Category:REPORTABLE OCCURRENCE REPORT (SEE ALSO AO LER)
MONTHYEARML20055F8591990-07-16016 July 1990 Special Rept 90-11:on 900613,06,25,18,21 & 28,fire Barriers Breached More than 7 Days & Not Made Operable in 14 Days. Corrective Actions:Operability of Fire Detectors Verified on One Side of Breached Barriers ML20055C6301990-05-21021 May 1990 Special Rept 90-09:on 900424,25,30,31 & 0502,fire Barriers Inoperable for More than 7 Days,Per Tech Spec 3.14.6.2 Requirement.Hourly Fire Watches Established & Penetrations & Doors Returned to Operable Status ML20055C6291990-05-21021 May 1990 Special Rept 90-08:on 900419,fire Pump Batteries Inoperable When Surveillance Procedure SP.206 Not Performed by Due Date.Caused by Test Frequency Incorrectly Changed from Weekly to Monthly.Surveillance Schedule Revised ML20247N7491989-05-30030 May 1989 Special Rept 89-13:on 890328-29,specific Activity of Primary Sys Exceeded Limits in Administrative Procedure & Chemistry Control Commitment.Possibly Caused by Power Reduction.Isotopic Analysis Continued ML20246D4691989-05-0101 May 1989 Special Rept 89-12:on 890330,Tech Specs Violated.Caused by Fire Penetrations 34-69AA & 36-64AA Not Restored to Operable Status within 7 Days.Fire Watch Posted & Penetrations Restored to Operable Status on 890405 ML20246D6411989-04-27027 April 1989 Special Rept 89-11:on 890328,fire Barrier Door Ns 352 Not Restored to Operable Status within 7 Days.Hourly Fire Watch Established & Fire Door Restored to Operable Status on 890405.Fire Barrier Work Requests Under Review ML20245D9191989-04-20020 April 1989 Special Rept 89-10:on 890131,water Deluge Sys for Fire Zone 110 Auxiliary Feedwater Pump Area Not Returned to Operable Status within 14 Days,Per Tech Specs.Work Request 145494 Initiated to Rework Valve.Fire Watch Posted ML20245D0391989-04-10010 April 1989 Special Rept 89-08:on 890311,security Personnel Identified Closure for Fire Barrier Door AU 109 Not Restored to Operable Status within 7 Days.Hourly Firewatch Posted in Area & Tech Spec 3.14.6 Satisfied ML20248G3531989-04-0303 April 1989 Special Rept 89-07:on 890304,fire Barrier Door Not Restored to Operable Status within 7 Days as Required by Tech Specs. Caused by Commitment of Personnel to Outage Activities & Rev of Procedure M.100.Hourly Firewatch Posted in Area ML20247G1151989-03-28028 March 1989 Special Rept 89-06:on 890226,fire Barriers Not Restored to Operable Status within 7 Days.Caused by Pulling Temporary Cables in Support of Special Test Procedure 1218.Hourly Firewatch Posted in Area ML20247B4261989-03-20020 March 1989 Special Rept 89-04:on 890216,fire Barriers Breached More than 7 Days,Per Tech Spec 3.14.6.2.Hourly Firewatch Previously Posted & Fire Barrier Penetrations Restored to Operable Status on 890218 ML20247B7571989-03-20020 March 1989 Special Rept 89-05:on 890221,Tech Spec Limit Exceeded.Caused by Fire Barrier Door AU 319 Not Being Restored to Operable Status within 7 Days Due to Door Sticking & Not Closing Properly.Fire Watch Established & Door Operability Restored ML20235R9091989-02-27027 February 1989 Special Rept 89-003:on 890201-02,RCS Sample Data Indicated Specific Activity Exceeded 0.8 Uci/Ml I-131 Limit.Caused by Normal Increase in Iodine Activity After Power Reduction. Isotopic Analysis Continued Until Restoration Complete ML20235T7881989-02-23023 February 1989 Special Rept 89-02 on 890125:fire Barrier Mechanical Penetration 2233 Not Restored to Operable Status within 7 Days Per Tech Specs & Rubber Boot Seal Removed from Penetration.Hourly Firewatch Posted & Penetration Restored ML20206L8231988-11-23023 November 1988 Special Rept 88-18:on 881025 & 26,failure to Maintain Specific Activity of Primary Sys within Administrative Limits Occurred.Alternate Letdown Sys Purification Demineralizer Placed in Svc ML20206F5421988-11-14014 November 1988 Special Rept 88-17:on 881026,technicians Discovered That Fire Barrier Doors Were Not Restored to Operable Status within 7 Days as Required by Tech Spec 3.14.6.2.Fire Barrier Doors Were Returned to Operable Status ML20207N6211988-10-12012 October 1988 Special Rept 88-15:on 880915,fire Barrier Doors AU 216 & AU 217 Not Restored to Operable Status within 7 Days.Caused by Doors Being Kept Open to Provide Ventilation in Support of Work on Auxiliary Bldg HVAC Sys.Doors Restored ML20207N6041988-10-12012 October 1988 Special Rept 88-16:on 880918,PASS Inoperable More than 72 H. Caused by Clearance Tags Placed on Addl Valves to Disable Flow