Proposed Tech Specs Implementing Reactor Operating Limits for Reload I1 Fuel
ML20134E311
Person / Time
Site: Big Rock Point File:Consumers Energy icon.png
Issue date: 08/16/1985
From:
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
Shared Package
ML20134E286 List:
References
NUDOCS 8508200148
Download: ML20134E311 (3)


Text

-.

o i

ATTACliMENT Consumers Power Company Big Rock Point Plant Docket 50-155 l

PROPOSED TECilNICAL SPECIFICATION PAGE CHANGES August 16, 1985 2 Pages 8500200148 050016 DR ADOCK 05000155 p

PDR Ic0885-0258-NLO4

I..

43 l

TABLE 1 l

R31ccd G Reload l

Reloads Including Reload G3/G4/H1/

Reload F & Modified F G13/G14 G1U H2/H3/H4 II l

Minimum Critical Power l

Ratio at Normal Operation 1.59 1.59 1.59 1.59 1.59

)

Conditions

  • l Mi:imus Bundle Dryout Time ** Figure 1 l

MaximusHeatFluxag Ov:rpower, Btu /h-Ft 500,000 395,000 407,000 392,900 392,900 l

Maximus SteadygState Heat Flux, Btu /h-ft 410,000 324,000 333,600 322,100 322.100 l

Maximus Average Planar Linear He:t Generation Rate, Steady State, kW/Ft***

Table 2 Table 2 Table 2 Table 2 Table 2 l

Maximus Bundle Power, MW Fig. 2 x 0.95 Fig. 2 Fig. 2 Fig. 2 Fig. 2 t

l l

St:bility Criterion: Max.

j Me::ured Zero-to-Peak Flux Amplitude, Percent cf Average Operating Flux 20 20 20 20 20 Maximum Steady-State Power Level, MW, 240 240 240 240 240 Maximum Value of Average Coro Power Density 46 46 46 46 46 8 240 W, kW/L g

Nominal Reactor Pressure l

During Steady-State Power 1,335 1.335 1,335 1,335 1,335

)

Oper tion, Pais l

l Minimum Recirculation 6

6 6

6 6

l Flow Rate Lb/h 6 x 10 6 x 10 6 x 10 6 x 10 6 x 10 l

l Rato of Change of Reactor Power During Power Operation C:: tral rod withdrawal during power operation shall be such that the average rate of l

chang 3 of reactor power is less than 50 MW, per minute when power is less than 120 MW '

j 1000 than 20 MW e

mir:towhenpowIrisbetween200MW,and240MW.per minute when power is Betwee per g

t g

  • Th3 bundle Minimus Critical Power Ratio (MCPR), based on the Exxon Nuclear C:rporation XN-2 Critical Power Correlation, must be above this value.

CiThe actual dry out time for GE 9x9 fuel (based on the General Electric Dryout C:rrelation for Nonjet Pump Boiling Water Reactors, NEDE-20566) should be above th3 dryout time shown in Figure 1.

CC0F r operation with only one recirculation loop in service these limits shall be r:duced by 5 percent for Reload F and Modified F and reduced by 20 percent for cther fuel types.

Proposed TSB0885-0258-NLO4 l

L

43a TABLE 2 MAPLHGR (KW/FT) LIMITS Planar Average Reload Reload Recon-Exposure Modi-Reload Reload Reload G3/G4/ Reload Reload stituted Reload (MWD /STM) fied F F

G G1U Hi H2 H3/H4 G13/G14 II O

7.21 7.0 6.77 6.92 200 9.5 9.4 7.28 360 7.62 1,000 7.95 7.8 7.56 7.65 1,630 7.56 7.81 3,810 7.57 3,900 7.65 7.95 5,000 9.9 9.7 6,440 7.28 6,620 7.50 7.48 7.48 7.48 7.89 10,000 9.9 9.7 12,880 7.17 13,520 7.49 8.00 13,610 7.56 15,000 9.8 9.6 19,050 7.11 7.89 20,000 8.7 8.6 l

20,320 7.56 7.56 7.56 20,870 7.78 7.76 l

24,580 6.84 25,000 8.4 8.3 26,400 7.32 7.32 7.32 7.19 26,760 7.64 28,210 6.08 30,000 7.4 7.3 6.0 6.97 31,210 6.73 6.73 6.73 32,000 7.0 6.9 6.0 33,020 7.12 6.81 33,380 6.69 6.69 6.69 l

34,000 6.5 6.5 6.0 34,470 5.73 6.73 36,000 6.2 6.1 6.0 36,290 5.73 38,000 6.0 40,000 6.0 41,400 6.0 J

Proposed TSB0885-0258A-NLO4

- ' ' - ~ '

~

~