ML20128F287

From kanterella
Jump to navigation Jump to search
Summary of 921118 Meeting W/Numarc Re Fire Endurance Testing Acceptance Criteria.List of Attendees & Rept W/Proposed Criteria Also Encl
ML20128F287
Person / Time
Issue date: 11/20/1992
From: Mccracken C
Office of Nuclear Reactor Regulation
To: Thadani A
Office of Nuclear Reactor Regulation
References
NUDOCS 9212080298
Download: ML20128F287 (24)


Text

e q

v

^b O -;[#'

g 3_

L' 8-NUCLEAR REGULATORY COMMISSION-o.

j

WASHINGTON, D, c 20555

...../

November 20,11992-MEMORANDUM FOR: J Ashok Thadani, Director Division of Systems Safety and Analysis FROM:

Conrad McCracken, Chief-Plant Systems Branch Division of Systems Safety and Analysis

SUBJECT:

SUMMARY

OF NOVEMBER 18, 1992, MEETING BETWEEN NRC STAFF-AND NUMARC ON FIRE ENDURANCE TESTING /CCE HANCE CRITERIA NRC staff met with representatives of the Nuclear Utilities Management and

-Resources Council (NUMARC) on November 18, 1992, to discuss the NRC staff's proposed fire barri_er testing acceptance criteria that had'been presented in summary form to the Commission on November '13,1992, is a list of' the attendees.

NRC staff provided NUMARC with the proposed criteria (Enclosure 2).nd solicited technical and programmatic questions from the meeting attendees, The NRC staff also discussed the Thermo-Lag combustibility issues and-informed.

-/'

NUMARC of plans to issue an information notice on the results of combustibility tests.

The staff stated that the proposed criteria would be issued through the-normal' regulatory process, providing an opportunity for public comment. However, if-any attendees had significant initial comments, the staff requested that-they be submitted within about two weeks. NUMARC representatives stated that they plan to provide the NRC with comments on the staff proposed acceptance criteria within this time period,

( Q,

&c p{ t

'Conrad

. McCra en, Chief-Plant: Systems Brench Division of Systems Safety and Analysis 4

Enclosures:

As stated 1(

M '

REE'ID RGuiiDRY CBEE.1ES x c;hn4

"**m ss e m, p J

N NWA k

., m w **e.e-teer

~f j'f,'

  • v jj?4&Q-RCl
PDR,

.y y

.l cc w/ enclosures:

d Mr. Bill Rasin-Vice_ President & Director Technical Division fluclear Utilities Managemont and Resources Council 1776 Eye Street, N.W.

Suite 300 Washington, D.C.

20006-2496 i

QISTRIBUTION w/ enclosures:

[ Cent 8al@I Fi[leJjT$l36.6(I SF'LB IS

)

flRC PDR FMiraglia-12 G 18 WRussell 12 G 18 GHolahan CMcCracken RArchitzel PMadden MWidmann IMoghi t,si JFouchard sJPA) 2G5 GMulley (IG)

EW-542 EPawlik REG 111 SWest 9A2 AMasciantonio 13 0 18 SHom (OGC) 15 B 18 MCallahan (OCA) 17 A 3 LPlisco PGill 7E4 l

RJenkins 7E4 a

i s ',

a

[A -

i SPLB:DSSA SPLB:DSSA PLB:DSSA

-GHo ]han

-[

A IMoghiss M RArchitzel CMcCracken

'ATh i

l-11/x /92 11/y/92 11fgi/92

}{/-

92 I

.,2 i

[G:\\ THERM 0LA\\ll-18MTG. IBM]

l i

g' s

e*.

=g:

Meetina eftendeel Enclosure-I Hama

- Affiliation C. McCracken USNRC C. Berlinger

- USNRC R. Architzel USNRC

~

P. Gill USNRC I. Moghissi USNRC

'M Widmann USNRC.

.I. Moghissi USNRC A. Pal

- USNRC.

A. Masciantonio USNRC S. West USNRC A. Marion

- NUMARC B. Bradley NUMARC M.' Schreim NUMARC D. Alemayehu Pacific Nuclear R. Beller Pacific Nuclear d

P. Lersey?

Pacific Nuclear A.-Cohlmeyor Pacific Nuclear-M. Powell Arizonsi-Public Service R. Oehlberg EPRI.

F. Ozysz Penn Power & Light' D. Smith Florida Power & Light C.-Fisher

. Florida Power & Light

-R. Allen Union Electric P. Genter-NIRS J. MacGregor

_Winston & Strawn R. Huston Tennessee Valley Authority T. Meisenheimer Bechtel' C. Skinker

- Bechtel

'J. Raleigh STS J. Ste3 hens Miller _ & Chevalier R. Licit 3M T. Dinh' HNUS P.'Boulden Virgin:a Power 1

D. Notley_

SAIC_

D. Perramt sel f-employed V

i e

<y-a

-g

.~-.

,,y

.e-7.

% g.

.:r U.S. Nuclear. Regulatory Commission Meeting on Fire Endurance Test Acceptance Criteria With the Nuclear Management and Resources Council November 19,1992

+

1 o

FIRE BARRIER TESTING

~

~

mms-ACCEPTANCE CRITERIA

~

~

FIRE TEST HOSE

- BARRIER ASTM-E119 STREAM CONDITION !

> 325 F

< 325 F l

. HOSE BARRIER VISUAL INSP

. STREAM CONDITION CABLES i

NOT OK OK HOSE BARRIER STREAM CONDITION NOT OK NOT OK c

FIRE BARRIER DEVIATION CONDITION RATED FIRE q

il BARRIER 1

~

j.

