ML20117D061

From kanterella
Jump to navigation Jump to search
Unit One Maximum Doses Resulting from Aquatic Effluents Period of Release 950101-1231
ML20117D061
Person / Time
Site: Braidwood  
Issue date: 12/31/1995
From:
COMMONWEALTH EDISON CO.
To:
Shared Package
ML20117C657 List:
References
NUDOCS 9608280163
Download: ML20117D061 (5)


Text

REVISED TABLE 3.2-1 BRAIDWOOD STATION UNIT ONE ACTUAL 1995 MAXIMUM DOSES (MREM) RESULTING FROM AQUATIC EFFLUENTS PERIOD OF RELEASE - 01/01/95 TO 12/31/95 CALCULATED 08/19/96 ADULT RECEPTOR 1ST 2ND 3RD 4TH DOSE TYPE QUARTER QUARTER QUARTER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC TOTAL 1.34E-02 1.24E-02 1.39E-02 8.65E-03 4.84E-02 BODY INTERNAL 1.68E-02 1.25E-02 1.54E-02 1.78E-02 5.93E-02 i

ORGAN LIVER Gl_LLI LIVER GI_LLI Gl_LLI i

THIS IS A REPORT FOR THE CALENDAR YEAR 1995 COMPLIANCE STATUS - 10 CFR 50 APP, I


 % OF APP 1. ------------

1 QTRLY IST QTR 2ND OTR 3RD OTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I TOTAL BODY (MREM) 1.5 0.90 0.83 0.93 0.58 3.0 1.61 CRIT. ORGAN (MREM) 5.0 0.34 0.25 0.31 0.36 10.0 0.59 LIVER GI_LLI LIVER GI_LLI GI_LLI RESULTS BASED UPON:

ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995 IO8$00hkOIO$$056 R

PDR

r l

l REVISED TABLE 3.2-1 (Continued)

BRAIDWOOD STATION UNIT TWO ACTUAL 1995 MAXIMUM DOSES (MREM) RESULTING FROM AQUATIC EFFLUENTS PERIOD OF RELEASE - 01/01/95 TO 12/31/95 CALCULATED 08/19/96 ADULT RECEPT 0R l

1ST 2ND 3RD 4TH I

DOSE TYPE QUARTER QUARTER QUARTER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC TOTAL 1.34E-02 1.24E-02 1.39E-02 8.65E-03 4.84E-02 BODY INTERNAL 1.68E-02 1.25E-02 1.54E-02 1.78E-02 5.93E-02 ORGAN LIVER GI_LLI LIVER GI_LLI GI_LLI THIS IS A REPORT FOR THE CALENDAR YEAR 1995 COMPLIANCE STATUS - 10 CFR 50 APP. I

____________ % OF APP I. ------------

OTRLY 1ST OTR 2ND OTR 3RD OTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I TOTAL BODY (MREM) 1.5 0.90 0.83 0.93 0.58 3.0 1.61 CRIT. ORGAN (MREM) 5.0 0.34 0.25 0.31 0.36 10.0 0.59 LIVER GI_LLI LIVER GI_LLI GI_LLI RESULTS BASED UPON:

ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995

REVISED TABLE 3.3 1 i

BRAIDWOOD STATION UNIT ONE 10 CFR 20 COMPLIANCE ASSESSMENT PERIOD OF ASSESSMENT 01/01/95 TO 12/31/95 CALCULATED 08/19/96 1

1.

10 CFR 20.1301 (a)(1) Compliance Total Effective Dose Egivalent. mrem /yr 3.49E-02 l

10 CFR 20.1301 (a)(1) limit mrem /yr 100.0

% of limit 0.03 Compliance Summary - 10CFR20 1st 2nd 3rd 4th

% of Otr Qtr Otr Otr Limit TEDE 9.18E-03 7.79E-03 9.60E-03 8.35E-03 0.03 RESULTS BASED UPON:

ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995 I

i l

r

~

REVISED TABLE 3.3-1 (Continued)

BRAIDWOOD STATION UNIT TWO

~

10 CFR 20 COMPLIANCE ASSESSMENT PERIOD OF ASSESSMENT 01/01/95 TO 12/31/95 CALCULATED 08/19/96 1.

10 CFR 20.1301 (a)(1) Compliance Total Effective Dose Eqivalent, mrem /yr 4.65E-02 l

10 CFR 20.1301 (a)(1) limit mrem /yr 100.0 l

% of limit 0.05 l

l Compliance Summary - 10CFR20 1st 2nd 3rd 4th

% of Otr Otr Otr Otr Limit l

TEDE 9.32E-03 7.76E-03 1.44E-02 1.50E-02 0.05 l

RESULTS BASED UPON:

ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995 l

l l

i I

i

Revised Section 3.2 Liquid Effluent Pathways 1994.

The three principal pathways through the aquatic environment for potential doses to man from liquid waste are the ingestion of potable water, eating aquatic foods, and j

exposure while walking on the shoreline. Not all of these pathways are significant or applicable at a given time or station but a reasonable approximation of the dose can be made by adjusting the dose formula for season of the year or type and degree of use of the aquatic environment. NRC developed equations

  • were used to calculate the doses to the whole body, lower GI tracts, thyroid, bone, skin; specific parameters for use in the equations are given in the Comed Offsite Dose Calculation Manual. The j

maximum whole body dose for the year was 4.16E-02 mrem and no organ dose exceeded 5.02E-02 mrem (Table 3.2-1).

1995

- The three principal pathways through the aquatic environment for potential doses to man from liquid waste are the ingestion of potable water, eating aquatic foods, and exposure while walking on the shoreline. Not all of these pathways are significant or applicable at a given time or station but a reasonable approximation of the dose can be made by adjusting the dose formula for season of the year or type and degree of use of the aquatic environment. NRC developed equations

  • were used to calculate the J

doses to the whole body, lower GI tracts, thyroid, bone, skin; specific parameters for

]

use in the equations are given in the Comed Offsite Dose Calculation Manual. The j

maximum whole body dose for the year was 4.84E-02 mrem and no organ dose exceeded 5.93E-02 mrem (Table 3.2-1).

j

k Vwalth*winerrata. doc r

-