Text
_
/
4*%
UNITED STATES E
NUCLEAR REGULATORY COMMISSION 3
p WASHINGTON, D. C. 20555
~s.,...../
ALABAMA POWER COMPANY DOCKET NO. 50-348 JOSEPH M. FARLEY NUCLEAR PLANT, UNIT NO. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 58 License No. NPF-2 1.
The Nuclear Reg.,latory Comission (the Comission) has found that:
A.
The application for amendment by Alabama Power Company (the licensee) dated April 20, 1984, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, as amended, the provisions of the Act, and the regulations of the Comission; C.
There is reasonable assurance: (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.
The issuance of this license amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-2 is hereby amended to read as follows:
8505150496 850502 DR ADOCK 0500 8
. (2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 58, are hereby incorporated in the license.
The licensee shall operate the facility in accordance with the Technical Specifications.
3.
This license amendment is effective as of its date of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION
/241G4A.
f F
teven A. VargiI, Operating Reactors nch #1 Division of Licensi
Attachment:
Changes to the Technical Specifications Date of Issuance: May 2, 1985 h
ATTACHMENT TO LICENSE AMENDMENT AMENDMENT NO. 58 FACILITY OPERATING LICENSE N0. NPF-2 DOCKET N0. 50-348 Revised Appendix A as follows:
Remove Pages Insert Pages 3/4 4-28 3/4 4-28 3/4 4-29 3/4 4-29 3/4 4-30 3/4 4-30 8 3/4 4-7 8 3/4 4-7 8 3/4 4-8 8 3/4 4-8 8 3/4 4-9 B 3/4 4-9 6-25 None*
Page was page 6-27 but was removed by Amendment No. 33 dated October 14, 1983.
o w
w y_w-
,.-.-e.-
m m
ww a
w-w em
-w,-
w
TABLE 4.4-5 REACTOR VESSEL MATERIAL SURVEILLANCE PROGRAM-WITHDRAWAL SCHEDULE VESSEL LEAD WITHDRAWAL CAPSULE LOCATION FACTOR TIME Y
343' 3.12 Removed 1.13 EFPY U
107' 3.12 Removed 3.02 EFPY X
287*
3.12 6 EFPY W
110*
2.70 12 EFPY Y
290' 2.70 21 EFPY Z
340' 2.70 Standby FARLEY - UNIT 1 3/4 4-28 AMENDMENT NO. 58
't I[ MATERIAL PROPERTY BASIS, CONTROLLING M ATERIAL: WELD METAf.
COPPER CONTENT: 0.2 ' IVT'i PHOSPHORUS CONTENT: U.0M WT%
RT 0
NDT INITIAL: 0 F RTNOT AFTER 7 EFPY: 1/4T 3/4T,,1850F 87'F CURVE APPLICABLE FOR HEATUP RATES UP TO 60*F/HR FOR THE SERVICE PERIOD UP TO 7 EFPY AND CONTAINS ACCEPTABLE 3000 MARGINS OF 10'F AND 60 PSIG FOR REGION FOR POSSIBLE INSTRUMENT ERRORS NYDR0 STATIC TESTING OPERATIONS s
g LEAK TEST LIMIT E
E 2000 UNACCEPTABLE a.