ENGINEERING. EVALUATION q

DEMONSTRATE: FUNCTIONALITY NRC REVIEW a

i l

4

PROPOSED

SUMMARY

OF PROPOSED FIRE ENDVRANCE TESTING CRITERIA FOR FIRE BARRIER 5 SYSTEMS USED TO SEPARATE SAFE SHU100WN FUNCTIONS WITHIN THE SAME FIRE AREA PROPOSED CRITERIA PREVIOUS CRITERIA RATIONAL FOR CHANGE Temperature, as Temperature, as Temperature - Difficult measured on the measured on the to measure a uniform external surface of the unexposed side of the temperature on 'he fire Raceway, should not fira barrier material, barrier material exceed 325 F (Note 1),

should not exceed 325"F.

surface. Raceway temps provide good indication This temperature is of internal temp-rise determined by averaging and potential barrier temperature readings of failure locations similar series of during the test.

thermocouple (e.g.,

cable tray side rail).

(Note 2)

Barrier Condition -

Barrier Condition - The Barrier Condition -

d Raceway fire barrier barrier shall have Cotton waste has not shall remain intact. No withstood the fire and been used in raceway visible signs of hose stream test fire barrier testing as conductor or raceway without the p3sscge of an indicator of barrier after fire and hose flame or hot gasses hot failure.

Visual stream test.

enough to ignite cotton inspection process

waste, provider a better indication of barrier condition after the fire and hose stream test.

Hose Stream testing is Hose Stream testing is Hose Stream - To required. (solid strean, required. (solid stream reflect alternative test as required by test as required by methods found NFPA 251 on second test NFPA 251) acceptable (Note 3),

specimen after being The use of a fog nozzle subjected to a fire for the hose stream at exposure of 1/2 the end of a full duration (Note 4) or a duration of the fire fog stream after the test provides a good full fire exposure.)

method for testing erosion and cooling effects.

PROPOSED PROPOSED CRITERIA PREVIOUS CRITERIA RATIONAL FOR PHANGE Cable condition - If Cable condition - No Cable condition - The the above temperature consideration given to objective of these fire.

limit is exceeded, the determining the barriers is to assure cable condition must be material condition of that thermal damage to visually inspected.

the cable, protected safe shutdown Cables when inspected cables or components should show no signs of does not occur.

degraded conditions resulting from the thermal affects of the fire exposure, GUIDANCE - ENGINEERING EVALVA110NS JUSilYING DEVIAll0NS FROM THE FIRE BARRIER ACCEPTANCE CRITERIA Functionality is needed Functionality N-Functionality is to be demonstrated if guidance provideo p

considered to be a the preceding criteria to licensees to deviation from the are exceeded (Note 5),

demonstrate by acceptance criteria and engineering analysis, must be justified on a Recommended method Analysis kept on file case-by-case basis i,cludes:

for NRC review.

which includes an i

Engineering analysis assessment of cable

- Megger test generally based on jacket material.

- Hi-Pot test (60%)

internal temperature below the ignition Demonstration of temperature. No functionality should consideration given also cc-ider operating cable operating temperature of the temperatures within the cables inside the fire barrier at the onset of barrier at the onset of the fire exposu.e.

the fire exposure.

Combustibility of a fire barrier system should be demonstrated by testing to ASIM-E136.

Certain applications of fire barriers materials (e.g., radiant energy heat shield inside containment) are required by Appendix R to be non-combustible.

Note 1 - The 325 F temperature condition was established by allowing the internal temperature on the raceway surface to rise a maximum of 250 F above ambient laboratory air temperature, assumed to be 75 F, during the fire test, hate 2 - NFPA 251/ ASTM-E119 allows the temperature condition to be determined by averaging the thermocouple readings. The conditions of acceptance are also placed on the temperature conditions measured by a single thermocouple.

Under these conditions of acceptance, if any single thermocouple exceeds 30% above the maximum allowable temperature rise (i.e., max, allowable 250 F + 75'F =

325 F) the test is considered to have exceeded the criteria temperature limit.

PROPOSED

' ~

Note 3-l$RP9.5.1recognizestheuseofafogstreamasan-alternativehose stream testing method for qualifying fire barrier-penetration seals, Note 4 - The application of this' hose stream test method provides assurance

- that the fire barrier system has sufficient structural-integrityEto resist fire related barrier-breaches. caused by falling objects, Note 5 - A fire barrier system which does not meet the performance conditions of the fire endurance acceptance criteria is considered not to be a-rated fire barrier.

For those performance conditions (i.e., high raceway temperature, barrier openings, water projection, cable damage) which deviate from this acceptance criteria, an engineering analysis which clearly demonstrates the functionality of the protected component or cables can be submitted to the staff for review, These deviations will be evaluated by the staff on a case-by-case basis, E

f 9

a<

-.13.e s.i.

,,, - ~

e - :'----

-,so.-y7-.-,e.-

<-w,e-.+,.----w

~

PROPOSED POSITION - November 19. 1992 FIRE ENDURANCE TEST ACCEPTANCE CRITERIA FOR FIRE BARRIER SYSTEMS USED TO SEPARATE SAFE SHVTDOWN FUNCTIONS WITHIN THE SAME FIRE AREA 1.

BACKGROUND in 1975. Se Browns Ferry Nuclear power plant experienced a serious electrical cable '

  • e.

This fire had a significant impact on the operators response to the e from a safety perspective.

The= fire caused spurious-instrumentation indications and affected the control of sever,al safety systems.