Path for Backup Dilution/Flush Water from Chilled Water Tank.Sys Returned to Operable Svc ML20207M1241988-10-11011 October 1988 Special Rept 88-14:on 880915,fire Barrier Penetrations Between Fire Areas 75/1 & 77/2 Not Returned to Operable Status within 7 Days.Caused by Insufficient Data in Design Drawings.Fire Watch Posted.Penetrations Restored by 881021 ML20155G2871988-09-27027 September 1988 Special Rept 88-13:on 880908,fire Barrier Penetration Seals for Floor Slots H8FS86 & H8FS87 Not Returned to Operable Status within 7 Days,Per Tech Spec 3.14.6.2.Hourly Firewatch Posted & Penetration Seals Will Be Restored by 881021 ML20154C9711988-09-0606 September 1988 Suppl to Special Rept 88-03 Re Removal of CO2 Fire Suppression Sys from Zones 75-80 Bringing Nuclear Svc Electric Bldg Into Compliance w/10CFR50,App R Requirements ML20154C0481988-08-30030 August 1988 Special Rept 88-12:on 880801,fire Barrier Penetration Seals for Penetrations 2041 & 2044 Breached for More than 7 Days During Power Escalation on 880729.Hourly Fire Watch Provided in Auxiliary Bldg within 1 H of Discovery ML20153F9651988-08-23023 August 1988 Suppl to Special Rept 88-07:fire Sys Changed from Deluge Sys to Spray Type Sys.Auxiliary Feedwater Pump Motors Will Only Be Sprayed During Actual Fire Situation.Shrouding on Motor Vents Modified for Addl Protection Against Water Spray ML20151U5011988-04-18018 April 1988 Special Rept 88-09:during Dec 1987 & Jan 1988,annual Surveillance of Reactor Bldg Surfaces Made ML20151T7181988-04-14014 April 1988 Special Rept 88-08:provides Updated List of Fire Barriers Breached More than 7 Days.Four Breaches Added to Support Ongoing Mod Activites & 23 Breaches Have Been Repaired.Util Will Return to Original Reporting Format ML20151K5401988-04-11011 April 1988 Special Rept 88-07:on 880315,water Deluge Sys for Fire Zone 110 Declared Inoperable.Actuation of Deluge Sys Could Adversely Affect Operability of Both Auxiliary Feedwater Pumps.Compensatory Measures Taken & Fire Watch Established ML20151F9311988-03-25025 March 1988 Special Rept 88-03:on 880225,Tech Spec 3.14.4 Violated. Caused by Fire Suppression CO2 Sys Not Being Restored to Operable Status within 14 Days.Fire Watch posted.CO2 Sys Will Remain Inoperable Until Redesign of Fire Damper Logic ML20148H3151988-03-15015 March 1988 Corrected Special Rept 88-05:on 880206 & 08,both Electric & Diesel Driven Fire pumps,P-440 & P-996 Declared Inoperable Due to Controller Replacement.Errata Corrects Date of Rept Inadvertently Omitted from Original Submittal ML20150E1361988-03-15015 March 1988 Special Rept 88-06:provides Updated List of Fire Nonfunctional Fire Barriers Which Have Not Been Restored to Functional Status within 7 Days,Per Tech Spec 3.14.6.2 ML20196E3691988-02-19019 February 1988 Special Rept 88-05:on 880208,fire Suppression Water Sys Declared Inoperable Due to Inoperable Electric & Diesel Driven Fire Pumps.Sampling Procedure CHM-5105 Revised & Auxiliary Fuel Storage Tank Assembled ML20196E3171988-02-18018 February 1988 Retracted RO 80-26 Re B&W Abnormal Transient Operating Guidelines Program Analysis Concerning Steam Generator Tube Rupture.Concerns Addressed in RO 80-26 Never Valid Since Procedure E.06 Ensures That Offsite Dose Limits Met ML20149K9441988-02-16016 February 1988 Special Rept 88-04,providing Updated List of Nonfunctional Fire Barriers Not Restored within 7 days.Forty-five Reportable Breaches Repaired.Fifteen Breaches Added During Period to Support Ongoing Mod Activities ML20149H9631988-02-0909 February 1988 Special Rept:On 880208,motor & Diesel Driven Fire Pumps Declared Inoperable Due to Failure of Fuel Storage Tank Sample Taken Per Surveillance Requirement 4.18.2.1.h.2. Diesel Pump Functional & Remains Lined Up to Supply Water ML20149D7751988-01-20020 January 1988 Special Rept 88-02:on 880106 & 17,diesel & Electric Driven Fire Pumps Declared Inoperable.Caused by Test Data Indicating Pumps Not Meeting Tech Spec Requirements & Pump Failure of Surveillance Test.Test Procedures Rewritten ML20149D5171988-01-18018 January 1988 Ro:On 880117,motor Driven Fire Pump Declared Inoperable.Pump Repaired & Returned to Operable Status on 880118.Telcon Notification Made on 880118 Per Tech Spec 3.14.2.3.b.1 ML20148K6651988-01-13013 January 1988 Special Rept 88-01:nonfunctional Fire Barriers Not Restored to Functional Status within 7 Days.Since Special Rept 87-26, 29 Reportable Breaches Repaired & 46 Breaches Added to Support Mod Activities