ML20128B866

From kanterella
Jump to navigation Jump to search
Forwards Corrected LER 92-019-00,including Event Date Inadvertently Omitted from 930128 Memo
Date released: 05/21/2020 Download: ML20128B866


:on 921230,design Deficiency W/Ac Electrical Sys Confirmed When Single Nonaccident Event Could Result in Common Mode Failure of Both Dgs.Permanent Electrical Jumper Installed in Each Breaker Trip Circuit
ML20128B881
Person / Time
Site: Cooper Entergy icon.png
Issue date: 01/28/1993
From: Reeves D
NEBRASKA PUBLIC POWER DISTRICT
To:
References
Download: ML20128B881 (7)
Forwards Corrected LER 92-019-00,including Event Date Inadvertently Omitted from 930128 Memo
ML20128B861
Person / Time
Site: Cooper Entergy icon.png
Issue date: 01/29/1993
From: Gardner R
NEBRASKA PUBLIC POWER DISTRICT
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
Download: ML20128B861 (1)