As a result of this fire, the NRC issued the following fire protection guidelines and regulations concerning fire protection programs at nuclear power plants:

May 1. 1976 Branch ' Technical Position (APCSB) 9.5-1, " Fire Protection Program."

february 24, 1977 Appendix A to Branch Technical Position APCSB 9.5-1, " Guidelines for Fire Protection for Nuclear Power Plants Docketed Prior to July 1, 1976."

February 19, 1981 10 CFR 50.48, " Fire protection."

February 19, 1981 Appendix R to 10 CFR 50, " Fire Protection Program for Nuclear Power Facilities Operating Prior to January 1979 "

July 1981 NUREG-0800, Standard Review Plan (SRP), 9.5.1,

" Fire Protection for Nuclear Power Plants."

In addition to the above fire protection guidance and regulations the NRC, in an ef fort to clarify its fire protection requirements to the industry, issued Generic Letter (GL) 81-12 " Fire Protection Rule (45 FR 76602, November 19, 1980)," February 20,1981; GL 83-33, "NRC P'sition on Certain Requirements of Appendix R to 10 CFR 50," October 19,

and GL 86-10,

" Implementation of Fire Protection Requirements," Apr'.. 24, 1986.

GL 86-10, which took precedence over previous staff guidance, provided staff interpretations to Appendix R and answers to industry questions relatirg to the implementation of Appendix R.

The NRC, in an effort to give the licensees

.more flexibility to make changes to their plant specific fire protection program, issued GL 88-12, " Removal of Fire Protection Requirements From i

Technical Specifications." Through the implementation and the adoption of a l

standard license conditio-a licensee can make changes which do not adversely E

affect a plant ability tochieve and_ maintain post-fire safe shutdown to their fire protection program in accordance with 10 CFR-50.59.

The aforementioned NRC documents provided the industry with NRC staff guidance concerning fire barriers separating plant fire areas, including-the fire l

resistance (endurance) ratings for these barriers and the qualification ~

l

4 EMEND POSilLON - @.ynker 19. 1992 testing that establishes their fire resistance ratings, in addition, these documents provided guidance on combustibility of structural materials and the testing required to demonstrate low flame spread properties.

The following sections of this document provide the objective for providing safe shutdown related fire barriers in nuclear power plants, definition of fire protection terms related to fire barriers, and the NRC's fire endurance testing acceptance criteria for fire barriers used to separate safe shutdown functions within the same fire area.

11.

OBJECllVE Of flRE BARRIERS USED TO SEPARATE SAFE SHUTDOWil FUf4CT10f45 WITHlu 1HE SAME FIRE AREA fire rated barriers are used in nuclear power plants to provide fire area separation between redundant safety related components and safe shutdown functions. They provide fire resistan'ce protection, as required by Appendix R', to one safe shutdown train in those fire areas which contain both trains.

The objective of the safe shutdown related Appendix R fire barrier is to ensure that a safe shutdown train is conservatively protected from fire-related thermal damage.

The necessity for these fire barriers has been verified by n1ultiple PRAs.

These PRAs indicate, even with these fire barriers installed, fires provide a Yajor contribution to core melt probab il i t ie s.

It is the position of the Plant Systems Branch that fire endurance ratings of building construction and materials are demonstrated by testing fire barrier assemblies in accordance with the provisions of the aoplicable sections of NFPA 251, " Standard Methods of Fire Tests of Building Construction and Materials," and ASTM E-119, " Fire Test of Building Construction and Mat eri al s. " Assemblies which pass specified occaptance criteria (e.g.,

standard time-temperature fire endurance exposure, uraxposed sidc temperature rise, and huse stream impingement) are considered to have a specific fire resistance rating. to GL 86-10, Interpretations of Appendix R, provided additional guidance with respect to the term " free from fire damage."

interpretation 3,

" Fire Damage," states, "In promulgating Appendix R, the Commission has provided methods acceptable for assuring that necessary structures, systems, and components are free from fire damage (see Section Ill.G.2a, b, ar.d ci, that is, the structure, system or component under consideration is capable of performing its intended function during and af ter the postulated fire, as reeded."

for advanced reactor designs, redundant safe shutdown functions are required to be located in separate 3-hour fire areas... _ -

j PROPOSED POSITION - November 19. 1992 GL 86-10, Question 3.2.1, also stated that "The resulting 325 'F cold side temperature criterion is used for cable tray wraps because they perform a fire barrier function to preserve the cables free from fire aamage.

It is clear that cable that b1 gins to dearade at 450 'F is free from fire damage at 325

'F."

(Emphasis added.)

In addition, the staff's response stated that "for newly identified conduit and cable trays requiring such wrapping new materials which meet the 325 'F crit'e'rion should be used, or justification should be provided for the.use of material which does not meet-the 325 'F criterion.

This may be based on an analysis demonstrating that the maximum recorded temperature is sufficient 1v below the cable insulation ignition temperature." -(Emphasis added.-)

The basic premise of the NRC fire resistance criteria is that fire barriers which do not exceed 325 'F (163 *C) cold side temperature and pass the hose stream test provide adequate assurance that the shutdown capability is protected without further analyses.

If the temperatu' criteria is exceeded, sufficient additional information is needed to perfo s an engineering evaluation to demonstrate that the shutdown capability is protected.

^

111.

DEFINITIONS In order to support the understanding of the_ technical terms used throughout this document, the following definitions are provided.

(These terms and definitions are consistent with those used in NUREG 0800, SRP 9.5.1, " Fire Protection for Nuclear Power Plants.")

tmproved - tested md accepted for a specific purpose or application by a nationally recognized testing laboratory.

CombAstible Material - Material that does not meet the definition of non-combustible.