ML20234D4651987-12-15015 December 1987 Special Rept 87-26:updated List of Nonfunctional Fire Barriers Breached More than 7 Days Provided.Listed Penetrations Erroneously Reported as Breached & Deleted from Rept ML20237A0971987-11-23023 November 1987 Special Rept 87-25:on 871104,fire Detection Zones 13 & 16 Not Restored to Operable Status within 14 Days as Specified in Tech Spec Section 3.14.1.Firewatches Established.Zones 13 & 16 Fire Detection Sys Will Be Returned to Svc by 871215 ML20236V6371987-11-16016 November 1987 Special Rept 87-24:on 870518,fire Barrier Door AU-218 Breached for More than 7 Days.List of Status of Reportable Breaches in Fire Barriers Encl.Addl 26 Breaches Added Since Special Rept 87-20.Fire Watches Established ML20236M2331987-11-0303 November 1987 Special Rept 87-22:on 871013,listed CO2 Zones Not Restored to Operable Status within 14 Days as Specified in Tech Spec Section 3.14.4.Firewatches Established.Sys Will Be Restored to Operable Status Upon Completion of Maint by 871231 ML20236K2511987-11-0303 November 1987 Special Rept 87-23:on 870910,util Identified That CO2 Zones 53 & 54 Not Restored to Svc within 14 Days.Caused by Opening Doors to Allow Nitrogen Dissipation Due to Plant Maint. Firewatches Established ML20236K4771987-10-29029 October 1987 Special Rept 87-21:on 870929,deluge Sys for Zone 81 Not Returned to Operable Status within 14 Days.Caused by Delay in Required Matl Procurement.Fire Watch Established for Inoperable Sys Per Tech Spec 3.14.3.2 ML20236B4531987-10-15015 October 1987 Special Rept 87-20:forwards Updated List of Nonfunctional Fire Barriers Not Restored to Svc within 7 Days.Since Last rept,72 Breaches Repaired.Twenty Breaches Still Open.Addl 87 Breaches Added to Support Ongoing Mod Activities ML20236A2201987-10-0505 October 1987 Special Rept 87-19:on 870920,Zone 110 Fire Protection Components Not Restored to Operable Status within 14 Days Per Tech Specs.Caused by Disabling of Sys to Prevent Actuation During Mod Work.Firewatch Posted.Sys Restored ML20235S2301987-09-22022 September 1987 Special Rept 87-18:on 870907,Zone 80 Fire Suppression Carbon Dioxide Sys Not Restored to Operable Status within 14 Days. Fire Watch Posted within One Hour Per Tech Specs Section 3.14.4.2 ML20235B0681987-09-15015 September 1987 Special Rept 87-17:on 870824,diesel Drive Fire Pump P-996 Inoperable for Over 7 Days,Per Tech Spec 3.14.2.2.Pump P-996 Restored to Operable Status on 870904 Following Bearing Replacement & Satisfactory Surveillance Testing ML20235J6241987-09-15015 September 1987 Special Rept 87-16,providing Updated List of Nonfunctional Barriers Not Restored to Functional Status within 7 Days. Revised Forecast Dates for Completion of Required Significant Engineering Work for Listed Penetrations Stated ML20238B6381987-08-21021 August 1987 Special Rept 87-15:on 870625,listed Carbon Dioxide Zones Inoperable.Caused by Sys Isolation at Sys Manual Isolation Valve.Fire Watch Established for Listed Inoperable Sys in Accordance W/Tech Spec 3.14.4.2 ML20237F8581987-08-18018 August 1987 Special Rept 87-14:providing Updated List of Nonfunctional Fire Doors Which Have Not Been Restored to Functional Status within 7 Days.Since Issuance of Special Rept 87-13,83 Breaches Repaired & 62 New Breaches Added to List ML20236M8481987-07-15015 July 1987 Special Rept 87-13 Re Nonfunctional Fire Barriers Which Have Not Been Restored to Functional Status within 7 Days.Util Evaluated Each Nonfunctional Fire Barrier Against Tech Spec Requirements & Verified That Proper Fire Watch Established 1990-07-16
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML20211H7921999-08-13013 August 1999 Safety Evaluation Supporting Amend 126 to License DPR-54 ML20195D1901999-05-0606 May 1999 Annual Rept ML20195H8571998-12-31031 December 1998 1998 Annual Rept for Smud. with ML20155D4801998-10-27027 October 1998 Amend 3 to Rancho Seco DSAR, Representing Updated Licensing Basis for Operation of Permanently Shutdown & Defueled Rancho Seco Nuclear Facility During Permanently Defueled Mode ML20248C4301998-05-0606 May 1998 Annual Rept, Covering Period 970507-980506 ML20249A7831997-12-31031 December 1997 1997 Smud Annual Rept ML20198G8271997-08-22022 August 1997 Safety Evaluation Supporting Amend 125 to License DPR-54 ML20217D3271997-07-30030 July 1997 Update of 1995 Decommissioning Evaluation for Rancho Seco Nuclear Generating Station ML20140A6371997-05-0606 May 1997 Annual Rept, Covering Period 960507-970506 