ML20128L912

From kanterella
Jump to navigation Jump to search
Supplemental NPDES Noncompliance Notification:On 850710, Review of June 1985 Discharge Monitoring Rept for Outfall 002 Revealed Excessive Total Suspended Solid Levels. Rainwater in Dike Will Be Retained for Longer Period
ML20128L912
Person / Time
Site: Surry  Dominion icon.png
Issue date: 07/12/1985
From: Taylor J
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: Jenkens R, Ronaldo Jenkins
VIRGINIA, COMMONWEALTH OF
References
NUDOCS 8507250146
Download: ML20128L912 (1)


Text

IM Offn eilas Jot >On ktdeuntd, Vargunus 21261 I

July 12, 1985 CERTIFIED MAIL RETURN RECEIPT REQUESTED Mr. Ray R. Jenkins, Jr.

State Water Control Board Piedmont Regional Office 2201 West Broad Street Richmond, Virginia 23230 Surry Power Station - NPDES Dermit Exception

Dear Mr. Jenkins:

This is to provide additional information concerning the NPDES permit exception at our Surry Power Station that was reported to you previously by phone on July 10 and in the Junit 1985 Discharge Monitoring Report for Outfall 002. ,

Analysis of samples from Outfall 002, the Gas Turbine Dike on June 13 and 17 revealed total suspended solid (TSS) levels of 53.4 and 16.2 mg/1, respectively. The average TSS value for this outfall was 34.8 mg/l for June, 1985. This exceeds our permit limitation of 30.0 mg/l for the TSS average.

As corrective action, rainwater trapped within this dike will be retained for a longer period, to allow settling of suspended solids before discharging.

If you have any questions regarding this exception, please do not hesitate to contact this department.

Very truly yours, Jo n A. Taylor, Ph.D.

Manager Water Quality cc: Dr. J. Nelson Grace, USNRC - Docket Nos. 50-280/50-281 /

Mr. Harold R. Denton, USNRC - Docket flos. 50-280/50-281 Mr. Donald J. Burke, USNRC - Docket Nos. 50-280/50-281 0507250g K6 g 70 00 f/g on A PDR