Fire Barrier - Those components of construction (walls, floors and their supports), including beams, joists, columns, penetration seals or closures, fire doors, and fire dampers that are rated by approving _ laboratories-in hours of resistance to fire and are used to prevent the spread of fire.

Raceway Fire Barrier - Non-bearing partition type envelope system installed around electrical components and cabling that are rated by approving laboratories in hours of resistance to ' ire and are used to maintain safe shutdown functions free from fire dame <

Fire Resistance Rating --Tht: time that,aterials of test assemblies have withstood a fire exposure as established in accordance with the test procedures of " Standard Methods of Fi.re Tests of Building Construction and Materials," (NFPA 251)...

+c

EROP0MDRillM - Nonmbstm_J192 thrgo-busLitdtMethl - (a) Material which in the form in which it is used and und<fr the conditions anticipated, will not ignite, burn, support a

astion, or release flammable vapors when subjected to fire or heat; (b)

M..erial having a structural base of noncombustible material, with a surf acing not over 1/8-inch thick that has a flame sp" cad rating of not higher than 50 when neasured using ASTM L-84 lest " Surface Burning Charbcteristics of Buildirg Materials."

(flote - There i.s an exception to itis definition as defined by BlP Appendix A, Position D. 1. d.

This position allows the use of coibustible interior finishes when listed by a nationally recognized testing laboratory, such as factory Mutual or Underwriters Laboratories, Inc. for a flane spread, smoke and fuel contribution of 25 or less in its use c on f 14u r a t i ofi. )

IV.

I1RL Ef4DURAfill iLSTitiG ACCLP1 MICE CR11[RIA FOR flRE BARRllR WALLS, il00R5, AfiD C[lllf4GS USED 10 S[PARAlf SAff SHU100Wri FUtiC110f45 W11Hlfl THi SAML F1Rl AR[A lo denonst ate the adequacy of fire barrier walls, floors, ceilings, and enclosures, barrier designs should be verified by fire endurance testing.

f4RC fire protection guidance refers to the guidance of lifPA 251 end ASTM E-119 as acceptable test methods for demonstrating fire endurance performance, lhe following are the fire endurance testing acceptance criteria for the subject fire barriers:

The fire barrier design hes withstood the fire endurance test without the passage of flame or the ignition of cotton waste on the unexposed side for a period of time equivalent to the fire resistance rating required of the barrier; The iemperature levels recorded on the unexf 'ed side of the fire barrier are analyzed and demonstrable that tne maximum temperature does not exceed 250 *I above ambient; snd The fire barrier remains int act and does not allow projection of water beyond the unexposed surface Ju' ring the hose stream test. (for acceptable hose stream test methods and time of appli'ation - See Section Vll.)

If the aeove criteria are met for five earr 9 r war s, floors, an<1 ceilings separating safe shutdown functions within the s ue fire area, the barrier is considered to be acceptable, f1RC fire protec-n guidance alsu ensures that door and ventilation openings and penet otions. e properly prot ected.

H e guidance requires that these

opening, e protected with fire doors and fire dampers which have been fire tested and listed Ly a nationally recognized testing laboratory (e.g.,

Underwriters Laboratories or factory Mutual).

In addition, the construction.

PROPOSED POSITION - November 19. 1992 and installation techniques for door and ventilation openings and other penetrations through these fire barriers should be appropriately qualified by fire resistive testing.

The guidance of hfPA 251 and ASTM E-119 should be consulted with regard to construction, materials, workmanship, and details such as dimensions of parts, and the size of the specimen (s) to be tested.

In addition, NFPA 251 and ASTM should be consulted with regard to the placement of thermocouples on the specimen.

V.

ELEC1RICAL RACEWAY AND COMPONENT flRE BARRIER SYSTF.MS FOR SEPARATING SAFE SHU1DOWN IUNCTIONS WITHIN THE SAME flRE AREA The NRC provided guidance in Appendix A to Branch Technical Position 9.5-1, position D.3.(d), for cable tray fire barriers.

This fire protection guidance states that the design of fire barriers for horizontal and vertical cable trays should, as a minimum, meet the requirements of ASTM E-119, " fire Test of Building Construction and Materials," including hose stream test.

On November 19, 1980, the NRC issued Appendix R to 10 CFR 50.

The technical basis for Section !!!.M " fire Barrie.r Penetration Seal Qualification," states that " fire barriers are ' rated' for fire resistance by being exposed to a

' standard test fire.'

This standard test fire is defined by the American Society of Testing and Materials in ASTM E-Il9."

In addition, this technical basis stated that "If specific plant conditions preclude the installation of a 3-hour fire barrier to separate the redundant trains, a 1-hour fire barrier and ntomatic fire suppression and detection system for each redundant train will be considered the equivalent of a 3-hour barrier."

in 1984 Appendix R workshops held with industry, and later in GL 86-10, the staff provided guidance related to fire barrier designs for raceways, in, Question and Answers, to this GL, Question 3.2.1., " Acceptance Criteria," the staff provided guidance en the cold side temperature for fire barrier cable tray wraps.

In response to this question the staff stated that the acceptance criteria contained in Chapter 7 of NTPA 251, " Standard Methods of fire Tests of Building Ccnstruction and Materials," pertaining to non-bearing fire barriers was applicable to :able tray fire barrier wraps.

Chapter 5 of NFPA 25) explains the co'nduct of the fire test.

