Part 21 & Deficiency Rept SSH-M-85/01 Re Defective Circuit Breakers for Recombiners Supplied by Rockwell Intl.Initially Reported on 841124.Equipment Deficiencies Corrected Prior to Installation.Rockwell Intl Requested to Follow Up ActionML20116N614 |
Person / Time |
---|
Site: |
Monticello |
---|
Issue date: |
05/03/1985 |
---|
From: |
Musolf D NORTHERN STATES POWER CO. |
---|
To: |
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE) |
---|
References |
---|
REF-PT21-85, REF-PT21-85-195-000 PT21-85-195, PT21-85-195-000, SSH-M-85-01, SSH-M-85-1, NUDOCS 8505070286 |
Download: ML20116N614 (3) |
|
|
---|
Category:DEFICIENCY REPORTS (PER 10CFR50.55E & PART 21)
MONTHYEARML20140A4761997-05-27027 May 1997 Provides Addl Info to 970429 Part 21 Rept Re Potential safety-related Problem W/Asco HV 266000-007J Scram Solenoid Pilot Valves.Corrective Actions Also Listed ML20059H7721994-01-17017 January 1994 Part 21 Rept Re Virginia Power Notifying Fairbands Morse Via Failure Analysis Rept NESML-Q-058 of Defective Air Start Distributor cam,16104412 ML20059F2631994-01-0707 January 1994 Part 21 Rept Re Air Start Distributor Cam Mfg by Fairbanks Morse.Mfg Suggests That Site Referenced in Encl App I Inspect Air Start Distributor Cam as Soon as Practical ML20125C7161992-12-0707 December 1992 Part 21 Rept Re Possibility for Malfunction of Declutching Mechanisms in SMB/SB-000 & SMB/SB/SBD-00 Actuators. Malfunction Only Occurs During Seismic Event.Balanced Levers May Be Purchased from Vendor.List of Affected Utils Encl ML20127P5861992-11-23023 November 1992 Followup to 921005 Part 21 Rept Re Potential Defect in SB/SBD-1 Housing Cover Screws.Procedure Re Replacement of SBD-1 Spring Cover Bolts Encl.All Fasteners Should Be Loosened & Removed.List of Affected Utils Encl ML20118B4391992-09-11011 September 1992 Part 21 Rept Re Degradation in Abb Type 27N Undervoltage Relays Used in Electrical Switchgear.Recommends That Users Review Applications Requiring Exposures Greater than 1E03 Rads TID W/Time Delay Function Option ML20096F5921992-05-11011 May 1992 Followup to 920417 Part 21 Rept 10CFR21-0062 Re Failed Shaft in DG W/Emd 645 Series Engines Using Turbochargers Remanufactured from May 1991 to Jan 1992.Turbochargers Should Be Removed & Returned to EMD for Insp/Repair ML20043A6091990-04-27027 April 1990 Part 21 Rept Re Defective Axial Cracks in Pump Shaft in Region Immediately Above Impeller & in Reactor Recirculation Pumps.Probably Caused by Crack Growth as Thermal Fatigue. Technical Advisory Bulletin Will Be Sent to Each Util ML20005G6831990-01-0505 January 1990 Part 21 Rept Re Installation Instructions for Grommet Use Range for Patel Conduit Seal P/N 841206.Conduit Seals in Environ Qualification Applications Inspected for Proper Wire Use Range & Grommets Replaced ML20247D3011989-07-12012 July 1989 Part 21 Rept 10CFR21-0047 Re Control Wiring Insulation of Inner Jacket Used on General Motors Diesel Generator Sets Identified as 999 or MP Series.Encl List of Owners of Units Notified ML20246K7401989-04-26026 April 1989 Part 21 Rept Re Incorrectly Stamped Name Plates on Certain Asco Nuclear Qualified Valves.Vendor Will Contact Each Affected Facility & Furnish Correctly Stamped Plates & in Near Future Discontinue Sale of Rebuild Kits for Valves ML20207N4641988-10-12012 October 1988 Part 21 Rept Re Potential Problem W/Emd 20-645E4,Type 999 Excitation Sys Circuit Breaker & Wiring.Potential for Field Circuit Breaker to Trip Due to Combined Air Temps & Field Current Exists at All Plants W/Model 999 Sys ML20211P7211987-02-23023 February 1987 Part 21 Rept Re Rockbestos Coaxial Cable Used in Sorrento Electronics Digital & Analog high-range Radiation Monitor. Insulation Resistance at High Temp Not High Enough for Ion Chamber & Associated Electronics to Operate Properly ML20205T6451986-06-10010 June 1986 Part 21 Rept Re Defect in GE Type Sbm Control Switch Intended for Use in Alternate Shutdown Sys.Defective Switch Rejected & Returned to Vendor.Remaining Switches Examined. Corrective Action Rept M-36 Issued to United Controls,Inc ML20141D8051986-04-0101 