.734 65.1815

.028 1730 538.771 65.1850

.034 O

1745 538.796 65.1868

.044 1800 538.813 65.1895

.036 1815 538.855 65.1931

.045 1830 538.864 65.1952

.036 1845 538.902 65.1976

.049 1900 538.915 65.2012

.034 1915 538.943 65.2032

.041 1930 538.960 65.2066

.031 1945 538.990 65.2090

.037 2000 539.016 65.2112

.041 2015 539.038 65.2141

.038 2030 539.049 65.2162

.033 2045 539.068 65.2193

.028

)

2100 539.087 65.2213

.028 2115 539.117 65.2230

.036 2130 539.135 65.2257

.033 i

2145 539.152 65.2282

.030 2200 539.194 65.2299

.043 2215 539.190 65.2323

.030 2230 539.229 65.2344

.040 t

2245 539.238 65.2373

.032 2300 539.254 65.2400

.028 2315 539.279 65.2418

.032 2330 539.298 65.2439

.032

.040 MEAN OF THE MEASURED LEAKAGE RATES

=

.200

=

MAXIMUM ALLOWABLE LEAKAGE RATE

.150 l

OF MAXIMUM ALLOWABLE LEAKAGE RATE

=

754

.069

=

THE UPPER 952 CONFIDENCE LIMIT

.025

=

THE CALCULATED LEAKAGE RATE D-3

O APPENDIX E PLOTS; AIRMASS, TEMPERATURE, PRESSURE, i

VAPOR PRESSURE, AND LEAKAGE RATE 1

i l

O i

lO

STABILIZATION, ILRT AND VERIFICATION CALUERT CLIFFS UNIT 1

ILRT AIRMASS LBM X 1999 O

654.29 653.89 STABILIZATION ILRT JERIFICATION 653.40 653.99 652.69 652.20 245 519 630 520 Q

START TIME DATE -

HOURS END TIME DATE TEMPERATURE DEGREES F 81.900 FAN COOLERS ON 79.999 I

77.999

~

75.999 4

FAN COOLERS OFF 73.999 O

FAN C00ltRS a v 71.999 i

245 519 630 520 START TIME DATE END TIME DATE I

E-1

STABILIZATION, ILRT AND VERIFICATION CALUERT CLIFFS - UNIT 1 ILRT PRESSURE PSIA (DRY AIR) 65.400

~~~

65.200 65.000

/

/

64.800 l i

64.600 64.400s 245 519 TIME HOURS 630 520 START TIME DATE END TIME DATE O

UAPOR PRESSURE PSIA

.370

.360

, v~ _.__.

-r '.

M_ s,,, w

.350

.340

'p.m./

.330 ',I

/

O

.32a 245 519 TIME HOURS 630 520 START TIME DATE END TIME DATE

.-2 E

ILRT AfR LBM 100 AND RE ESSION LINE 653.20

^

m,___

W y ^

_ _. c.

653.10 s.'s W= h N,

653.00 0.75 La

~

652.90

\\s 652.80

~

hYM!DATE ENDhk$!DATE AIRMASS LBM X 1000 UERIFICATION TEST 653.06 sg'~_s~ LOWER LIMIT 652.98

~

' ~,._,_~

652.91

~

_,,\\-

\\-

652.83 s

UPPER LIMIT

652.76

's.

s' O

652.68 130 520 TIME HOURS 630 520 START TIME DATE END TIME DATE E-3

ILRT i

l CALUERT CLIFFS UNIT 1

ILRT MASS POINT LEAMAGE RATE AND UCL X/ DAY lO

.299

.169 0.5 u l

.120 1

.989

/,

~

I i,

-==

.949 l,

.999 1339 519 2339 519 START TIME DATE -

HOURS END TIME DATE 1

TOTAL TIME LEAEAGE RATE AND UCL X/ DAY

.299 0.5 u

.160

.129

.989

,,1

' i, t

I i

.949 l

i,_..._,

~ _

Q.

.999 1339 519 2330 519 4

START TIME DATE - HOURS END TIME DATE i

E-4

4.

  • s--

--M

--s VERIFICATION CALUERT CLIFFS - UNIT 1 ILRT O

MASS POINT LEAMAGE RATE - X/ DAY UERIFICATION TEST

.500

.400

~

.300 N

UPPER LIMIT x

.200 RATE LOWER LIMIT

.100

.000 130 520 TIME HOURS 630 520

. O STant TIME naTE END TIME DATE TOTAL TIME LEAMAGE RATE - X/ DAY UERIFICATION TEST

