Docket No. 50-336 Attachment Millstone Nuclear Power Station, Unit No. 2 Proposed Revision to Technical Specification 3/4.7.10 Penetration Fire Barriers.

I.

October 1985 E '88&M 88&884u P

PM

b

?,.

PLANT SYSTEMS 3/4.7.10 PENETR ATION FIRE BARRIERS LIMITING CONDITION FOR OPER ATION 3.7.10 All fire rated assemblies (walls, ficor/ ceilings, cable tray enclosures, and other fire barriers) separating safety-related fire areas or separating portions of redundant systems important to safe shutdown within a fire area and all sealing devices in fire rated assembly penetrations (fire doors, fire windows, fire dampers, cable, piping, and ventilation duct penetration seals shall be OPERABLE.

APPLICABILITY: At all times unless otherwise determined that the separation of saf ety-related fire areas or separating portions of redundant systems important to safe shutdown within a fire area is not required based on the MODE of operation.

ACTION:

a.

With one or more of the above required fire rated assemblies and/or penetration sealing devices inoperable, within 1 hour:

1.

determine that the fire areas / zones on both sides of the affected fire rated assembly and/or penetration sealing device are monitored by either an OPERABLE fire detection or automatic suppression system and establish a fire watch patrol that inspects both areas at least once per hour, g 2.

establish a continuous fire watch on at least one side of the affected fire rated assembly and/or penetration seal, E 3.

temporarily repair the inoperable fire rated asseinbly and/or sealing device and classify h as temporary.

All temporary or inoperable fire rated assemblies and/or sealing devices sha!! be permanently repaired within thirty (30) days, or implement action 1 or 2 above, b.

The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

l MILLSTONE - UNIT 2 3/4 7-42 l

w

f.',

SURVEILL ANCE REQUIREMENTS 4.7.10 The above required fire ratco assemblies and penetration sealing devices shall be verified to be OPER ABLE by a visual inspection:

a.

At least once per IS months for fire doors and fire dampers.

l b.

At leas.t once per IS months for fire barrier penetration seals, on at least 10% of the total number of penetration seals. If any of the

.l penetration seals in the inspection sample are found to be inoperable, then an additional 10% sample of the total number of penetrations seats shall be visually inspected.

Sampling and inspection shall continue until all of the seals in a sample are found OPER ABLE or 100% of the seals are inspected, c.

Prior to returning a fire rated assembly and/or penetration sealing device to OPERABLE status following repairs or maintenance.

MILLSTONE - UNIT 2 3/4 7-43

-