ML20129F622
| ML20129F622 | |
| Person / Time | |
|---|---|
| Site: | Perry |
| Issue date: | 07/05/1985 |
| From: | Youngblood B Office of Nuclear Reactor Regulation |
| To: | Edelman M CLEVELAND ELECTRIC ILLUMINATING CO. |
| References | |
| RTR-REGGD-01.118, RTR-REGGD-1.118 NUDOCS 8507170413 | |
| Download: ML20129F622 (4) | |
Text
. n' s g
g UNITED STATES g
p, NUCLEAR REGULATORY COMMISSION j
WASHINGTON, D. C. 20555 r
\\...../
JUL 0 51985 Docket Nos.: 50-440 and 50-441 Mr. Murray R. Edelman, Vice President Nuclear Operations Group The Cleveland Electric Illuminating Company P. O. Box 5000 Cleveland, Ohio 44101
Dear Mr. Edelman:
Subject:
Confirmatory Information Required for Performance of Surveillance Testing Pertaining to Regulatory Guide 1.118, Rev 2, " Periodic Testing of Electrical Power and Protection Systems" -- Perry Nuclear Power Plant (Units 1 and 2)
Your letter dated May 14, 1985 updated the Perry plant's conformance with various regulatory guides revising FSAR Tables 1.8-1 and 1.8-2.
In its review of these revised tables the staff noted that the degree of conform-ance with Regulatory Guide 1.118, Revision 2, " Periodic Testing of Electrical Power and Protection Systems", was found to be inconsistent with the degree of conformance previously documented in the FSAR and accepted by the staff.
The staff has detemined that the lifting of leads to perform surveillance testing is not in conformance with the recommendations of Regulatory Guide 1.118 and is, therefore, unacceptable without an ensuing analysis.
- Further, the staff finds that opening of a fuse and/or breaker to perform a surveil-lance test would be acceptable only if it satisfies the positions of Regulatory Guide 1.22.
As a confimatory item, the staff requires that CEI submit a detailed discus-sion regarding the Perry I&C designs' degree of compliance with Regulatory Guide 1.118.
If you plan to utilize the jumpering of wires, the removal of fuses or the opening of breakers, then their use should be correlated with the various positions (6a and 6b) set forth in the aforementioned regulatory guide.
The opening of circuit breakers to perform surveillance testing should also be discussed within the context of Regulatory Guide 1.22.
For the cases that fall outside the purview of these regulatory guides, your staff should modify the design accceding to these regulatory guides or provide acceptable justif-cation (s) for deviating from these guidelines.
8507170413 850705 PDR ADOCK 05000440 l
- =y o,, JUL 0 51985 In addition, your staff should confirm that response time testing as discussed in Regulatory Guide 1.118 is applicable to both the reactor protection system and the engineered safety feature systems, including the sensors where applicable.
Your imediate attention to this matter is urged in view of the on-going testing of, and projected fuel load date for Perry Unit 1.
Sincerely.
DElIGINAL 81c igd BYl B. J. Youngblood, Chief Licensing Branch No. 1 Division of Licensing cc: See next page DIS M M*et-Ele-R Local PDR PRC System NSIC LB#1 R/F MRushbrook JStefano OELD ACRS(16)
JPartlow BGrimes EJordan RWHouston FRosa, ICSB/DSI JMauck, ICSB/DSI RKnop, Region III RLanksbury, Region III i
JGrobe, SRI / Perry 1
I)
J N
B 1/DL LBF /..'
tefano/mac BJYo blood 0 g/85 07/ /85
'(
- JUL 0 51985 In addition, your staff should confirm that response time testing ps discussed in Regulatory Guide 1.118 is applicable to both the reactor protection system and the engineered safety feature systems, including the sensors where applicable.
Your imediate attention to this matter is urged in view of the on-going testing of, and projected fuel load date for Perry Unit 1.
Sincerely,
{
00 B. J).
ungbl'ood, Chief Licdns ng Branch No. 1 Division of Licensing cc: See next page
-r.
-,--s,w,-,-,----..,-,.--,--,.,,,,-,-----n,
'a JUL 0 51985 Mr. Murray R. Edelman Perry Nuclear Power Plant The Cleveland Electric Units 1 and 2 Illuminating Company cc:
Jay Silberg, Esq.
Mr. Larry O. Beck Shaw, Pittman, & Trowbridge The Cleveland Electric 1800 M Street, N. W.
Illuminating Company Washington, D. C.
20006 P. O. Box 97 E-210 Perry, Ohio 44081 Donald H. Hauser, Esq.
The Cleveland Electric Illuminating Company P. O. Box 5000 Cleveland, Ohio 44101 Resident Inspector's Office U. S. Nuclear Regulatory Consnission Pamly at Center Road Perry, Ohio 44081 Regional Administrator, Region III U. S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137 Donald T. Ezzone, Esq.
Assistant Prosecuting Attorney 105 Main Street Lake County Administration Center Painesville, Ohio 44077 Ms. Sue Hiatt OCRE Interim Representative 8275 Munson Mentor, Ohio 44060 Terry J. Lodge, Esq.
618 N. Michigan Street Suite 105 Toledo, Ohio 43624 John G. Cardinal Esq.
Prosecuting Attorney Ashtabula County Courthouse Jefferson, Ohio 44047