ML20140G4481997-05-0101 May 1997 Part 21 Rept Re Potential Defect in Component of Dsrv & Dsr Enterprise Standby Diesel Generator Sys.Recommends That Springs Be Inspected on Periodic Basis,Such as During Refueling Outages ML20137W8151997-03-20020 March 1997 Amend 1 to Post Shutdown Decommissioning Activities Rept ML20141J2711996-12-31031 December 1996 Smud 1996 Annual Rept ML20138L1231996-11-13013 November 1996 Smud Rancho Seco Incremental Decommissioning Action Plan, Rev 0,961113 ML20129E7151996-10-14014 October 1996 Defueled SAR for Rancho Seco ML20059H6821994-01-17017 January 1994 Revised Rancho Seco Quality Manual ML20058K3841993-12-0909 December 1993 Part 21 Rept Re Potential Defect in Component of Dsrv & Dsr Enterprise Standby DG Sys,Regarding Potential Problem W/ Subcover Assembled Atop Power Head ML20056E5171993-08-31031 August 1993 Technical Review Rept, Tardy Licensee Actions ML20059K1981993-05-0606 May 1993 Annual Rept, Covering Period from 920501- 930506,consisting of Shutdown Statistics,Narrative Summary of Shutdown Experience & Tabulations of Facility Changes, Tests & Experiments,Per 10CFR50.59(b) ML20128C9641993-02-0202 February 1993 Informs Commission of Status of Open Issues & Progress of Specified Facilities Toward Decommissioning ML20127H2301993-01-15015 January 1993 Part 21 Rept Re Potential Defeat in Component of Dsrv & Dsr Enterprise Standby DG Sys.Starting Air Distributor Housing Assemblies Installed as Replacement Parts at Listed Sites ML20126B0421992-12-17017 December 1992 Final Part 21 Rept Re Potential Problem W/Steel Cylinder Heads.Initially Reported on 921125.Caused by Inadequate Cast Wall Thickness at 3/4-inch-10 Bolt Hole.Stud at Location Indicated on Encl Sketch Should Be Removed ML20125C7161992-12-0707 December 1992 Part 21 Rept Re Possibility for Malfunction of Declutching Mechanisms in SMB/SB-000 & SMB/SB/SBD-00 Actuators. Malfunction Only Occurs During Seismic Event.Balanced Levers May Be Purchased from Vendor.List of Affected Utils Encl ML20127P5861992-11-23023 November 1992 Followup to 921005 Part 21 Rept Re Potential Defect in SB/SBD-1 Housing Cover Screws.Procedure Re Replacement of SBD-1 Spring Cover Bolts Encl.All Fasteners Should Be Loosened & Removed.List of Affected Utils Encl ML20126E6771992-08-0303 August 1992 Rev 7 to Rancho Seco Quality Manual NL-90-451, Monthly Operating Rept for Oct 1990 for Rancho Seco Nuclear Generating Station1990-10-31031 October 1990 Monthly Operating Rept for Oct 1990 for Rancho Seco Nuclear Generating Station ML17348B5061990-10-0909 October 1990 Part 21 Rept Re Zener Diode VR2 on Power Supply Board 9 1682 00 106 Possibly Being Installed Backwards ML20059G9621990-09-10010 September 1990 Safety Evaluation Supporting Amend 115 to License DPR-54 NL-90-443, Monthly Operating Rept for Aug 1990 for Rancho Seco1990-08-31031 August 1990 Monthly Operating Rept for Aug 1990 for Rancho Seco ML20217A5711990-08-28028 August 1990 Final Engineering Rept,Assessment of Spent Fuel Pool Liner Leakage NL-90-439, Monthly Operating Rept for Jul 1990 for Rancho Seco Nuclear Generating Station1990-07-31031 July 1990 Monthly Operating Rept for Jul 1990 for Rancho Seco Nuclear Generating Station ML20055F8591990-07-16016 July 1990 Special Rept 90-11:on 900613,06,25,18,21 & 28,fire Barriers Breached More than 7 Days & Not Made Operable in 14 Days. Corrective Actions:Operability of Fire Detectors Verified on One Side of Breached Barriers NL-90-423, Monthly Operating Rept for June 1990 for Rancho Seco Nuclear Generating Station1990-06-30030 June 1990 Monthly Operating Rept for June 1990 for Rancho Seco Nuclear Generating Station ML20055C6291990-05-21021 May 1990 Special Rept 90-08:on 900419,fire Pump Batteries Inoperable When Surveillance Procedure SP.206 Not Performed by Due Date.Caused by Test Frequency Incorrectly Changed from Weekly to Monthly.Surveillance Schedule Revised ML20055C6301990-05-21021 May 1990 Special Rept 90-09:on 900424,25,30,31 & 0502,fire Barriers Inoperable for More than 7 Days,Per Tech Spec 3.14.6.2 Requirement.Hourly Fire Watches Established & Penetrations & Doors Returned to Operable Status ML20058B6521990-05-0404 May 1990 Rev 0 to ERPT-M0216, Property Loss Study for Rancho Seco Nuclear Generating Station in Long Term Defueled Mode ML20248E0121989-09-13013 September 1989 Supplemental Part 21 Rept Re Potential Problem W/Six Specific Engine Control Devices in Air Start,Lube Oil, Jacket Water & Crankcase Sys.Initially Reported on 