April 1986 Part 21 Rept Re Model 402 Series Level Control Used for safety-related Application Shipped W/O Torque Check. Customers Will Be Notified by 860428 & Requested to Perform Torque Check.List of Plants Using Component Encl ML20140A5281985-12-19019 December 1985 Part 21 Rept Forwarding Ltr Sent to Customers Re Check Valves Missing Lock Welds on Hinge Supports or Hinge Support Capscrews,Per 851121 Request.List of Customers Receiving Ltr Also Encl ML20134Q1741985-08-29029 August 1985 Part 21 Rept Re Potential Maint Issues Associated w/Anker-Holth Snubbers.Owners of Anker-Holth Snubbers Will Be Informed of Problems & Sent Revs to Technical Instruction Manuals to Include Procedures for Seal & Fluid Maint ML20210G9921985-08-13013 August 1985 Part 21 Rept Re Failure of Isolated Worm Shaft Gear When Certain Critical Speeds Combined W/Repetitive Transfer of Actuator Clutch Mechanism from Manual (Handwheel) to Motor Drive Mode.Two Possible Solutions Noted ML20116N6141985-05-0303 May 1985 Part 21 & Deficiency Rept SSH-M-85/01 Re Defective Circuit Breakers for Recombiners Supplied by Rockwell Intl.Initially Reported on 841124.Equipment Deficiencies Corrected Prior to Installation.Rockwell Intl Requested to Follow Up Action ML20113A4291985-01-11011 January 1985 Part 21 Rept Re Incorrect Insulating Tape.Instructions Governing Handling of Incoming Matls Fully Adequate & If Followed,Would Have Prevented Error ML20095G6011984-08-22022 August 1984 Part 21 Rept Re Defects in 18-inch SA-333 RHR Pipe.Samples of Defective Pipe Matl Being Shipped to Techninat Corp,Per Request.Defects Located in One Length of SA-333 Grade 6 Pipe ML20090H8501984-07-20020 July 1984 Supplemental Part 21 Rept Re Two Laminar Type Discontinuties Noted in Tioga Pipe Supply Co 18-inch Carbon Steel Pipes. Corrective Action Rept M-27 Issued to Bechtel on 840705 Requesting Identification of Cause ML20077H7051983-08-0404 August 1983 Part 21 Rept Re 75 Components (Part P2073A) Lacking Conformance to Specs for Size & Fusion.Initially Reported on 830718.Conditions Which Allowed Erroneous Shipment Corrected ML20083L9751983-05-27027 May 1983 Part 21 Rept Re Failure of Circuit Breakers During Environ Testing.Test Results Indicate That Temp Sensitivity Problem May Be Generic to All Ite Imperial Corp thermal-magnetic Circuit Breakers Calibr for 40 C Svc ML20090L5211974-10-0303 October 1974 Significant Deficiency Rept SDR5 Re High Pressure Svc Water Valve Weld Failure.Initially Reported on 730601.Vendor Weld Stress Analysis Calculations Reviewed & Table of Acceptable Weld Sizes Prepared ML20090L7291974-10-0101 October 1974 Deficiency Rept Re Potential Seal Failures Found in Bergen-Paterson Snubbers Installed at Several Bwrs.Fittings W/Ethylene Propylene Flaps Made Available for Future Snubber Maint 1997-05-27
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML20217D1261999-09-30030 September 1999 Monthly Operating Rept for Sept 1999 for Monticello Nuclear Generating Plant.With ML20216E7031999-08-31031 August 1999 Monthly Operating Rept for Aug 1999 for Monticello Nuclear Generating Plant.With ML20210Q0521999-08-0404 August 1999 Safety Evaluation Approving Relief Request 10 to License DPR-22 Per 10CFR50.55a(g)(6)(i).Inservice Exam for Relief Request 10,Parts A,B,C,D & E Impractical & Reasonable Assurance of Structural Integrity Provided ML20210Q6611999-07-31031 July 1999 Monthly Operating Rept for July 1999 for Monticello Nuclear Generating Plant.With ML20209F7901999-06-30030 June 1999 Monthly Operating Rept for June 1999 for Monticello Nuclear Generating Plant.With ML20195H0351999-05-31031 May 1999 Monthly Operating Rept for May 1999 for Monticello Nuclear Generatintg Plant.With ML20206N1721999-04-30030 April 1999 Monthly Operating Rept for Apr 1999 for Monticello Nuclear Generating Plant.With ML20205N0861999-04-12012 April 1999 Safety Evaluation Re Licensee Response to GL 95-07, Pressure Locking & Thermal Binding of Safety-Related Power-Operated Gate Valves ML20205P5701999-03-31031 March 1999 Monthly Operating Rept for Mar 1999 for Monticello Nuclear Generating