ML20129A867

From kanterella
Jump to navigation Jump to search
Application for Amend to License DPR-45,revising Site Flooding Tech Specs to Require Plant to Be in Cold Shutdown Before Flooding Above Grade Floor of Plant Starts
ML20129A867
Person / Time
Site: La Crosse File:Dairyland Power Cooperative icon.png
Issue date: 06/25/1985
From: Linder F
DAIRYLAND POWER COOPERATIVE
To: Zwolinski J
Office of Nuclear Reactor Regulation
Shared Package
ML20129A871 List:
References
LAC-10969, NUDOCS 8507150402
Download: ML20129A867 (3)


Text

_ - _

.: p"

):

D DA/RYLAND h

COOPERAT/VE

  • P O. BOX 817 2615 EAST AV SOUTH
  • LA CROSSE WISCONSIN S4601 (608) 788-4000 June 25, 1985 In reply, please refer-to LAC-10969 DOCKET NO. 50-409 Director of Nuclear Reactor Regulation Attn:

Mr. John Zwolinski, Chief Operating Branch #5

~ Division of Licensing U. S. Nuclear Regulatory Commission Washington, DC 20555

SUBJECT:

DAIRYLAND POWER COOPERATIVE LA CROSSE BOILING WATER REACTOR (LACBWR)

PROVISIONAL OPERATING LICENSE NO. DPR-45 APPLICATION FOR AMENDMENT TO LICENSE

REFERENCES:

(1) DPC Letter, Linder to Crutchfield, LAC-9480 dated December 19, 1983.

(2) NUREG-0827, " Integrated Plant Safety Assessment Systematic Evaluation Program La Crosse' Boiling.

Water Reactor", dated June 1983.

(3) 10 CFR 50, Section 50.90.

Dear Mr. Zwolinski:

In Reference 1, DPC proposed Technical Specifications in response to Reference 2.

Included in Reference 1 were proposed specifications on site flooding.

l The NRC reviewed the submittal and requested revision of the DPC proposed requirement. During telecons in March-May 1985, DPC_and NRC representatives j

agreed on a modified, more restrictive version of~the proposed specification on site flooding. Therefore, in accordance with the provisions of Reference 3, an application to amend Provisional Operating License No. DPR-45 for the La Crosse Boiling Water Reactor is hereby filed with three (3) signed original applications, together with thirty-seven (37) copies. A copy of the revised page containing the site flooding Technical Specification is attached.

l-l The revised proposed specification is as follows:

If the plant is in CONDITION 1, 2, or 3 and the Mississippi River level adjacent to the plant reaches 639.2' and is predicted to exceed 640', conrnence reactor shutdown and be in CONDITION 4 prior l

to the river level exceeding 640'.

f The basis-of the above is that 640 feet is the floor elevation of the turbine building and cribhouse. The maximum rate at which the river level is 0

WPl.6.8 850715040285M5 0

PDR ADOCM 05000409 l \\. M i

P pg y

,.s Mr. Jchn Zwolinski, Chief Juns 25, 1985 Operating Branch #5 LAC-10969 predicted to increase is-1.6 feet per day, which is 0.8 feet per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

.If plant shutdown is started at 639.2 feet, the river will not exceed 640 feet 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> later. The plant can be placed in cold shutdown in a 12-hour period.

This specification, therefore, requires the plant to be in cold shutdown before flooding above the grade floor of the plant starts.

If, however, flooding above 640 feet is not predicted, the plant will not be required to shut down unnecessarily.

Finding of no significant hazards We have reviewed the hazards considerations reference in 10 CFR 50, Sections 91 and 92 and have determined that with these criteria no significant hazards result from these proposed amendments. 10 CFR 50.92 (c) (1-3) provide the questions for review of significant hazards considerations. They are repeated here for reference.

10 CFR 50.92 (c)

(1) Involve a significant increase in the probability or consequences of an accident previously evaluated; or (2) Create the possibility of a new or different kind of accident from any accident previously evaluated; or (3) Involve a significant reduction in a margin of safety.

The proposed change adds new requirements to LACBWR Technical Specifications.

No existing requirements are downgraded or modified in any way. Therefore, this license amendment results in "no" answers to the three questions in 10-CFR 50.91 and no significant hazards determination is justified on this licensee amendment in the opinion of the licensee.

As this license amendment application is a revision requested by the NRC to a previously submitted amendment request, it has been determined to be exempt from any fee.

If there are any questions, please contact us.

Sincerely, DAIRYLAND POWE 00 PERATIVE M

Frank Linder, General Manager FL:LSG SKS i

l Attachment i

WPl.6.8 f

Mr. John Zwolinski, Chief Juna 25, 1985 Operating Branch #5 LAC-10969 cc:

J.-G. Keppler, Regional Administrator i

U. S. Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137 Mr. Clarence Riederer, Chief Engineer Wisconsin Public Service Commission P. 0. Box 7854 Madison, WI 53707 i

NRC Resident Inspector R. Dudley, LACBWR Project Manager STATE OF WISCONSIN )

)

COUNTY OF LA CROSSE) 1 Personally came before me this 2 0 #3( day of Yf,mmx /

1985, I

the above named, Frank Linder, to me known to bgj 'he person who executed the t

foregoing instrument. and acknowledged the same.f/

Notary Publicg/La Crosse County Wisconsin My commission expires February 21, 1988 f

WPl.6.8 -

-