890429. California Controls Co Will Redesign Valve Seating NL-89-634, Monthly Operating Rept for Aug 1989 for Rancho Seco Nuclear Generating Station1989-08-31031 August 1989 Monthly Operating Rept for Aug 1989 for Rancho Seco Nuclear Generating Station NL-89-598, Monthly Operating Rept for Jul 1989 for Rancho Seco Nuclear Generating Station1989-07-31031 July 1989 Monthly Operating Rept for Jul 1989 for Rancho Seco Nuclear Generating Station ML20247B3611989-07-17017 July 1989 Safety Evaluation Supporting Amend 112 to License DPR-54 NL-89-556, Monthly Operating Rept for June 1989 for Rancho Seco Nuclear Station1989-06-30030 June 1989 Monthly Operating Rept for June 1989 for Rancho Seco Nuclear Station ML20245E1161989-06-20020 June 1989 Safety Evaluation Supporting Amend 111 to License DPR-54 ML20245B6651989-06-15015 June 1989 Part 21 Rept 150 Re Potential Defect in Component of Dsr Standby Diesel Generator.Cause of Failure Determined to Be Combination of Insufficient Lubrication to Bushings.Listed Course of Action Recommended at Next Scheduled Engine Maint ML20245A1991989-06-0909 June 1989 Safety Evaluation Supporting Amend 110 to License DPR-54 ML20248B9361989-06-0505 June 1989 Safety Evaluation Supporting Amend 107 to License DPR-54 ML20248B6321989-06-0505 June 1989 Safety Evaluation Supporting Amend 108 to License DPR-54 ML20248B9621989-06-0505 June 1989 Safety Evaluation Supporting Amend 109 to License DPR-54 NL-89-517, Monthly Operating Rept for May 1989 for Rancho Seco Nuclear Generating Station1989-05-31031 May 1989 Monthly Operating Rept for May 1989 for Rancho Seco Nuclear Generating Station ML20247P1761989-05-30030 May 1989 Safety Evaluation Accepting Generic Ltr 83-28,Item 4.5.2 Re on-line Testing of Reactor Trip Sys ML20247N7491989-05-30030 May 1989 Special Rept 89-13:on 890328-29,specific Activity of Primary Sys Exceeded Limits in Administrative Procedure & Chemistry Control Commitment.Possibly Caused by Power Reduction.Isotopic Analysis Continued ML20247K7261989-05-23023 May 1989 Safety Evaluation Supporting Amend 105 to License DPR-54 1999-08-13
[Table view] |
Text
..
t7.,i S M U D SACRAMENTO MUNICIPAL UTluTY DISTRICT O 6201 S Street, P.O. Box 15830, Sacramento, CA 95813; (916) 452-3211 AN ELECTRIC SYSTEM SERVING THE HEART OF CALIFORNIA RJR 85-300 June 17, 1985 J B MARTIN, REGIONAL ADMINISTRATOR REGION V 0FFICE OF INSPECTION AND ENFORCEMENT ATTN: DOCUMENT CONTROL DESK U S NUCLEAR REGULATORY COMMISSION WASilINGTON DC 20555 DOCKET No. 50-312 LICENSE NO. DPR-54 SPECIAL REPORT NUMBER 85-07 The Sacramento Municipal Utility District hereby submits Special Report 85-07 in accordance with Rancho Seco Nuclear Generating Station Technical Specification, Sections 3.14.6.2 and 6.9.5.E. This report provides an updated list (attached) of non-functional fire barriers reported in our May 17, 1985 Special Report 85-
.04 and identifies any non-functional fire barriers detected since that report which were not restored to functional status within seven (7) days. It should be noted that the breached barrier list has been modified to reflect the area desig-nations used in the District's updated Fire llazards Analysis.
Ef fective June 14, 1985, the District has committed to meet the applicable re-quirements of 10 CFR 50, Appendix R, or to take the appropriate compensatory action. This commitment will result in reporting additional fire barrier pene-trations which potentially require corrective action to meet Appendix R require-ments. Thus, these fire barriers are considered non-functional for purposes of specifying fire watches and will be included in our next Special Report.
The District has evaluated each non-functional barrier against the requirements of Technical Specification 3.14.6.2 and has verified that the appropriate fire watch has been established.
The District presently has two crews working to reseal non-functional fire barriers. We have completed the walk down for all'of the electrical penetrations and identified fire seals that need to be resealed and/or fixed. We have iden-tified 105 fire doors that need miscellaneous work. We have scheduled to have both the doors and the electrical penetration seals fixed by August, 1985. We still have a six-man crew in the field walking down mechanical penetrations.
Next month's listing will include any new penetrations found.
If-you have any questions concerning this list, please contact Mr. Ron W. Colombo at the Rancho Seco Nuclear Generating Station No. 1.