.500

.400

.300 UPPER LIMIT u_\\

RATE

.200 A

LONER LIMIT

.100 O

.000 130 520 TIME HOURS 630 520 START TIME DATE END TIME DATE r.- s

~

d.A-4 me--2 L... - -

..e-

_.a.

.a_.

+-

ie 4

-a t

u*

t t

I APPENDIX F VERIFICATION FLOW

SUMMARY

AND DATA I

i l

i 1

i l

l l

J l

t i

i E

1 1

i 1

VERIFICATION CALVERT CLIFFS - UNIT 1 ILRT O

SUMMARY

DATA

.200 VOLUME =

2000000.

ALMAX

=

VRATET =

.198 VRATEM =.205 TIME DATE TEMP PRESSURE VPRS VOLUME 2345 519 539.304 65.2458

.3557 2000000.

O 520 539.320 65.2495

.3554 2000000.

15 520 539.353 65.2519

.3550 2000000.

30 520 539.373 65.2535

.3558 2000000.

45 520 539.387 65.2548

.3556 2000000.

100 520 539.401 65.2558

.3556 2000000.

115 520 539.438 65.2558

.3560 2000000.

130 520 539.435 65.2578

.3555 2000000.

145 520 539.477 65.2582

.3561 2000000.

200 520 539.480 65.2585

.3568 2000000.

215 520 539.502 65.2592

.3565 2000000.

230 520 539.535 65.2609

.3563 2000000.

245 520 539.543 65.2610

.3567 2000000.

300 520 539.570 65.2621

.3566 2000000.

315 520 539.574 65.2627

.3565 2000000.

330 520 539.595 65.2639

.3568 2000000.

345 520 539.616 65.2643

.3569 2000000.

400 520 539.637 65.2653

.3568 2000000.

415 520 539.657 65.2662

.3570 2000000.

430 520 539.677 65.2670

.3572 2000000.

n/

445 520 539.686 65.2666

.3576 2000000.

I 500 520 539.701 65.2669

.3577 2000000.

s-515 520 539.712 65.2684

.3573 2000000.

530 520 539.739 65.2692

.3579 2000000.

545 520 539.750 65.2701

.3579 2000000.

600 520 539.765 65.2707

.3579 2000000.

615 520 539.775 65.2714

.3577 2000000.

630 520 539.782 65.2716

.3579 2000000.

i F-1 t

k VERIFICATION CALVERT CLIFFS - UNIT 1 ILRT O

LEAKAGE RATE (WEIGHT PERCENT / DAY)

MASS POINT ANALYSIS 1

TIME AND DATE AT START OF TEST:

130 520 1985 TEST DURATION:

5.00 HOURS TIME TEMP PRESSURE CTNT. AIR MASS LOSS AVERAGE MASS (R)

(PSIA)

NASS (LBM)

(LBM)

LOSS (LBM/HR)


.435 65.2578 653059.

130 539 145 539.477 65.2582 653012.

46.7 186.8 200 539.480 65.2585 653010.

1.6 96.7 215 539.502 65.2592 652991.

18.9 89.6 230 539.535 65.2609 652969.

22.5 89.7 245 539.543 65.2610 652960.

8.9 78.9 300 539.570 65.2621 652938.

21.9 80.3 315 539.574 65.2627 652939.

.9 68.4 330 539.595 65.2639 652926.

13.1 66.3 345 539.616 65.2643 652904.

21.7 68.6 400 539.637 65.2653 652889.

15.1 67.8 415 539.657 65.2662 652874.

15.4 67.2 430 539.677 65.2670 652858.

15.9 66.9 445 539.686 65.2666 652843.

15.2 66.5 a

500 539.701 65.2669 652828.

14.8 65.9 q

515 539.712 65.2684 652828.

.5 61.4 530 539.739 65.2692 652805.

23.6 63.5 i

545 539.750 65.2701 652801.

4.0 60.7 l

600 539.765 65.2707 652788.

12.7 60.1 l

615 539.775 65.2714 652783.

5.2 58.0 i

630 539.782 65.2716 652776.

6.8 56.5 FREE AIR VOLUME USED (CU. FT.)

=2000000.

REGRESSION LINE

= 653031.

INTERCEPT (LBM)

-S4.8

=

SLOPE (LBM/HR)

