Southem California Edison Company 33 PAnnt m STREt T D con er 3 92

,'l',((!l' i

U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C.

20555 Gentlemen:

Subject:

Docket Nos. 50-361 and 50-362 i

Amendment Application Nos. 127 and 111 Changes to Technical Specification 3.3.3.1, " RADIATION MONITORING," San Onofre Nuclear Generating Station Units 2 and 3 Enclosed are Amendment Application Nos. 127 and 111 to facility Operating Licenses NPF-10 and NPF-15 for San Onofre Units 2 and 3, respectively.

These amendment applications consist of Proposed Change Number (PCN) 416.

PCN-416 is a request to revise Units 2 and 3 Technical Specification (TS) 3.3.3.1,

" RADIATION HONITORING." This amendment request increases the required number of )lant vent stack wide range noble gas radiation monitors from 1 to 2 when eitler Unit 2 or 3 is in Mode 1, 2, or 3.

When either Unit 2 or 3 is in Mode 4 and the other unit is in Mode 4, 5, or 6, either the plant vent stack monitor (2/3RT-7808) or both wide range gas monitors (2RT-7865-1 and 3RT-7865-

1) will be required. Editorial clarifications are also made.

if you would like additional information on this Technical Specification change request, please let me know.

Sincerely, d'

cc:

J. B. Hartin, Regional Administrator, NRC Region V C. W. Caldwell, NRC Senior Resident inspector, San Onofre Units 1, 2&3 H. B. Fields, NRC Project Manager, San Onofre Units 2 and 3 H. Kocol, California Department of Health Services 310033 0

9; 9212310144 921230 l

PDR ADOCK 05000361 g

.P PDR