O B506240297 850617 PDR ADOCK 05000312 S PDR R. J. ODRICUE h ASSISTANT GENERA MANAGER, NUCLEAR s\
cc: Director NRR
'*N g&au *TQ
e
, LIST OF NON FUNCTIONAL FIRE BARRIERS JUNE 17 0 1985 BREACHED BARRIERS (Cable Trays & Floor Slots)
ELEC PEN
- FIRE AREA DETECTOR ZONE ELEC PEN # FIRE AREA DETECTOR ZONE 1-17 AA 1-17 3-13 1-17 AC 1-17 3-13 1-17 AD 1-17 3-13 1-17 AE 1-17 3-13 1-17 AG 1-17 3-13 1-17 M 1-17 4-13 1-17 AL 1-17 4-13 1-17 AQ 1-17 4-13 1-17 AK 1-17 4-13 1-17 80 1-17 4-13 1-17 A0 1-17 4-13 15-71/3 AD 15-71/3 11-10 1-17 88 1-17 4-13 17-31 AK 17-31 13-37 1-17 8F 1-17 4-13 1-17 8K 1-17 4-13 1-17 BL 1-17 4-13 1-17 BN 1-17 4-13 1-17 80 1-17 4-13 1-17 BQ 1-17 4-13 1-17 85 1-17 4-13 1-17 BW 1-17 4-13 1-20 AK 1-20 4-16 1-20 AG 1-20 4-16 15-71/3 A8 15-71/3 11-10 39-50 AA RG1-R81 47-43 17-31 AJ 17-31 13-37 15-16 AA 15-16 11-12 1-17 8X 1-17 3-13 16-17 M 16-17 12-13 1-20 AC 1-20 4-16 17-18 M 17-18 13-14 1-20 AF 1-20 4-16 17-18 AC 17-18 13-14 17-31 AL 17-31 13-37 17-18 AF 17-18 13-14 16-31 AA 16-31 12-37 17-20 AC 17-20 13-16 15-71/2 M 15-71/2 11-10 17-29 AB 17-21 13-19 16-17 A8 16-17 12-13 17-29 AD 17-M1 13-20 16-29 M 16-M1 12-19 18-19 M 18-19 14-15 17-18 A8 17-18 13-14 18-19 AC 18-19 14-15 17-18 AD 17-18 13-14 18-31 AC 18-31 14-37 17-20 A8 17-20 13-16 19-20 AD 19-20 15-16 17-29 M 17-21 13-19 19-20 AF 19-20 15-16 17-29 AC 17-M1 13-19 19-32 AD 19-32 15-38 17-29 AE 17-21 13-19 19-32 AF 19-32 15-38 18-19 A8 18-19 14-15 20-29 AC 20-M1 16-20
r BREACHED BARRIERS (Cable Trays & Floor Slots)
(Continued)
ELEC PEN # FIRE AREA DETECTOR ZONE ELEC PEN # FIRE AREA DETECTOR ZONE 18-31 AE 18-31 14-37 20-29 AF 20-M1 16-20 18-31 AF 18-31 14-37 21-33 AA 21-33 17-39 18-47 AA 18-47 14-46 19-32 AE 19-32 15-38 18-47 AB 18-41 14-46 20-29 A8 20-M1 16-20 19-20 AC 19-20 15-16 20-29 AE 20-M1 16-20 19-20 AE 19-20 15-16 20-32 AA 20-32 16-38 19-32 AC 19-32 15-38 20-29 AA 20-m1 16-20 22-29 AA RGI- M 1 18-20 25-29 AA 25-21 19 27-29 AB 27-m1 20 27-29 AC 27-M1 20 28-29 AA 28-M1 20 20-32 AD 20-32 16-38 29-71/2 A8 M1-71/2 19-10 16-31 AJ 16-31 12-37 31-36 AC 31-36 37-42 31-36 AE 31-36 37-42 31-36 A8 31-36 37-42 33-36 AA 33-36 39-42 32-33 AA 32-33 38-39 34-64 AA RG1-64 42 32-36 AG 32-36 38-42 47-49 AC 47-RBI 46 33-36 A8 33-36 39-43 46-47 AA 46-47 46 47-49 A8 R81-47 46 75/1-77/2 AA 75/1-77/2 75-77 83/1-84/1AA 83/1-84/1 83-84 18-82/A8 18-82 14-82 75/1-81/AA 75/1-81 75-81 76/1-82/A8 76/1-82 76-82 76/1-82/AA 76/1-82 76-82 78/2-82/A8 78/2-82 78-82 85/1-85/4 85/1-85/4 85 85/1-85/4 A8 85/1-85/4 85 85/1-85/4 AA 85/1-85/4 85 85/3-88/A8 85/3-88 85-88 85/3-88/A 85/3-88 85-88 32-36 AA 32-36 38-42
- The following cable tray penetrations were inaccessible for inspection and are considered nonfunctional.
90/1-90/2 90/1-90/2 90 90/1-90/2/A8 90/1-90/2 90 88-90/2/AA 88-90/2 88-90 88-90/2/A8 88-90/2 88-90 85/3-88/AA 85/3-88 85-88 90/1-90/2AA 90/1-90/2 90 19-81/AA 19-81 15-81
BREACHED BARRIERS (Bus Ducts) 0.EC PEN # FIRE AREA DETECTOR ZONE ELEC PEN # FIRE AREA DETECTOR ZONE 3971/1 AD 30-71/1 36-33 30-71/1 AF 30-71/1 36-33 20-32 AB 20-32 16-38 20-32 AC 20-32 16-38 30-31 AC 30-31 36-37 30-31 AE 30-31 36-37 31-32 M 31-32 36-37 17-31 M 17-31 13-37 17-31 AB 17-31 13-37 15-71/3 M 15-71/3 11-10 15-71/3 AC 15-71/3 11-10 30-31 AG 30-31 36-37 30-31 AA 30-31 36-37 30-31 AH 30-31 36-37 30-71/1 AG 30-71/1 36-33 17-31 AM 17-31 13-37 20-05 AC 20-05 16-OS 20-05 AD 20-05 16-05 20-05 AE 20-05 16-05 20-05 AF 20-05 16-05 75/1-83/1 M 75/1-83/1 75-83 76/1-83/1 M 76/1-83/1 76-83 76/1-83/1 A8 76/1-83/1 76-83 75/1-83/1 A8 75/1-83/1 AB 75-83 75/1-05 AA 75/1-05 75 76/1-05 AA 76/1-05 76 s
1
BREACHED BARRIERS (Electrical Penetrations)