OPERATION S'
4o I
5 HEATUP RATES S ACCEPTABLE E
UP TO 600F/HR OPERATION p CRITICALITY LIMIT P BASED ON INSERVICE HYDROSTATIC TEST TEMPERATURE i
0 (325 F) FOR THE -
SERVICE PERIOD UP TO 7,.EFPY 0
0 100 200 300 400 500 v,
INDICATED TEMPERATURE (*F) 7 l
" Di Figure 3,4-2 Farley Unit I-Reactor Coolant System Heatup Limitations Applicable For The First 7 EFPY FARLEY-UNIT 1 3/4 4-29 AMENDMENT NO. 58
MATERIAL PROPERTY GASIS CONTROLLING MATERIAL: WELD METAL COPPER CONTENT: 0.24 WT%
PHOSPHORUS CONTENT: 0.011 WT%
1 RTNDT INITIAL:0 F 0
_ RTNDT AFTER,7 EFPY: 1/47,1850F _
3/4T 87'F CURVE APPLICA8LE FOR COOLD,OWN I
RATES UP TO 1000F/HR FOR THE SERVICE '
PERIOD UP TO' 7 MARGINS OF 10*F AND 60 PSIG FOREFPY AND CO POSSIBLE INSTRUMENT ERRORS 2%0 o
k Es N
' UNACCEPTABLE '
E OPERATIOi' --
i 8
f b5 5
1000 -
ACCEPTABLE DPERATION COOLDOWN RATES #F/HR en
)
20 -
y 40 ' s 60
===""
100 0
0 100' 200 300 400 INDICATED TEMPERATURE (*F)
Figure 3.4 3Farley Unit 1 Reactor Coolant System Coo)down Limitations Applicable For The First 7 EFPY 4
I FARLEY-UNIT 1 3/4*4-30 AMENOMENT NO. 58
.e,--
e
-,,.---m.
.-%-,,,,w.
--.---w.,e,
f REACTOR COOLANT SYSTEM BASES
- 4) The pressurizer heatup and cooldown rates shall not exceed 100*F/hr and 200*F/hr respectively..The spray shall not be used if the temperature difference between the pressurizer and the spray fluid is greater than 320*F.
i
- 5) System preservice hydrotests and in-service leak and hydrotests shall be performed at pressures in accordance with the requirements of ASME Boiler and Pressure Vessel Code,Section XI.
The fracture toughness properties of the 'ferritic materials in the reactor vessel.are determined in accordance with ASTM E185-82 and in accordance with additional reactor vessel requirements. These properties are then evaluated in accordance with Appendix G of the 1976 Summer Addenda Jto Section III of the ASME Boiler and Pressure Yessel Code and the calculation methods described in WCAP-7924-A, " Basis for Heatup and Cooldown Limit Curves, April 1975."
Heatup and coolonwn limit curves are calculated using the most limiting value of the nil-ductility reference temperature, RTndt, at the end of 7 effective full power years of service life. The 7 EFPY service life period is chosen such that the limiting RTndt at the 1/4T location in the core region is greater than the RTndt of the limiting unirradiated material. The selection of such a limiting RTndt assures that all components in the Reactor Coolant System will be operated conservatively in accordance with applicable Code requirements.
The reactor vessel materials have been tested to determine their initial RTndt; the results of these tests are shown in Table B 3/4.4-1. Reactor operation and resultant-fast neutron (E greater than 1 MEV) irradiation can cause an increase in the RTndt. Therefore, an adjusted reference temperature, based upon the fluence and copper content of'the material in question, can be predicted using Figure B 3/4.4-1 and the recommendations of Regulatory Guide 1.99, Revision 1, " Effects of Residual Elements on Predicted Radiation Damage to Reactor Yessel Materials." The heatup and cooldown limit curves of Figures 3.4-2 and 3.4-3 include predicted 4
adjustments for this shift in RTndt at the end of 7 EFPY (as well as adjustments for possible errors in the pressure and temperature sensing instruments).
k J
FARLEY - UNIT 1 B 3/4 4-7 AMENDMENT NO. 58 4
,,_.r w.
,.r-m m.
,.,.y-,.,
~,, _, _..
... -,, -. ~,,,,.
. -... -..,, _., _ _. -,, -.. ~. - ~......
BASES Values of ARTndt determined in this manner may be used until the results from the material surveillance program, evaluated according to ASTM E185-82, are available.
Capsules will be removed in accordance with the requirements of ASTM E185-82 and 10CFR50, Appendix H.
The surveillance specimen withdrawal schedule is shown in Table 4.4-5.
The heatup and cooldown curves must be recalculated when theowRT determined from the surveillance capsule exceeds the calculated ARTndt ndt for the equivalent capsule radiation exposure.
