,J

=

Cp&L Carolina Power & Light Company SERIAL: NLS-35-244 JUL 0 81985 Director of Nuclea'r Reactor Regulation Attention:

Mr. D. B. Vassallo, Chief Operating Reactors Branch No. 2

,c Division of Licensing United States Nuclear Regulatcry Commission Washington, DC 20555 F

BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS.1 AND 2 DOCKET NOS. 50-325 & 50-324/ LICENSE NOS. DPR-71 & DPR-62 CONTAINMENT SYSTEMS - PRIMAR.Y CONTAINMENT AIRLOCKS

Dear Mr. Vassallo:

On May 2,1985, your staff requested additional information concerning our license amendment application dated October 24,1984, as. supplemented February 27, 1985 regarding Technical Specification (TS) Section 3.6.l.3.

The staff determined that reference to an inoperable airlock door _ interlock in Action Statement A of TS 3.6.1.3 is inappropriate and requested the Company to provide the specific action to be taken in

/

the event of an inoperable airlock door interlock.

We have reviewed the request and revised Section 3.6.1.3. A new Action Statement B, dealing with an inoperable primary containment airlock door interlock, has been added.

In the event of an inoperable airlock door interlock, the inner airlock door will b6 maintained locked closed and verified to be locked at least once per 31 days until the interlock is restored to operable status.

Enclosed are revised TS pages for Section 3.6.1.3.

Please refer any further qu'estian,s regarding this matter to Mr. Sherwood R. Zimmerman at (919) 836-6242.

Your

,ery trul,

~'

j$

d

~

A. B. Cutter - Vice President Nuclear Engineering & Licensing

[

MAT /ccc (1684 MAT)

Enclosure cc:

Dr. J. Nelson Grace (NRC-RII)

Mr. M. Grotenhuis (NRC)

Mr. W. H. Ruland (NRC-BNP)

A. B. Cutter, having been first duly sworn, did depose and say that the information contained herein is true and correct to the best of his information, knowledge and belief; Carolina Power & Light Company.

(go(

and the sources of his information are officers, employees, contractors, and agents of AA L 2?f M%.U8'~ 4 f

Notery( wei) 4e,. -.. 3 My commission expires: ///A7//f_

g NOTARY \\ \\

i 0507160608 B50708 hg l

PDR ADOCK 05000 PUBLIC i.

......'*'.*c,,

PDR p

,.,ttevme sueet. e. o. sox 15s1. R81e'9h, N. C. 27602

+

.uM.)>jf

.1

..