ELEC PEN # FIRE AREA DETECTOR IONE ELEC PEN # FIRE AREA DETECTOR IONE 5-25 M Ril-RMI 6-19 32-36 AD 32-36 38-42 1-17 BH 1-17 4-13 32-05 AD 32-05 38 1-17 BJ 1-17 4-13 32-36 AC 32-36 38-42 1-17 AJ 1-17 4-13 32-36 AI 32-36 38-42 1-17 Bx 1-17 3-13 32-05 AB 32-05 38 1-17 AH 1-17 4-13 32-05 AC 32-05 38 17-31 M 17-31 13-37 34-0UTSIDE M RGI-05 42 19-46 M 19-R82 15-46 39-50 M 39-50 43-47 1-20 AH 1-20 4-16 1-20 AJ 1-20 4-16 1-20 AL I-20 4-16 1-20 Al 1-20 4-16 1-20 M 1-20 4-16 31-05 AD 31-05 37 1-20 M 1-20 4-16 31-05 M 31-05 37 1-20 A8 1-20 4-16 31-05 M 31-05 37 31-05 AC 31-05 37
BREACHED BARRIERS (Doors) 000R NLMBER FIRE AREA DETECTOR ZONE 000R NUMBER FIRE AREA DETECTOR ZONE AUB08 18-19 14-15 AU201 67-21 18 AUB12 48-49 47 AU202 RGI-M1 18 AU6061 19-81 15-81 AU203 RG1-M1 18-20 AUB062 18-82 14-81 AU205 28-21 20 AU102 36-RG1 43 AU206 28-72 20 AU103 36-67 43 AU207 27-28 20 AU106 R82-RG1 43 AU208 21-M1 17-20 AU108 36-RG1 36 AU209 21-M1 17-18 Aull) 33-36 39-42 AU210 20-21 16-17 Aull3 32-36 38-42 AU211 20-M1 16-20 Aul14 32-36 38-42 AU212 19-20 15-16 AU115 19-32 15-38 AU213 18-19 14-15 AU116 18-19 14-15 AU214 17-18 13-14 Aull? 31-32 37-38 AU217 15- 21 11-19 AU118 31-36 37-42 AUB06 47-57 48 AU119 18-31 14-37 AUB07 47-56 48 AU120 31-36 37-42 AU328 2-RT1 104-5 AU121 30-36 36-42 AU327 2-RT1 104 AU123 30-71 36-33 AU215 17-m1 13-19 AU124 36-62 42 AU216 16-M1 12-19 AU126 36-RG1 42 AU218 71-21 10-19 AU127 47-RG1 42 AU220 71-m1 10-19 AU128 38-69 41 AU221 71-21 10-19 AU130 36-38 41-42 AU224 62-21 19 AU131 36-71 41-33 AU226 15-71 10-11 AU132 38-71 41-33 AU227 16-17 11-12 AU133 37-71 40-33 AU301 67-RTI 5 AU134 37-69 40 AU333 1-RTI 4-6 AU135 33-36 39-43 AU334 1-RT1 3-6 AU138 30-31 36-37 AU342 71-14 2-6 AU139 36-RG1 42 AU344 6-RTI 6 AU141 R82-RG1 43 AU345 6-RT1 6
b BREACHED BARRIERS (Doors)
(Continued) 000R NWSER FIRE AREA DETECTOR ZONE DOOR NtMBER FIRE AREA DETECTOR ZONE NS063 81-82 81-82 NS359 80-85/2 80-85 NS151 -- -- NS401 83/2-91/1 83-91 NS152 - - NS402 - -
NS153 83/1-83/2 83 NS154 76/1-76/3 76 NS155 76/1-76/2 76 NS156 75/1-75/2 75 NS157 75/1-75/3 75 NS158 75/1-83/1 75-83 NS159 76/1-83/1 76-83 NS160 82-83/1 82-83 NS161 81-83/1 81-83 NS232 82-84/1 82-84 NS233 81-84/1 81-84 NS234 78/1-78/2 78 NS235 77/1-77/2 77 NS238 77/2-84/1 77-84 NS239 84/1-84/2 84 NS240 78/2-84/1 78-84 NS241 84/1-84/3 84 NS242 83/2-84/1 83-84 NS351 -- --
NS352 85/1-87 85-87 NS353 85/1-89 85-89 NS354 85/1-85/3 85 NS355 85/1-85/2 85 NS356 83/2-85/1 83-85 NS357 2-85/4 104-85 NS358 79-85/3 79-85
BREACHED BARRIERS (Mechanical Penetrations)
PENETRATION # FIRE AREA DETECTOR ZONE PENETRATION # FIRE AREA DETECTOR ZONE 2066 (AUX BLDG) M1-RT1 6-20 2112 15-TURB BLDG 11-10 2067 M1-RTI 6-20 2113 15-TURB BLDG 11-10 2068 M1-RG1 20-42 2114 15-TURB BLOG 11-10 No Nwber (10) M1-28 20 2115 15-TURB BLDG 11-10 3075 31-36 37-42 2116 15-TURB BLDG 11-10 2" Pipe Sleewe 38-36 19 2014 M1-RG1 18 3" Pipe Sleeve 38-36 19 2015 M1-RG1 18 Opening with RGI-36 42 2016 M1-RG) 18 Cermic Wool HVAC Duct Not 1-RT1 4-6 2017 M1-RG) 18 Sealed
- 8000 20-21 16-17 2027 M1-67 18
- 8001 20-17 16-13 2028 M1-67 18
- 8002 17-M1 13-19, 20 2029 M1-67 18
- 8003 17-16 13-12 2030 M1-67 18
- 8005 M1-67 18 *8010 M1-RG1 18
- 8006 M1-67 18 2085 M1-TURB BLDG 19-10
- 8007 M1-67 18 2006 M1-TURB BLOG 19-10
- 8008 M1-67 18 2087 M1-TURB BLDG 19-10
- 8009 M1-67 18 2088 M1-TURB BLDG 19-10 2071 20-M1 16-20 2089 M1-TURB BLOG 19-10 2072 17- M1 13-19, 20 2090 M1-TURB BLDG 19-10 2108 15-M1 11-19 2091 M1-TURB BLDG 19-10 2110 15-M1 11-19 2092 M1-TURB BLOG 19-10 2107 15-M1 11-19 2093 M1-TURB BLDG 19-10 2109 15-M1 11-19 2094 M1-TURB BLDG 19-10 2111 15-TURB BLDG 11-10 2095 M1-TURB BLDG 19-10
- Newly identified penetrations (temporary ID No assigned).