The following is the NFPA 251 acceptance criteria:

The wall or partition shall have withstood the fire endurance test without the passage of flame or gases hot enough to ignite cotton waste, for a period equal 't'o that for which classification is desired; The wall or partition sball have withstood the fire and hose stream test as specified in Chapter 5, without passage of flame, or gases t

hot enough to ignite cotton waste, or of the hose stiee.m. The 1 r

EROPOSED P011110N - Novefn.htr__llE assembly shall be considered to have failed the hose stream test if I

an opening develops and permits projection of water from the stream beyond the unexposed surface during the hose stream test; and Transmission of heat through the wall or partition during the fire endurance test shall nct have been such as to raise the temperature on its unexposed surface more than 250 'T (121 'C) above it s initial t errperat ure.

The staff considers the fire endurance qualification test to be successful if the following conditions are rnet:

lhe internal temperature of the fire barrier system, as measured on theexteriorsurfaceoftheracewayorcomponynt,didnotexceed 250 *f (121 *C) above its initial temperature ;-or (Staff Guidance: NfpA 251/AsiM-E119 allows this temperature to be determined by averaging thermocouple temperature readings.

for-the purposes of this criteria, therniocouple averaging can be used providing similar series of thermocouples-(~

9., cable tray side rail) are averaged together to dete mine temperature performance of the raceway fire barrier sy' stem.

In addition, the conditions of acceptance are also placed on the temperatures measured by a single thermocouple.

Under the conditions of acceptance, if any single thermocouple exceeds 30 percent of the maximum allowable temperature rise (i.e., 250 'f + 75 'f 325 'F) the test is considered to have exceed the criteria tempera,ture limit.)

Wheretheabovethermallimitsareexceeded,a-visualinspectionof the of the cables is required.

Cables when inspected shall not

  1. The 325*f temperature condition was established by allowing the internal temperature on the raceway to rise 250*f above. ambient laboratcry air temperature, assumed to be 75*f, during the fire test.

3 for components, when the temperature criteria.is exceeded, an assessment of component operability at the temperature conditions which would be experienced by the component during the fire test is required that is, fire endurance tests which are judged acceptable on the basis of a visual inspection may not be applied to other components without a specific evaluation.

l e

PROPOSED POSITION - November 19. 1992 show signs of degraded conditions' resulting from the thermal affects of the fire exposure; and (Staff Guidance: f or those cases where signs of thermal degradation to the cables is present, it is considered that the fire barrier did not perform its intended fire resistive fun:. tion.

For those barriers which are not capable of p?rforming their intended function, a deviation based on demonstrating that the functionality of thermally degraded cables was maintained and that these cables would have adequately performed their intended function during and after a postulated fire exposure may be granted.

The attachment to this proposed position provides a suggested methodology for demonstrating the functionality of safe shutdown cabling during and after a fire test exposure.)

The raceway fire barrier system shall have remained intact during the fire exposure and water hose stream test without developing any openings tt Mugh which the electrical conductor or raceway is visible.

Section Vil identifies acceptable hose stream test methods and the time of application.

The test specimen shall be representative of the construction for which the fire rating is desired, as to materials, workmanship, and details such as dimensions of parts, and shall be built under representative conditions.

Raceway fire barrier systems being subjected to qualification fire endurance testing shtuld be representative of the end use.

For example, if it is intended to install a cable tray fire barrkr system in the plant without protecting the. cable tray supports, t1En the test program should duplicate these field conditions, in addition, the fire testing program should bound the raceway sizes and various configurations for those fire barrier systems installed in the plant, it should be noted that several-test specimens will be required in order to qualify various sizes of horizontal _ and vertical runs of cable trays and conduits, junction boxes and pull boxes, etc.

The raceway design used for testing should be constructed with materials and configurationt representative of in plant conditions (e.g., mass associated with typical steel conduit, steel cable trays).

Due to the poor thermal canductivity of cable jacket and insulation material, measuring cable temperatures is not considered a reliable means for determining excessive temperature conditions which may occur at any point along the length of the cable during the fire test, in lieu of-measuring the unexposed surface temperature of the fire barrier test specimen, methods which

' Examples of thermal cable degradation; jacket swelling, splitting, cracking, blistered, melted, or discoloration; shield exposed; conductor insulation exposed, degraded, or discolored; bare copper conductor exposed, i

l

a PROPOSED PO3ITION - November 19. 1992 will adequately measure the surface temperature of the raceway (e.g., exterior of the conduit, side rails of cable trays, bottom and top of cable tray surf aces, junction box external surfaces) can be considered as equivalent if the raceway components used to construct the fire test specimen represent plant specific couponents and configurations.

The netal surfaces of the raceway, under fire test conditions, exhibit good thermal conductivity properties.

Temperatures measured on these surfaces provide a reliable indication of the actual temperature rise within the fire barrier system.

ANI criteria for testing fire barriers recommends the cable temperatures be monitored by thermocouples.

Industry considers this the proper location for determining the temperature rise within the raceway fire barrier system.

Since cable jackets have a low thermal conductivity, the actual temperatures of the cable, indications of barrier failure, and internal fire barrier temperature rise conditions during the fire exposure are masked.

Monitoring cable temreratures can give indications of low internal fire barrier temperature conditions during the fire endurance test.

Using this temperature monitoring approach, cable damage can occur without indication of excessive temperatures on the cables.

This linked with no loss of circuit integrity would give indications of a successful test.

The staff considers monitoring the cable temperature as the primary means of determining barrier performance to be nonconservative. As discussed above, temperatures monitored on the exterior surface of the raceway provide a more representative indication of fire barrier performance.

The following are suggested placement of thermocouple on raceway fire barrier enclosures:

Conduits - measure the temperature of the conduit by placing the thermocouples every 6-inches on the conduit surface underneath the fire barrier material.