I VERIFICATION TEST LEAMAGE RATE UPPER LIMIT =

.255 VERIFICATION TEST LEAKAGE RATE LOWER LIMIT =

.155 r

.201

=

l THE CALCULATED LEAXAGE RATE 4

i 1

1 ilO F-2 i

VERIFICATION CALVERT CLIFFS - UNIT 1 ILRT O

LEAKAGE RATE (WEIGHT PERCENT / DAY)

TOTAL TIME ANALYSIS TIME AND DATE AT START OF TEST:

130 520 1985 TEST DURATION:

5.00 HOURS TIME TEMP PRESSURE MEASURED (R)

(PSIA)

LEAKAGE RATE 130 539.435 65.2578 145 539.477 65.2582

.687 200 539.480 65.2585

.355 215 539.502 65.2592

.329 i

230 539.535 65.2609

.330 245 539.543 65.2610

.290 300 539.570 65.2621

.295 315 539.574 65.2627

.251 330 539.595 65.2639

.244 345 539.616 65.2643

.252 400 539.637 65.2653

.249 415 539.657 65.2662

.247 430 539.677 65.2670

.246 445 539.686 65.2666

.244 500 539.701 65.2669

.242 O

515 539.712 65.2684

.226 530 539.739 65.2692

.233 545 539.750 65.2701

.223 600 539.765 65.2707

.221 615 539.775 65.2714

.213 630 539.782 65.2716

.208

.279 MEAN OF THE MEASURED LEAKAGE RATES

=

VERIFICATION TEST LEAKAGE RATE UPPER LIMIT =

.248 VERIFICATION TEST LEAKAGE RATE LOWER LIMIT =

.148

.166 THE CALCULATED LEAKAGE RATE

=

i f

i F-3

,am._.

4

_4 c_

aJ-.

_a a

4_a

%A

--AA..u_4

&._m.

a a..AeAa--.am.-.-a--

  • .-.+

J f

I 4

APPENDIX G j

ISG CALCULATIONS 4

i 4

l c

l I

i @

1 I

i l,

t l

l i

1 i

a i

f 4

I(e.

i i

i I

i i

ISG CALCULATION

( ANSI /ANS 56.8 - 1981 )

........=S====================

....-====================================

CALIBRATION DATA

  1. OF SENSORS SENSITIVITY (E)

REPEATABILITY (r)

TEMPERATURE (T) 16 0.0100 deg. F O.0100 deg. F PRESSURE (P) 2 0.0010 pais 0.0010 paia VAPOR PRESS (Pv) 6 0.1000 deg. F O.1000 dag. F i

Length of Test (t) 10.0 hrs Test Pressure (P) 50.8 psig

==>

65.5 psia Fros Steas Table 0.0120 pai/deg. F (at 69 deg. F)

La O.2000 wt*/ day INSTRUMENT MEASUREMENT ERRORS

\\

2 2

1/2 1/2 e7 = ((ET)

+ (rT) 3

/t# of sensors]

e7 =

0.0035 deg. F 2

2 1/2 1/2 eP = [(EP)

+ (rP) 3

/t# of sensors 3 eP =

0.0010 pais 2

2 1/2 1/2 ePv = ((EPv)

+ (rPv) 3

/t# of sensors) ePv 5 0.0007 paia I

INSTRUMENT SELECTION GUIDE 2

2 2

1/2

+ 2(eT/T) 3 ISG = 2400/tt 2(eP/P)

+ 2(ePv/P)

ISG =

0.0067 wtx/ day

(

254 of La 0.0500 wtM/ day s

35 5553=3553 5=33333M555335553353.s=S555 WWWESSSSSSSSESSSSSSESWSSSSSSSSSW G-1 l

i l

4 l

O i

l

  • f t

i APPENDIX H i

I LOCAL LEAKAGE RATE TEST EVALUATION i

\\

1 i

l i

I t

i I

4 i

a l

1 I

3 1

l l

I f

4

)

i j

I i

l I

I 9

i i

i n ew e.

e m - m m,m,

G APPENDIX H LOCAL LEAKAGE RATE TESTING EVALUATION During refueling outages, local leakage rate testing (LLRT) is commenced at the beginning of the outage and completed in approximately six to eight weeks. The ILRT, if scheduled for that outage, is conducted af ter the completion of the LLRT.