Allowable pressure-temperature relationships for various heatup and cooldown rates are calculated using methods derived from Appendix G in Section III of the ASME Boiler and Pressure Vessel Code as required by Appendix G to 10CFR Part 50 and these methods are discussed in detail in WCAP-7924-A.
The general method for calculating heatup and cooldown limit curves is based upon the principles of the linear elastic fracture mechanics.
(LEFM) technology.
In the calculation procedures a semi-elliptical surface defect with a depth of one-quarter of the wall thickness T,
and a length of 3/2T is assumed to exist at the inside of the vessel wall as well as at the outside of the vessel wall. The dimensions of this postulated crack, referred to in Appendix G of ASME Section III as the reference flaw, amply exceed the current capabilities of inservice inspection techniques. Therefore, the reactor operation limit curves developed for this reference crack are conservative and provide sufficient safety margins for protection against non-ductile failure.
To assure that the radiation embrittlement effects are accounted for in the calculation of the limit curves, the most limiting value of the nil ductility reference temperature, RTndt, is used and this includes the radiation induced shift, ART for which heatup and cooldown curves are generated.ndt, corresponding to the FARLEY
, WIT 1 B 3/4 4-8 AMENDMENT NO.
58
....~~.-......-..__-.,_,--~.-___...-.,--,....-.,.-_m._,.
. -. ~. _ _ _ _ _ _., _. -.
---e---
TABLE B 3/4.4-1 n
REACTOR VESSEL TOUGHNESS DATA y
Material Cu P
T MWD NMWD RT Upper Shelf Energy NOT NDT j
Component Code No.
Type
(%)
_(%)
{*F1 M
- F
{*FJ MWO NMWO Z
Closure head done B6901 A533B, C1.1 0.16 0.009
-30 20 40
-20 140 a)
Closure head segment 86902-1 A533B, C1.1 0.17 0.007
-20
-10 10(a)
-20 138-Closure head flange B6915.1 A508, C1.2 0.10 0.012 60(a) -20 0(a) 60 I
75 *)
Vessel flange B6913-1 A508, C1.2 0.17 0.011 60(a) -30
-10(a) 60 106(a)
Inlet nozzle B6917-1 A508, C1.2 0.010 60(*)
45 60 110 Inlet nozzle B6917-2 A508, C1.2 0.008 60(a) 115 60 80 Inlet nozzle B6917-3 A508, C1.2 0.008 60(a) 35 60 98 Outlet nozzle B6916-1 A508, C1.2 0.007 60(a) 60 60 96.5 Outlet nozzle B6916-2 A508, C1.2 0.011 60(a) 30 60 97.5 w
Outlet nozzle B6916-3 A508, C1.2 0.009 60(a) 50 60 100 Nozzle shell B6914-1 A508, C1.2 0.010 30 70 90(a) 30 148 a
'4 Inter. shell B6903-2 A533B, C1.1 0.13 0.011 0
-25 40 0
151.5 97 Inter. shell B6903-3 A533B, Cl.1 0.12 0.014 10 5
52 10 134.5 100 Lower shell B6919-1 A533B, C1.1 0.14 0.015
-20
-5 75 15 133 90.5 Lower shell B6919-2 A533B, Cl.1 0.14 0.015
-10 0
65 5
134 97 Bottom head ring B6912-1 A508, C1.1 0.010 10
-25
-5(a) 10 163.5 g
Bottom head segment B6906-1 A533B., C1.1 0.15 0.011
-30
-50
-30(a)
-30 147 E
Bottom head dome B6907-1 A533B, C1.1 0.17 0.014
-30
-10
-10(a)
-30 143.5 Inter. shell long.
0.27 0.015 0(a)
<60 0
H weld seams h
Inter. 10 lower shell 0.24 0.011 0(a) weld seam
<60 0
E Lower shell long.
0.17 0.022 0(a)
<60 0
weld seam
(*) Estimated per NRC Regulatory Standard Review Plan, section 5.3.2.
MWD - Major Working Direction NMWD - Normal to Major Working Direction
-