Safety Evaluation Supporting Util Response to Generic Ltr 83-28,Items 3.1.1,3.1.2,3.2.1,3.2.2 & 4.5.1 Re post-maint Testing Verification
ML20126F456
Person / Time
Site: Quad Cities  
Issue date: 05/31/1985
From:
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20126F387 List:
References
GL-83-28, NUDOCS 8506170482
Download: ML20126F456 (2)


Text

'

'f Uh p

4 UNITED STATES g

NUCLEAR REGULATORY COMMISSION

,9 WASHINGTON, D. C. 20555 L

SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULA: ION RELATED TO LICENSEE RESPONSE TO GENERIC LETTER N0. 83-28 COMMONWEALTH EDISON COMPANY AND IOWA-ILLIN0IS GAS ANU ELECTRIC COMPANY QUAD CITIES STATION, UNITS 1 AND 2 DOCKET NOS. 50-254/265

1.0 INTRODUCTION

Background Information m

L._ -

_. Subsequent to the anticipated transient without scram (ATWS) events at the Salem Nuclear Power Plant, the Comission reviewed intermediate term actions to be taken by the licensees. The actions taken were developed on the basis of information contained in NUREG-1000, " Generic Implications of ATWS Events at the Salem Nuclear Power Plant." On July 8, 1983, Generic Letter (GL) No. 83-28 was issued by NRR. The letter identified NRC positions developed from review of the Salem ATWS events. These positions are related to reactor trip system reliability and general management capability. The specific GL 83-28 items covered by the Safety Evaluation are Sections 3.1.1 and 3.1.2, " Post-Maintenance Testing (RTS Components);" 3.2.1 and 3.P.2,

" Post-Maintenance Testino (All Other Safety-Related Components);" and 4.5.1,"RTSReliability(SystemFunctionalTestDescription)."

Licensee's Response to Generic letter (GL) No. 83-28 By letters dated November 5, 1983, and June 1, 1984, Commonwealth Edison Company responded to specific items of GL 83-28. The licensee swviarized the results of the requested review and concluded that all items have been appropriately addressed.

Scope of Review The staff's review consisted of an evaluation of the response to determire if the requirements of GL 83-28 had been satisfied. The evaluetion for each of the items is given below.

2.0 EVALUATION Items 3.1.1 and 3.1.2, " Post-Maintenanco Testing (RTS Components)

The review criteria for these items require that the licensee submit a statement indicating that he has reviewed plant test and maintenance procedures and Technical Specifications to ensure that post-maintenance 8506170482 850531 PDR ADOCK 05000254 P

PDR

. operability testing of safety-related components in the reactor trip system is required. Also, the licensee's statement should contain a verification that vendor-recommended test guidance has been reviewed, evaluated, and where appropriate, included in the test and maintenance procedures or the Technical Specifications. The staff has evaluated the licensee's November 5,1983 submittal for this item and has determined it to be adequate in content.

Items 3.2.1 and 3.2.2, "Pc ct-Maintenance Testing (All Other Safety-Related Components)

The review criteria for these items require that the licensee submit a statement indicating that he has reviewed plant test and maintenance procedures and Technical Specifications to ensure that post-maintenance operability testing of all safety-related components is required. Also, a 4

statement is required that contains a verification that vendor-recommended test guidance be reviewed, evaluated, and where appropriate, included in

_the test and maintenance procedures or the Technical Specifications. The staff has evaluated the licensee's November 5,1983 submittal for this item and has determined it to be adequate in content.

Item 4.5.1, "RTS Reliability (System Functional Test Description)

The review criteria for this item requires that the licensee submit a statement committing to independent, on-line functional testing of the diverse trip features. The staff has evaluated the licensee's November 5, 1983 and June 1,1984 submittals for this item and has determined them to be adequate in content.

3.0 CONCLUSION

The staff concludes that the programs outlined in the licensee's submittals adequately. address the requirements of Generic Letter No. 83-28 for the areas specified in this Safety Evaluation, w

Principal Contributor:

T. E. Taylor Dated:

May 31, 1985

.