During the LLRT, repairs and adjustments are made to some systems which may change that penetration's leak rate. The term "As Found" indicates the leak rate before repairs and adjustments and the term "As Lef t" is the leak rate after repairs and adjustments. An evaluation of the difference between "As Found" and "As Lef t" can give only some indication of what the ILRT results would be if conducted prior to repairs and adjustments.

Table 1 is a comparison of the "As Found" and "As Lef t" data for those penetrations which had repairs and adjustments performed during the LLRT.

Units of measured leak rate are standard cubic centimeters per minute (secm).

O i

O SU-084 H-1

APPENDIX H LOCAL LEAKAGE RATE TEST RESULTS REPAIRS AND ADJUSTMENTS PENETRATION "AS FOUND" "AS LEFT" 1A 65 48.5 1B 903 199 1D 6.0 24.6 2A 2510 1950 2B 3912.2 106.10 7A 25.2 20.4 7B 670 494 8

86.3 510 13 486.15 486.16 14 416.77 2500.6 19A 1292 206 20A 3270 1711 20B 390 365 23 826 807 24 15.6 7.9 42 2420 36.5 47A 97.1 182.3 47B 13.5 19.2 47C 224 18.8 47D 44.1 6.0 49A 48.1 31.1 49B 19.2 16.7 49C 21.1 15.6 50 40.2 362 53 ZEB1 192 2.0 ZEB2 43.5 9.9 54 ZWB1 107.4 6.0 62 1810 22.4 64 4900 125.9 67 73.6 18.2 68 3698.94 7397.87 69 7397.9 925.7 O

36024.86 18632.43 t

TOTAL SYSTEM "AS FOUND".......... 45,105.26 "AS LEFT"........... 28,354.03 SU-084 11 - 2

4 l

4

O i

e I

i t

4' APPENDIX I I

3 MALFUNCTIONING SENSOR PLOTS i

I i

I i

,i O

!e i

1 l

1 i

i j

i i

4 i

I i

I I

t i

1 l

I 4

1 e

i l

?

i

'I t

l!@

1 i

i t

t

MALFUNCTIONING SENSORS CALUERT CLIFFS UNIT 1

ILRT 1

TEMPERATURE SENSOR 13 DEGREES F O

77.999

/,,J '

-s.,,

75.000 i, >

w i

s

,i,/.

' ^ sw-

'\\

I

73. BOO i

i, fd 71.999

~

~\\ "

69.000

\\-

67.990............................ '

245 519 639 529 O

START TIME DATE -

HOURS END TIME DATE i

TEMPERATURE SENSOR 14 DEGREES F

75.999 l

1 i

73.999 4

71.999

/f

~

i'/

I 69.900

/

J J, -

0 67.000 'll\\)/

I 65.999 1

245 519 639 529 START TIME DATE - HOURS END TIME DATE l

1-1

BALTIMORE GAS AND ELECTRIC CHARLES CENTER. P. O. BOX 1476. BALTIMORE, MARYLAND 21203 AnTHun E. LUNOVALL. JR-vice Passiocar

sum, August 5,1985 i

U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Washington, D.C. 20555 ATTENTION:

Mr. Edward J. Butcher, Jr., Acting Chief Operating Reactors Branch #3

SUBJECT:

Calvert Cliffs Nuclear Power Plant Unit Nos.1; Docket No. 50-317 Reactor Containment Building InteRrated LeakaRe Rate Test Report

REFERENCE:

(1) 10 CFR 50, Appendix 3 Gentlemen

]

A successful periodic Reactor Containment Building Integrated Leak Rate Test, in accordance with Reference (1), was performed on May 20,1985,on Unit No.1. Twelve copies of this test report are herewith forwarded for your review, as required by Section V of Reference (1).

,Very truly yoursi

(

f'.

',..._., /. a e<

\\

AEl./OPB/ bat Enclosures (12) cc:

D.A. Brune, Esquire G.F. Trowbridge, Esquire T.

Foley, NRC D.H. Jaf fe, NRC

.