P Cable Trays - measure temperature rise of cable tray by placing the thermocouples on the exterior surface of the tray side rails underneath the fire barrier material, in addition to placing thermocouples on the side rails, thermocouples shoul'd be attached to two 14 gage bare copper conductors. The first copper conductor should be installed on the bottom of the cable tray rungs along the entire length of the cable tray run.- The second conductor should be installed along the outer top surf ace of the cables closest to the top and towards the center of the fire barrier.

The bare copper,, wire is more responsive, than cable jackets, to temperature risc within the fire barrier enclosure.

The temperature changes measured along the bare copper conductors provide indication of joint failure or material burn through conditions.

Thermocouples should be placed every 6-inches along the cable tray side rails and along the bare copper conductors..

h

fiQEQjKD POSITION - November 19. 19R2 e

In addition, thermecouples should be placed every 12-inches on the surface of the outer cables nearest to the raceway and on the surface of l

the cables nearest to the underside of the top of the fire barrier.

lhe tenperature conditions on the raceway during the fire test should be determined by averaging the temperatures measured by the thermocouples.

In determining the raceway temperatute conditions, the thermocouples measuring similar fire barrier areas of performance should be averaged together and the basis of acceptance should be based on these individual averages.

The f ollowing method of averaging should be followed:

butdnits - The thermocouples applied to the outsido metal surface of the conduit should be averaged together.

Obie _ lam - The thermocouples on the cable tray side rail should be averaged separately.

For example, thermocouples placed on one side rail should be averaged separately from the other side rail.

In addition, the temperature conditions measured by thermocouples on the bare copper conductors should be averaged separately.

D blei - The thermocouples used to measure individual cable temperatures should be used for engineering purposes and should not_be used for evaluating tne performance of the fire barrier system.

for each thermocouple group, the averages should not exceed 250 'f above the initial +,emperature at the onset of.t.he fire endurance test, in addition, the temperature of each individual thermocouple should be evaluated.

Individual thertucouple conditions should not exceed the 250 *f limit by 30 percent (75 'F).

VI.

HOSE S1 REAM TESilNG NFPA 251 and ASIM E-119 allow some flexibility in hose stream testing.. The standards allow the hose stream test to be performed on a duplicate test specimen subjected to a fire endurance test for a period equal to one-half of that indicated as the fire resistance rating, but not for more than I hour (e.g., 30 minute fire exposure to qualify a 1-hour fire rated barrier).

for safe shutdown related fire barrier systems, the staff would find the hose stream application specified by the NFPA 251 acceptable.

NFPA 251 requires the stream of water to be delivered through a 24-inch (6.4 cm) hose u

discharging through a standard 1%-inc,h (2.9 cm) playpipe nozzle onto the test l

specimen after the fire exposure test.

The stream is applied with the nozzle orifice positioned 20 feet (6.1 meters) away from the center of the test specimen at a pressure of 30 psi (207 Kpa).

The application of the stream is to all exposed parts of the specimen for a minimum duration of 1 minute for a 1-hour barrier and 2) minutes for a 3-hour barrier.

I-

.g.

f20 POSED P0ilTION - November 19. l H2 As an alternate, the application of the hose stream test on the test specimen can be performed immediately af ter the completion of the full fire endurance test period.

If this method is used to satisfy the hose stream testing criteria, the following hose stream applications would be considered acceptable-The stream applied at random to all exposed surfaces of the test specimen through a 24-inch (6.4 cm) national standard playpipe with a 1%-inch (2.9 cm) orifice at a pressure of 30 psi (207 Kpa) at a distance of 20 feet (6.1 meters) from the saecimen, (Duration of the hose stream application 1 minute for a 1-lour barrier and 24 minutes for a 3-hour barrier); or The stream applied at random to all exposed surfaces of the test specimen through a 14-inch (8.3 cm) fog nozzle set'at a discharge angle of 30 degrees with a nozzle pressure of 75 psi (517.5 Kpa) and a minimum discharge of 75 gpm (284 1pm) with the tip of the nozzle at a maximum of 5 feet (1.5 meters) from the test specimen.

(Duration of the hose stream application - 5 minutes for both 1-hour and 3-hour barriers); or The stream applied at random to all exposed surfaces of the test specimen through 1%-inch (8.3 cm) fog nozzle set at a discharge angle of 15 degrees with a nozzle pressure of 75 psi (517.5 Kpa) and a minimum discharge of 75 gpm (284 1pm) with the tip of the nozzle at a maximum of 10 feet (3 meters) from the test specimen. (Duration of the hose stream applicat, ion - 5 minutes for both 1-hour and 3-hour barriers.)

Vll.

FIRE BARRIER COMBUSTIBit.lTY The NRC's fire protection guidelines and requirements establish the need for-each nuclear power plant to perform 4 plant-specific fire hazard analysis.

The fire hazard analysis should consider the potential for in-situ and transient fire hazards and combustibles.

With respect to building materials (e.g., cable insulation and jackets, plastics, thermal insulation, fire barrier materials), the combustibility, ease of ignition, and flame spread over the surface of a material should be considered by the fire hazards analysis.

One method of determining combustibility is by subjecting a sample of the fire barrier material _to a small scale vertical tube furnace as d 3cribed by ASTM E-136.

The flashover ignition temperature, as determined by ASTM-D1929, and the flame spread characteristics, as determined by AS1M E-84, of the fire barrier material should be evaluated, The potential heat release of the material should also be determined and factored into the fire hazard:.

analysis.

