ML20127K849

From kanterella
Jump to navigation Jump to search
Forwards Test Results of Five Test Lots of Five Star Products,Inc Grout,As Requested by Nrc,Demonstrating Ability to Meet or Exceed Critical Characteristics of Compressive Strength & Zero Shrinkage Required for Grout Placement
ML20127K849
Person / Time
Site: Brunswick  
Issue date: 11/16/1992
From: Mccarthy D
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NLS-92-310, NUDOCS 9211230279
Download: ML20127K849 (5)


Text

. _ -.

U. 3 Ca ouna power 8. Lhht Company L iH0V 161992 SERIAL:

NIS-92-310.

United States Nuclear Regulatory Commissio1 ATTENTION:

Document Control Desk Washington, DC 20555 BRUNSWICK STEAM ELECTPIC PLANT, UNIT NOS. 1 AND 2 DOCKET NOS. 50-325 AND 50-324/ LICENSE NOS. DPR-71 AND DPR-62 FIVE STAR GROUT Gentlemen Carolina Power & Light Company (CP&L) is pleased to provide 4che test results of five test lots of Pive Star Products, Inc. (Five Star) grout as requested by the NRC.

Carolina Power a Light Company was notified by letter dated August 25, 1992, that rive Star was suspending its quality program; Five Star was subsequently removed trom our approved supplier list, effective August 31, 1992.

NRC Information Notice 92-66 was rece19ad by CP&L on September 9, 1992.

Review of the Information Notice determined that our actions were consistent

-with the intent of tia Notice.

To ensure that the Five Star grout on hand at the Brurswick Steam Electric Plant (BSEP) was acceptable for use in safety-related applications, one bag.

per lot was tested.

These specimans were submitted to Law Engineering Compen;, Raleigh, North Carolina, on September 11, 1992. The bag lots were tested for the critical characteristics of 5,000 pounds par rquare inch compressive strength after curing for seven days, as well as for -ero vertical expansion and shrinkage.

Samples from each of the five lots exceeded the minimum required strength for compressivo tests at the 3,

7, and 28-day-1.ntervals and exhibited cero shrinkage.

- are included with this responae for your information.The test results from Law Engineering-Based an the results of the Law Engineering grout teste, the material has demonstrated its ability to meet or exceed the critical characterirties of compressive strength and zero shrinkage that aro riquired for grout placement.

In our experience using this material, Five Star grout has exhibited ita ability to adequately perform its desian function.

A h V 'p I i

9211230279 921116-DR ADOCK 0500 4

I m F.,,wwe sheet

  • P. O Bau 1551
  • Ra+9s N C PN2 l-

,,_wnemmwm-n mnran osuaw>

'* _ Document control Dook-

  • ~

NLS-92-310-/ Page 2

-If-any further_information on this subject is needed, please contact Mr. D.

B.

Waters at (919) 546-2710.

Yours_very truly,

/

f David c. McCarthy 5 Manager Nuclear Licensing Section JHH/jbw Enclosures cc:

Mr. S.

D.

Ebneter Mr. R.

H. Lo Mr. S. Magruder (NRR)

Mr. R. L. Prevatte (1836CLU)

M

NLS 92-310 ':

Attachment Page 1 of-3 d**

LAW ENGINEERING l etm tem October 23,1992 a wommwtus -

@GAWUS Carolins Power & Light Company Brunswick Nuclear Project Highway 87 North Southport, North Carolina 28461

Subject:

Five Star Grout Properties Tests CP&L Requisition Number - 2Q0083 CP&L Purchase Order No. 590184M-CL law Engineering Job No. 473-08096-01 Attn:

Mr. Frank Doty Following are the complete results of the great testing conducted on the Five Star Grout samples for the Erunswick Nuclear Project.

LOT A 3 Day Averare 7 Day Average 28 Day Average Compressive Strength Tests =

6700 psi 8110 psi 10010 psi.

Sample 1 Samole 2 t

3 Day Expansion / Shrinkage =

- 0.00%

0.00 %

7 Day Expansion Shrinkage =

0.00 %

0.00 %

28 Day Expansion /Shriakage =

0.00 %

0.00 %

i I.

l l~

3301 ATLANTIC AVE.

1 P.O. BOX 18238

- RALEIGH NC 27619 -

. 919 4 76 4416

I

(

NLS 92-310 At tach: ent Page 2 of 3

$M Carolina Power & Light Company October 23,1992 Page 2 IDTB I

3 Day Average 7 Day Average 28 Day Averagt Compressive Strengei Tests =

8660 psi 9030 psi 9540 psi Sample 1 Sampic.2 3 Day Expansion / Shrinkage =

0.00 %

0.00 %

7 Day Expansion / Shrinkage =

0.00 %

0.00 %

28 Day Expansion / Shrinkage =

0.00 %

0.00 %

LOT C 3 Day Average 7 Day Average 28 Day Average 8710 psi 9070 psi 10210 psi Compressive Strength Test:

=

Sample 1 Sample 2 3 Day Expansion / Shrinkage =

0.00 %

0.00 %

v 7 Day Expansion / Shrinkage =

0.00 %

0.00 %

28 Day Expansion / Shrinkage =

0.00 %

0.00 %

NLS 92-310

~

Attachment Page 3 of 3 z

Carolina Power & Light Company

  • 1 October 23,1992 Page 3 LOT D 3 Day Average 7 Day Average 28 Day Average Compressive Strength Tests =

8210 psi 9340 psi 9570 psi Sample 1 Sample 2 3 Day Expansion / Shrinkage =

0.00 %

0.00 %

7 Day Expansion / Shrinkage =

0.00 %

0.00 %

28 Day Expansion / Shrinkage =

0.00 %

0.00 %

LOT E 3 Day Average 7 Day Average 28 Day Average Compressive Strength Tests =

7650 psi 9380 psi 9670 psi Sample 1 Silm & _2 3 Day Expansion / Shrinkage =

0.00 %

0.00 %

7 Day Expansion / Shrinkage =

0.00 %

0.00 %

28 Day Expansion / Shrinkage =

0.00 %

0.00 %

Please call if you have any questions or if we can be of further service.

Sincerely, Law Engineering. Inc.

'llfwN TY Martin Phillips, E.I.T.

Staff Engineer