Amend 67 to License DPR-65,allowing Credit for Automatic Testing of Engineered Safety Feature Actuations Sys Instrumentation
ML20126H685
Person / Time
Site: Millstone 
(DPR-65-A-067, DPR-65-A-67)
Issue date: 04/09/1981
From: Clark R
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20126H683 List:
References
NUDOCS 8104200059
Download: ML20126H685 (5)


Text

pn **c v

f, k

UNIT ED STATES y7

[' i NUCLEAR REGULATORY COMMISSION g

9.4

. 5 C

WASHINGTON D, C. 20555

./

'e,

    • [

r PORTHEAST NUCLEAR ENERGY COMPANY THE CONNECTICUT LIGHT Al'D POWER COMPANY THE HARTFORD ELECTRIC LIGHT COMPANY THE WESTERN MASSACHUSETTS ELECTRIC COMPANY DOCKET NO. 50-336 MILLSTONE NUCLEAR POWER STATION, UNIT NO. 2 AMENDMENT TO FACILITY OP"rATillG LICENSE Amendment No. 67 License No. DPR-65 1.

The Nuclear Regulatory Conmission (the Comntssion) has found that:

A.

The aopliption for amendment by llortheast Nuclear Energy Company (the licensee) dated December 27, 1976, as supplemented by letters dated July 27, 1977, J anuary 16, 1979 and October 31,19P0, complies with the standards and requirements of the Atonic Energy Act of 1954, as anended (the /ct) and the Connission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in confor.oity with the application, the provisions of the Act, and the rules and regulations of the Conmission; C.

There is reasonable assurance (i) that the activities authorized by this a andnent can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuan:e of this amendment vill not be inimical to the common defense and security or to the health cad safety of the public; and E.

lhe issuance of this asentrent is in accordence with 10 CFR Pcrt El of the Con,issian's regJlatiODs and all appliCnhle reOuire" Ents h /c N cn sr.H sfi M.

s10420e O@

l

. 2.

Accordingly, the license is amen ed by changes to the Technical d

Specifications as indicated in the attachment to this license a~.endment, and peragraph 2.C.(2) of Facility Operating License Ho. OPR-65 is hereby amended to read as follows:

(2) Technical Specifications The Technical Specifications contained in Appendices A and B,'as revised through Anendment No. 67. are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendraent is effective as af the date of its issuance.

FOR THE UUCLLAR REGULATORY C0ti!11SS104

..L

. t is R. A. Clark, Chief Operating Reactors Branch #3 Division of Licensing

Attachment:

Chang.cs 'to the Technical Specifications Date of Issut.nce:

April 9, 1981

J

-)

ATi: HitENT TO LICEt!SE Af END! TENT ll0. 67 FACILITY OPERATilG LICENSE !!0. DPR-65 DOCKET NO 50-336 Replace the following pace of the Appendix A Technical Specifications wit.1 the enclosed page. The revised page is identified by Amendnent number and contains vertical lines indicating the area of change. The corresponding overleaf page is also provided to maintain document completeness.

Pages 3/4 3-25 0

0:

l TABLE 4_._3-21Conti_nuedj.

T/1 J. E l 0TATIC 'i C

l l

'~ t 3 oincident logi cire.uits shall be tested automatin.lly cc ally at least once per il days. The automatic t.se feature c c ceri fled CPERABLE at least once per 31 days.

m ww-

,.m---w,.,e-w-wwy--,

w

--wmy-,*w-->

w a-warw-y--r"--a y-y-w-v e-

t If1STRU"ENTATION 3/ 4. 3. 3 MONITORING lilSTRUf1ENTATION RADI ATION f'.0MITORIfiG LIMITIf;G CONDITION FOR OPERATION 3.3.3.1 The radiation monitoring instrumentation channels shown in Table 3.3-6 shall be OPERABLE with their alarm /+ rip setpoints within the specified limits.

APPLICABILITY: As shown in Table 3.3-6.

ACTION:

a.

With a radiation monitoring channel alarm / trip setpoint ex-ceeding the value shown in Table 3.3-6, adjust the setpoint to within the limit within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or declare the channel in-operable.

b.

With one or more radiation monitoring channels inoperable, take the ACT10f1 shown in Table 3.3-6.

The provisions of Speci-fications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REOUIRE!'ENTS 4.3.3.1 Each radiation monitoring instrumentation channel shall be demonstrated OPERAELE by the performance of the CHAl1NEL CHECK, CHANT 1EL CALIBRAT10:1 and CHA!4t;EL FUtiCT10NAL TEST operations during the modes and at the frequencies shown in Table 4.3-3.

l

l c_.