BREACHED 8ARRIERS (Mechanical Penetrations)
(Continued)
AUX BLDG PENETRATION # FIRE AREA DETECTOR ZONE PENETRATION # FIRE AREA DETECTOR ZONE 2096 M1-TUR8 BLDG 19-10 Expansion Joint 27-28 20 2097 M1-TUR8 BLDG 19-10 (unsealed) 2098 M1-TUR8 BLDG 19-10 Expansion Joint 56-51 48 2083 M1-TUR8 BLDG 19-10 (unsealed) 2004 M1-TUR8 BLOG 19-10
- 0011 M1-RG3 19 245 84/1-84/3 84
- 8012 M1-RG3 19 305 79-85/3 79-85
- 8013 M1-RG3 19 345 85/1-83/2 85-83
- 8014 M1-RG3 19 339 85/1-85/3 85
- 8015 M1-RG3 19 340 85/1-85/2 85
- 0019 M1-RG3 19 88027 RG1-28 18-20 88028 RG1-28 18-20
- 8029 RGI-28 18-20 2052 M1-27 20 2053 M1-27 20 2054 M1-27 20 2055 M1-27 20 2065 27-RG1 20
- 2068 27-RG1 20 2018 RGI-M1 18 3087 37-71 40-33
- Newly Identified penetrations (temporary 10 No, assigned).
8 REACHED BARRIERS (Fire Depers With Foam or Elastomer in Expansion Clearance)
DMPER NUMBER FIRE AREA DETECTOR ZONE DMPER NUMBER FIRE AREA DETECTOR ZONE FD-1 (Aux Bldg) 1-2 4-104 FD-12 RT1-72 7 FD-2 1-2 4-104 FD-43 Ril-RG1 5 FD-3 1-2 4-104 FD-21 (NSEB) 77/2-78/2 77-78 FD-4 1-2 4-104 FD-27 (NSEB) 77/2-84/2 77-84 FD-5 1-2 4-104 FD-34 (NSEB) 78/2-84/3 78-84 FD-6 1-2 4-104 FD-13 (NSEB) 76/1-85/5 76-85 FD-7 1-2 4-104 FD-26 (NSE8) 84/2 84 FD-8 1-2 4-104 FD-28 (NSEB) 84/1-84/3 84 FD-18 15-RMI 11-19 FD-29 (NSEB) 84/3-84/1 84 FD-21 14-31 13-37 FD-24 (NSE8) 87-84/2 87-84 FS-22 32-20 16-38 FD-31 (NSEB) 88-84/3 88-84 FD-23 34-36 42 FD-25 47-48 46-47 FD-26 57-R81 48 FD-28 R81-RB2 47 FD-29 49-56 47-48 FD-30 49-57 47-48 FD-41 56-47 47-48 FD-42 RT1-RG1 5 F D-46 Ril-RG1 5 FD-47 RT1-RG1 5 FD-48 Ril-RG1 5 FD-34 78/2-84/3 78-84 Motor Operated 16/17 Depers A,8,C in East Wall of FA 16 Motor Operated 21/20 Dampers D.E.F in West Wall of FA 21
. c W
8 REACHED BARRIERS
/
(Fire Dagwrs) l LUG # FIRE AREA DETECTOR ZONE 1 14-6' 6 2
RT1-6 j 6 3 RT1-6 6 4 Ril-27 7-20 5 Ril-27 7-20 6 6-00TSIDE 6.
7 27-28 20 8 mi-RG) 18 9 RG1-R82 43-46 -
~
10 28-RG1 20-42 11 70-47 42-46 12 37-38 40-41 13 R81-R82 46 14 47-R82 46 15 R82-RG1 46-43 -
4 16 47-R81 46-48 17 - -
18 RTI-RG1 5 19 27-00151DE 19 20 28-0UT510E 20 21 28-M1 20 22 47-0UISIDE 42 23 47-RG1 42 ,
l 24 47-R82 46 25 41-R82 46 28 Ril-001510E 42 29 Ril-00151DE 42 32 RGI-36 43 33 27-RMI 18 34 RGI-Mi 18 i
8 REACHED 8AERIERS f
(Fire Dampers)
(Continued)
FIRE AREA DETECTOR ZONE 35 RGI-36 43 36 RG1-36 43 Duct Pen WNo RT1-27 6-20 Fire Desper 10*x4" $ L&9.8 Duct Pen WNo 2744 20-42 Fire Desper 10*m4" 9 L49.8 I
I i
,