The heat release of the material can be determined by testing to the provisions of ASTM D-3286 or NFPA 259.

'.10

~

P 110 POSED POSITION - November 19 J JJ2 i

T'rt barrier materials used as radiant energy heat shields inside containment and used to achieve a combustible free zone are required to be noncombustible as defined in Section 111.

Vll). REFERENCES I

((glea r Reggl.010r_y Commi s siof) 1.

May 1, 1976 Branch Technical Position (APCSB) 9.5-1, " fire Protection Program."

2.

february 24, 1977 Appendix A to the Branch Technical Position APCSB 9.5-1,

  • Guidelines for fire Protection for Nuclear Power Pitnts Docketed Prior to. July 1 1976."

3.

february 19, 1981 10 CFR 50.48. " Fire protection."

4.

february 19, 1981 Appendix R to 10 CFR 50, " fire Protection for Nuclear Power Plants."

5.

february 20, 1981

" Staff Position - Safe Shutdown Capability,"

(Generic Letter 81-12) 6.

July 1981 NUREG - 0800, Standard Review Plan (SRP), 9.5.1,

" fire Protection for Nuclear Power Plants."

7.

October 19, 1983 "NRC Positions on Certain Requirements of Appendix R to 10 CFR 50," (Generic Letter 83-33) 8.

April 24, 1986

" Implementation of fire Protection Requirements," (Generic letter 86-10)

Merican Society for Tettina and Materials (ASTM) 1.

ASTM E-84 Test " Surface Burning Characteristics of Building Materials."

2, ASTM E-Il9, " fire Test of Buildin9 Construction and Materials."

3.

ASTM E-136, " Behavior of Mater.i.als in a vertical Tuoe furnace at 750'C."

4.

ASTM D-1929, " Test Method for 19nition Properties of Plastics."

5, ASTM D-3286, "lest Method for Gross Calorific Value of Solid fuel by the isothermal-Jacket Bomb-Calorimeter.".

4 e

PROPOSED POSITION - November 19. 1992 American Ngglear Insurers (A41) 1.

July 1979, ANI Information Bulletin No. 5 (79) test criteria for " Fire Endurance Protective Envelope Systems for Class IE Electrical Circuits."

National Fire Protection Association (NFPA)

Materials.,' Standard Methods of Fire Tests of Building Construction and NFPA 251, '

1.

2.

NFPA 259,

  • Standard Test Method for Potential Heat of Building Materials" G

[ CRITERIA.009) t L

e 4 !

PROPOSED POSllipF - Nqvember 19. 1992 ATTACHMENT i

ACCEPTABLE METHODS FOR DEMONSTRATING FUNCTIONAllTY OF I

CABLES PROTECTED BY RACEWAY flRE BARRIER SYSTEMS DURING AND AF1ER flRE ENDURANCE TEST EXPOSURE a.

11HR00VGLQ1{

1he NRC considers fire barrier systems, which do not exceed the acceptance criteria, to provide the level of safety required to meet the NRC's fire protection regulations.

Based on an engineering assessment of the conservatism (defense-in-depth) factored into the NRC's fire protection regulations and guidance, there is reasonable assurance that sensible heat from the unexposed side of the fire barrier will not be transmitted to the protected cable. Under such conditions, where the fire barrier system does not meet the intended fire rating, the margin.

of fire safety is not considered equivalent to-the level required by the regulations or fire protection guidelines.

The licensee, under_these conditions, can submit cn engineering analysis to the staff that clearly demonstrates the functionality of the protected cable (s).

This engineering analysis should consider the cable insulation type, actual voltage and current conditions, cable function, and thermal affects on the cable and it's ability to function.

This evaluation should also consider cable operating temper.atures within the fire barrier at the onset of the fire exposure.

b.

CABLE CIRCVIT INTEGRITY TESTING 6111 Criteria In 1981, American Nuclear Insur'ers (ANI) developed a fire endurance test criteria for raceway fire barrier systems.

This criteria, " Fire Endurance Protective Envelope Systems for Class IE Electrical Circuits,"'

specifies a circuit integrity test.

The intent of this test was to identify the onset of fire damage.to the cables within the raceway fire barrier test specimen during the fire endurance test' period.

The circuit integrity test voltage is 8 to 10' volts DC,:therefore the loss of circuit integrity under these voltage conditions may only occur as a result of a dead short or open circuit.

During actual fire testing conditions of raceway fire barrier systems.

thermal damage to the cables has resulted.

This thermal damage has, led to cable jacket and insulation degradation without the loss of circuit integrity as monitored using ANI criteria.

Since cable voltages used for AN! circuit integrity testing do not replicate cable operating voltages, loss of cable insulation conditions can exist during the fire test without a dead short occur' ring.

It is expected if the cables were at rated power and current a fault would propagate.

Therefore, the use E.

A

ERDP01RJEJ110N - November 19 1912 of ANI circuit integrity monitoring during the fire endurance test is not considered a valid method for demonstrating that the protected shutdown circuits are capable of performing their required function during and after the test fire exposure, c.

GMLIBSUL AT10N TESTI@

lhe two principal materials used as cable insulation and ceble jackets by the nuclear industry are thermoplastics and thermosetting polymeric materials.

A thermoplastic material can be sof tened and resof tened by heating and reheating.

Conversely, thermosetting cable insulation materials cure by chemical reaction and do not soften when heated.

Under excessive heating thermosetting insulation becomes stiff and brittie.

