-Q.

.w.

-X. ?

Southem Califamia Edison Company 23 PARKER STHE ET IRVINE. CALIF OHNiA 9271B WALTER C M AH SFt mcC1'/CC^71",..,

January 18, 1993 EU.E U. S. Nt

. " Regulatory Commission Atter Document Control Desk Wa

, D.C. 20555 Gentlemen:

Subject:

Docket No. 50-362 Report of NPDES Permit Violation San Onof re Nuclear Generating Station Unit 3

Reference:

Letter from H. W. Newton (SCE) to A. L. Coe (California Regional Water Quality Control-Board, San Diego Region),

NPOES Monitoring Report, November 30, 1992 Section 3.2 of Appendix B to Facility License No. NPF-15 for San Onofre Nuclear Generating Station (SONGS) Unit 3 requires Southern California Edison (SCE) to report violations of the National Pollutant Discharge Elimination System (NPDES) permit.

This letter reports one NPDES violation for Unit 3.

The referenced letter is provided as an enclosure.

During the month of October all sampled water sources were found to be within permit limits with one exception. A release of water with a total suspended solids concentration of 176 occurred on Octcher 2,1992. This exceeded the NPDES permit instantaneous limit of 100 ppm. The_ release was caused by a valving misalignment which resulted in the inadvertent release of water from the Full Flow Condensate Polish Demineralizer to the combined discharge rather than to a holding tank.

Procedural changes-have been made to prevent-recurrence.

If you have any questions, please contact me.

Sincerely, Q{j]61 Enclosure cc:

J. B. Martin, Regional Administrator, NRC Region V M. B. Fields, NRC Project Manager San Onofre Units 2 and 3 C. W. Caldwell, NRC Senior Resident Inspector,- San Onofre Units 1, 2&3 0&. l 9302010003 930116 i-U PDR ADOCK 05000362-PDR

(,,

S --

4 t.

November 30, 1992 California Regional Water Quality Control Board San Diego Region 9771 Clairemont Mesa Boulevard, Suite B San Diego, California 92124-1331 Attention:

Mr. Arthur L.

Coe

Dear Mr. Coe:

SU BJECT:

NPDES Monitoring Report San Onofre Nuclear Generating Station, Unit 3 The NPDES Discharge Monitoring Report (DMR) for San Onofre Unit 3 3

covering the month of October is submitted in accordance with the requirements of Order No. 85-13 (NPDES Permit No. CA01 s d181).

A summary of the generating unit's status and significant analytical results is provided below.

The unit was in operation all month and all sampled water sources were found to be within permit limits with one execption.

The exception occurred on October 2, 1992 at the Full Flow Condensate Polish Domineralizer with the release of water at a total suspended solids concentration of 176 ppm.

This exceeded the permit's instantaneous maximum concentration limit of 100 ppm.

The release was caused by a valving misalignment which resulted in the inadvertent release of water to the combined diccharge rather than to a holding tank.

Procedural changes have been made to prevent recurrence.

Pursuant to Order No. 85-13, Reporting Requirement 12, the following representative has prepared and is authorized to sign the reports requireil by this order:

Robert M.

Goodson, Environmental Engineer.

m I

--- - -. =

..... -. -. - _.. ~...... -,..

I y

.c.

4

- Mr. Arthur L.

Coe November 30',

1992-I certify under penalty of' law that I have personally examined

)

and am. familiar with the information submitted in the attached document,=and based on my inquiry of those individuals-immediately responsible for obtaining the information, I believe the submitted information is true, accurate, and complete.

I ani j

aware that there are significant penalties for submitting false j

information, including the possibility of fino and imprisonment.

j i/

I. W. NEWTON l

Manager, Site Support Services rmg:U3cct92NPD Enclosure cc:

Environmental Protection Agency, Region IX bec:

R.

M.

Rosenblum H.

W.

Newton /M. J. Johnson - w/o enclosure g R.

V.

D. Reid 1

N. J. Mascolc - w/o enclosure G.

E. Hannond - w/o enclosure K. T. Herbinson CDM Files Environmental Protection Files a

}

t 0

e u

o-w 7