APPENDIX A
b
h1
!
L
NOTICE OF DEVIATION
I
.-
,
. Gulf States Utilities
Docket:
50-458/85-18
River Bend Station
Permit:
Based on the results of an NRC inspection conducted during the period of
February 25 - May 3, 1985, and in-accordance with NRC Enforcement Policy
(10 CFR Part 2, Appendix C), 49 FR 8583, dated March 8, 1984, the following-
deviation was identified.
s
"
'
. Safety-Related Display Instrumentation Ranges
,
. '.
Table 7.5-1 of the River Bend Station FSAR (Amendment 11, dated January
1984) states that the ranges of instrumentation for. Low Pressure Core
,
,
- Spray (LPCS) flow and Residual Heat Removal (RHR) service water flow
~
'
-
'should be 0-8,000 gpm and 0-10,000 gpm, respectively.
s.
..,
-
In' deviation'from the above, the actual ranges for the above
"
'
instrumentation were 0-7,000 gpm and 0-8,000 gpm, respectively.
(458/8518-01)
.
-
a
Pursuant to the provisions of 10 CFR 2.201, Gulf States Utilities is'hereby
reques'ted to submit to this office, within 30 days of the date of this Notice
- of. Deviation, a written statement or. explanation in reply, including:
(1) the
corrective steps which have been taken and the results achieved;'(2) corrective
steps which will be taken to avoid further deviation from commitments made to
the Commission; and (3) the date when full compliance will be achieved.
Consideration may be given to extending your response time for good cause.
shown.
.
Dated:
.