RO:721215,smoke Observed Coming from RHR Svc Water Pump Seal.Pump Removed from Svc.Caused by Overtightening of Upper Gland Seal.Seal Packing for Subj Pump Replaced
ML20127G559
Person / Time
Site: Monticello 
Issue date: 01/11/1973
From: Mayer L
NORTHERN STATES POWER CO.
To: Anthony Giambusso
US ATOMIC ENERGY COMMISSION (AEC)
References
NUDOCS 9211170378
Download: ML20127G559 (1)


Text

.

' MSP

)m NORTHERN STATES POWER COMPANY MIN N E A POLIS, MIN N E SOTA 55401 January ll, 1973

{'

b p h g"{3 '

~31 Mr. A. Giambusso 6-gf 7

Deputy Director for Reactor Projects

'4 y

4 Directorate of Licensing y

United States Atomic Energy Commission y

e Washington, D. C.

20545 6

' Regulatory Filo Cyi

Dear Mr. Giambusso:

'JJ MONTICELLO NUCLEAR GENERATING PLANT Docket No. 50-263 License No. DPR-22 RHR Service Water Pump Seal Problem A condition occurred at the Monticello Nuclear Generating. Plant recently which we are reporting to your office in accordance with the provisions of Section 6.6.C.1 of Appendix A, Technical Specifications, of the Provisional Operating License DPR-22.

The Region III Compliance office has been notified of the event.

On December 15, 1972, while operating #11 RHR Service Water pump for shutdown cooling, smoke was observed coming from the pump.

The pump was removed from service.

An investigation of the problem revealed that the upper gland seal on the pump had l

overheated due to a lack of sealing water flow which was apparently caused by over-tightening of the upper gland seal.

The upper gland seal packing for #11 RHR Service Water pump was replaced and the pump t

was returned to service on December 19, 1972. A memo has been issued to remind l

Operations and Maintenance personnel of procedures for monitoring seal water flow l

and the manufacturers instructions for packing gland adjustments.

A Significant Operating Event Report is available at the site for the Regulatory Operations inspectors.

You:s very truly, k

g Docg '(

L. O. Mayer, P.E.

Director of Nuclear Support Services NC

^

I5l3

[ '.[

73 %

LOM/vm

~

G-Ai d(Y p g,

l cc B. H. Grier

%s m

1 l

9211170378 730111 PDR ADL'CK 05000263 S

PDR 1