ML20127F508

From kanterella
Jump to navigation Jump to search
Forwards Application for Amend to License NPF-3,revising Tech Spec Section 3.7.1.1 to Change Cold Shutdown (Mode 5) to Hot Shutdown (Mode 4).Safety Evaluation & Significant Hazard Consideration Also Encl.Fee Paid
ML20127F508
Person / Time
Site: Davis Besse 
Issue date: 06/17/1985
From: Crouse R
TOLEDO EDISON CO.
To: Stolz J
Office of Nuclear Reactor Regulation
Shared Package
ML20127F511 List:
References
1159, NUDOCS 8506250179
Download: ML20127F508 (1)


Text

F i

TOLEDO

%mm EDISON Docket No. 50-346 RICHARD P. CROUSE License No. NPF-3 y,, p,,,,,

Serial No. 1159 arme June 17, 1985 (4193 24naat Director of Nuclear Reactor Regulation Attention:

Mr. John F. Stolz Operating Reactor Branch No. 4 Division of Licensing Uaited States Nuclear Regulatory Commission kashington, DC 20555

Dear Mr. Stolz:

Under separate cover, we are transmitting three (3) original and forty (40) conformed copies of an application for Amendment to Facility Operating License No. NPF-3 for the Davis-Besse Nuclear Power Station Unit No. 1.

This application requests that the Davis-Besse Nuclear Power Station Unit 1 Technical Specifications, Appendix A, be revised to reflect the changes attached. The proposed change is in Section 3.7.1.1.

The attachment identifies the proposed changes and its safety evaluation and a significant hazard consideration. The proposed change concerns the Limiting Condition for Operation Action Statement which now requires that with one or more Code Safety Valves inoperable, either restore the va he(s) to OPERABLE status, or reduce power per Table 3.7-1, or shutdown the plant and proceed to COLD SHUTDOWN. This amendment requests to change COLD SHUTDOWN (MODE 5) to HOT SHUTDOWN (MODE 4).

The Code Safety Valves APPLICABILITY of this section is MODES 1, 2 and 3; therefore, the valves are not required in HOT SHUTDOWN (MODE 4) and the plant should not be required to enter COLD SHUTDOWN (MODE 5).

Toledo Edison requests that this amendment request be approved and issued by February 28, 1986.

Enclosed is a check for $150 as required by 10CFR170.12(C) for license

. application.

Very truly yours, f

\\

D RPC: GAB:RLW 8506250179 850617 PDR ADOCK 05000346 I

4[9 Attachment P

PDR cc: DB-1 NRC Resident Inspector State of Ohio E

THE TOLEDO EDISON COMPANY EDISON PLAZA 300 MADISON AVENUE TOLEDO, OHIO 43652 b

i Y