Electricalfaultsmaybecausedbysofteningandflowingof thermoplastic insulating materials at temperatures as low as 300 f (149 'C),

lhermosetting electrical conductor insulation materials usually retain their electrical. properties under short-term exposures to temperatures as high as 500 *T (260 *C),

insulation resistance (Megger) testing provides an indication of the condition of the cable insulation resistance, whereas the high potential (Hi-Pot) test provides assurance that the cable has sufficient dielectric strength to withstand the applied rated voltage.

A cable insulation failure usually results from two breakdown modes:

one failure mode is excessive dielectric loss which is due to low insulation resistance, and the other failure mode is overpotential stress which is due to loss of dielectric strength of the insulation material.

if megger tests are not performed at frequent intervals during the fire exposure, indications of insulation damage in insulation may go undetected.

Insulation, when removed from elevated temperatures will reset.

Megger testing of insulated cables after the fire endurance test and af ter the cable has sufficiently cooled may not detect degradation in the insulation resistance..Therefore, wet or dry megger of cables after a fire exposure does not provide reasonable assurance that the cables would have functioned as intended during the fire exposure.

To provide reasonable assurance that the cables would have functioned during and after the fire exposure, megger tests need to be performed before the fire test, at multi.p,le time intervals during the fire exposure (i.e, every 20 minutes during the 1-hour fire test and every hour during the 3-hour fire test) for instrumentation cables only, and after fire endurance test to assess the cable insulation resistance icvels.

This testing will assure that the cables will maintain sufficient insulation resistance levels necessary for proper operation of instruments.

The megger tests (pre-fire, during the fire ( if performed), and immediately after the fire test conditions) should be done conductor-to-,

ER0f01GLf011110N - Ngnaber.1L_19R conductor f or multi-conductor and conductor-to-ground for all cables.

1he minimum acceptable insulation resistance (IR) value, using the test voltage values as shown in the table below, is determined by using the following expression:

IR (Mega-ohms) 2 fif) MegA-ohm p_gr KV) 4 1 1

  • 1000 fft) 1 Length (ft)

Additionally, in determining the insulation resistance levels required for nuclear instrumentation cables, an assessment of the minimum insulation resistance value (e.g., one mega+ ohm) and its potential impact on the functionality of these cables should be evaluated, in addition, an AC or DC high potential (Hi-Pot) test for power cables greater than 1000 volts should be performed af ter the post-fire megger tests to assess the dielectric strength.

This test provides assurance that the cable will withstand the applied voltage during and after a fire.

The high potential test should be performed for a five minute duration at 60 percent of either 80 volts / mil ac or 240 velts/ mil dc (e.g., 125 mil conductor insulation thickness x 240 volts dc x 0.6 18.000 volts dc ).

The table below summarizes the pegger and Hi-Pot iest voltages which, when applied to power, control and instrumentation cables, would constitute an acceptable cable functionality test.

OPERAllNG MEGGER TEST HIGH POTENTIAL 11El Y.QLTAGES VOLTAGE TEST VOLTAGE POWER 2 1000 vtc 2500 ydc 60% x 80 V/ mil (ac) 60% x 240 V/ mil (dc)

POWER

< 1000 vac 1500 vdc #

NONE INSTRUM[NT $ 250 vdc 500 vdc NONE AND 5 120 vac CONTROL

  • A megger test valiag? of 1000 vdc will be acceptable provided a Hi-Pot test is performed after'the megger test for power cables rated at less than 1000 vac.

d.

(AHLLE[MA1_(JPOS_URE THRESHOLD 1he following is a proposed an'ilysis method for evaluating the cable functionality.

3

PROPOSED POSITION. November 19. 1992 This analysis is based on determining whether a specific insulation material will maintain the electrical integrity and operability within a raceway fire barrier system dur.ing and after an external fire exposure, in order to determine cable functionality, it is necessary to consider the operating cable temperatures within the fire barrier system at the onset of the fire exposure and the thermal exposure threshold (TET) temperature of the cable.

For example, if the TET of a specific thermoplastic cable insulation (Brand X) is 300 'f (149 'C) and the noimal operating temperature wtthin the fire barrier system is 150 'T (66 *C), then the maximum temperature rise within the fire barrier system should not exceed 150 *f (66 'C) during exposure to an external fire of a duration equal to the required fire resistance rating of the barrier.

For this example the TET limit for Brand X cable is 150 'f (66 *C) above the cable operating temperatures within the fire barrier system at the onset of the external fire exposure.

Because of the non-uniformity of cable insulation materials and variations in the manufacturing process, the cable insulation has inherent weak spots.

Therefore, the cable TET limits in conjunction with a post test visual cable inspection ar.d the Hi-Pot test described above should readily demonstrate the functionality of the cable circuit during and after a fire.

The cable normal operating temperature can be determined by subjecting cable specimens installed within a thermal barrier system and loaded at insulation may be obtained from, TET temperature limits for most cable rated voltage and current.

The the manufacturer's published data which is given as the short-circuit rating limit.

With the known TET and normal operating temperature for each thermal barrier system configuration, the maximum temperature rise limit within a fire barrier system may then be determined.

Due to poor thermal conductivit'y of cable insulation, measuring cable insulation temperatures is not considered a reliable means for determining temperature conditions which may occur along the entire length of the cable during the fire test.

However, as an alternate to measuring the unexposed surface temperature of the fire barrier test specimen, methods which will adequately measure the surface temperature of the raceway (e.g., exterior of the conduit, side rails of cable trays, bottom and tap of cable tray surfaces, junction box external surfaces) are considered equivalent.

The steel surfaces of the raceway, under fire test conditions, exhibit good thermal conductivity properties.

Temperatures measured on these surfaces provide a reliable indication of actual temperature rise within the fire barrier system.

y r

y -