PUBLIC SERVICE ELECTRIC AND GAS COMPANY PHILADELPHIA ELEGIRIC COMPANY DELMARVA POWER AND LIGHT COMPANY ATLANTIC CITY ELLCTRIC COMPANY DOCKET NO. 50-272 SALEM NUCLEAR GENERATING STATION, UNIT NO. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 66 License No. DPR-70 1.
The Nuclear Regulatory Comission (the Comission) has found that:
A.
The application for amendment by Public Service Electric and Gas Company, Philadelphia Electric Company, Delmarva Power and l
Light Company and Atlantic City Electric Company (the licensees)
]
dated December 7, 1984, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity witt. the application, the provisions of the Act, and the rules and regulations of the Comission; C.
There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.
The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. DPR-70 is hereby amended to read as follows:
h0070027G50916 p
ADOCK 05000272 PDR
-2 (2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through knendment No. 66, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
3.
This license amendment is effective as of the date of its issuance.
FOR THE NUCLEAp REGULATORY COMMISSION
}
OperatingReactRs(hif Var Branch #1
)
Division of Licen m g I
Attachment:
Changes to the Technical Specifications Date of Issuance: September 16, 1985 i
I l
1 f
s ATTACHMENT TO LICENSE AMEN 0 MENT NO. 66 i
i FACILITY OPERATING LICENSE NO. OPR-70 i
DOCKET NO. 50-272 i
~ Revise Appendix A as follows:
l Remove Page Insert Page 4
j 3/4 5-6a 3/4 5-6a I
i 1
l r
4 e
r e a==
2 3
1 r
r r
4 i.
l f
i EMERGENCY CORE COOLING SYSTEMS ECCS SUBSYSTEMS - Tavg < 350'F SURVEILLANCE RE0VIREMENTS 4.5.3.1 The ECCS subsystem shall be demonstrated OPERABLE per applicable Surveillance Requirements of 4.5.2.
4.5.3.2 All safety injection pumps, except the OPERABLE pump allowed above, shall be demonstrated inoperable at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> whenever the temperature of one or more of the.RCS cold. legs is less than or equal to 312*F by the following:
a.
By verifying that the notor circuit breakers have been removed from their electrical power supply circuits or.
'b.
For testing purposes, by verifying that the pump is in a recirculation flow path and that the penual discharge valve is.,
closed.
/
I l
SALEM - UNIT 1 3/4 5-6a Amendment No. 66
b UNITED STATES P
NUCLEAR REGULATORY COMMISSION g
.E WASHINGTON, D. C. 20555
\\...../
~
PUBLIC SERVICE ELECTRIC AND GAS COMPANY PhlLADELPHIA ELEGIRIC COMPANY DELMRVA POWER AND LIGHT COMPANY ATLANTIC CITY ELECTRIC COMPANY DOCKET N0. 50-311 SALEM NUCLEAR GENERATING STATION, UNIT NO. 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.41 License No. DPR-75 1.
The Nuclear Regulatory Comission (the Comission) has found that:
A.
The application for amendment by Public Service Electric and Gas Company, Philadelphia Electric Company, Delmarva Power and Light Company and Atlantic City Electric Company (the licensees)'
dated December 7, 1984, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.
The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. DPR-75 is hereby amended to read as follows:
(2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 41, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
3.
This license amendnent is effective as of the date of its issuance.
FOR THE NUCLEAR SEGULATORY COMMISSION 3
ven g
k Operating Reactors r nch #1 Division of Licensing
Attachment:
Changes to the Technical Specifications Date of Issuance: September 16, 1985 i
I I
l 1
I l
ATTACHMENT TO LICENSE AMENDMENT NO. 41 FACILITY OPERATING LICENSE NO. DPR-75 DOCKET NO. 50-311 Revise Appendix A as follows:
Remove Page Insert Page
^
3/4 5-8 3/4 5-8 I
4 6
em e
e l
e e
EMERGENCY CORE COOLING SYSTEMS ECCS SUBSYSTEMS - Tavg < 350*F
~
l SURVEILLANCE RE0UIREMENTS
~
4.5.3.1 The ECCS subsystem shall be demonstrated 0PERABLE per applicable Sur'veillance Requirenents of 4.5.2.
4.5.3.2 All safety injection purps, except the OPERABLE pump allowed above, shall be demonstrated inoperable at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> whenever the temperature of one or more of the RCS cold legs is less than or equal to 312*F by the following:
a.
By verifying that the motor circuit breakers have been removed from their electrical power supply circuits or, b.
For testing purposes, by verifying that the pump is in a recirculation flow path and that the penual discharge valve is closed.
s
/
SALEM - UNIT 2 3/45-8 Amendment No. 41 4