ML20133G925

From kanterella
Jump to navigation Jump to search
Rev 1 to Monthly Operating Rept for Apr 1985
ML20133G925
Person / Time
Site: Oyster Creek
Issue date: 04/30/1985
From: Molnar J
GENERAL PUBLIC UTILITIES CORP.
To:
Shared Package
ML20133G887 List:
References
NUDOCS 8508090124
Download: ML20133G925 (1)


Text

,_

OPERATING DATA REPORT OPERATING STATUS 1.

DOCKET:

50-219 2.

REPORTING PERIOD:

April 1985, Revision 1 3.

UTILITY CONTACT:

JOSEPH R. MOLNAR 609-971-4699 4.

LICENSED THERMAL POWER (MWt):

1930 5.

NAMEPLATE RATING (GROSS MWe):

687.5 X 0.8 = 550 6.

DESIGN ELECTRICAL RATING (NET MWe):

650 7.

MAXIMUM DEPENDABLE CAPACITY (GROSS MWe):

650 I

8.

MAXIMUM DEPENDABLE CAPACITY (NET MWe):

620 9.

IF CHANGES OCCUR ABOVE SINCE LAST REPORT, GIVE REASONS:

NONE 10.

POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWe): N/A 11.

REASON FOR RESTRICTION, IF ANY:

NONE MONTH YEAR CUMULATIVE 12.

REPORT PERIOD HRS 720.0 2880.0 134593.0 13.

HOURS RX CRITICAL 720.0 2221.0 87848.9 14.

RX RESERVE SHTDWN HRS 0.0 0.0 469.7 15.

HRS GENERATOR ON-LINE 700.4 2078.7 85615.4 16.

UT RESERVE SHTDWN HRS 19.6 19.6 22.3 17.

GROSS THERM ENER (MWH) 1144000 3524940 149187269 18.

GROSS ELEC ENER (MWH) 386820 1213960 47596955 19.

NET ELEC ENER (MWH) 371550 1163595 45726160 20.

UT SERVICE FACTOR 97.3 72.2 63.6 21.

UT AVAIL FACTOR 100.0 72.9 63.6 22.

UT CAP FACTOR (MDC NET) 83.2 65.2 54.8 23.

UT CAP FACTOR (DER NET) 79.4 62.2 52.3 24.

UT FORCED OUTAGE RATE 0.0 27.3 10.2 25.

FORCED OUTAGE HRS 0.0 781.7 9732.8 26.

SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, DURATION): N/A 27.

IF CURRENTLY SHUTDOWN ESTIMATED STARTUP TIME:

N/A B508090124 850611 PDR ADOCK 05000219 PDR R