Plant.With ML20204H4951999-03-18018 March 1999 SER Concluding That Licensee Established Acceptable Program to Verify Periodically design-basis Capability of safety-related MOVs at Monticello.Therefore Staff Concludes Licensee Adequately Addressed Action Required in GL 96-05 ML20205G7391999-02-28028 February 1999 Monthly Operating Rept for Feb 1999 for Monticello Nuclear Generating Plant.With ML20202F7901999-01-25025 January 1999 1999 Four Year Simulator Certification Rept for MNGP Simulation Facility ML20199E4871999-01-0606 January 1999 SER Accepting Licensee 951116,960214 & 0524 Responses to NRC Bulletin 95-002, Unexpected Clogging of Residual Heat Removal Pump Strainer While Operating in Suppression Pool Cooling Mode ML20199F6211998-12-31031 December 1998 Monthly Operating Rept for Dec 1998 for Mngp.With ML20205H0561998-12-31031 December 1998 Northern States Power Co 1998 Annual Rept. with ML20198P0691998-12-28028 December 1998 Safety Evaluation Concluding That NSP Proposed Alternative to Paragraph III-3411 of App III to 1986 Edition of Section XI of ASME Code Provides Acceptable Level of Quality & Safety.Alternative Authorized ML20198D0751998-12-10010 December 1998 Safety Evaluation Supporting NSP Proposed Change to EOPs to Use 2/3 Core Height as Potential Entry Condition Into Containment Flooding ML20198B2531998-11-30030 November 1998 Monthly Operating Rept for Nov 1998 for Monticello Nuclear Generating Plant.With ML20195E3691998-11-12012 November 1998 Safety Evaluation Concluding That Licensee USI A-46 Implementation Has Met Purpose & Intent of Criteria in GIP-2 & Staff Sser 2 for Resolution of USI A-46 ML20195D2381998-10-31031 October 1998 Monthly Operating Rept for Oct 1998 for Monticello Nuclear Generating Plant.With ML20198J4451998-10-22022 October 1998 Rev 2 to SIR-97-003, Review of Test Results of Two Surveillance Capsules & Recommendations for Matls Properties & Pressure-Temp Curves to Be Used for Monticello Rpv ML20154L3471998-09-30030 September 1998 Monthly Operating Rept for Sept 1998 for Monticello Nuclear Generating Plant.With ML20153F0511998-09-21021 September 1998 Rev 2 to MNGP Colr,Cycle 19 ML20153E9361998-09-0808 September 1998 Rev 1 to MNGP Colr,Cycle 19 ML20153B0861998-08-31031 August 1998 Monthly Operating Rept for Aug 1998 for Monticello Nuclear Generating Plant.With ML20237B8461998-07-31031 July 1998 Monthly Operating Rept for July 1998 for Monticello Nuclear Generating Plant ML20236W5041998-07-21021 July 1998 ISI Exam Summary Rept - Refueling Outage 19 ML20236R1941998-06-30030 June 1998 Monthly Operating Rept for June 1998 for Monticello Nuclear Generating Plant ML20249A5861998-05-31031 May 1998 Monthly Operating Rept for May 1998 for Monticello Nuclear Generating Plant ML20247K3971998-04-30030 April 1998 Monthly Operating Rept for Apr 1998 for Monticello Nuclear Generating Plant ML20217D8731998-04-13013 April 1998 Rev 0 to MNGP Colr,Cycle 19 ML20217F6431998-03-31031 March 1998 Monthly Operating Rept for Mar 1998 for Monticello Nuclear Generating Plant ML20216D1041998-03-0505 March 1998 Rev 21 to Operational QA Plan ML20216H6481998-02-28028 February 1998 Monthly Operating Rept for Feb 1998 for Monticello Nuclear Generating Plant ML20203G1431998-02-10010 February 1998 Rev 2 to Inservice Insp Exam Plan,Third Interval,920601- 020531 ML20203B2821998-01-31031 January 1998 Monthly Operating Rept for Jan 1998 for Monticello Nuclear Generating Station ML20202F9161998-01-29029 January 1998 Special Rept:On 980128,two of Three Fire Protection Pumps Were Removed from Svc as Result of Sys Configuration Necessary to Support Planned Maintenance.Fire Pumps Were Returned to Svc on 980128 ML20216D2071997-12-31031 December 1997 1997 Annual Rept for Northern States Power Co ML20197J8131997-12-31031 December 1997 Revised Evacuation Time Estimates for Plume Exposure Pathway Emergency Planning Zone at Monticello Nuclear Power Plant. W/One Oversize Drawing ML20198P2201997-12-31031 December 1997 Monthly Operating Rept for Dec 1997 for Monticello Nuclear Generating Plant ML20203J7131997-11-30030 November 1997 Monthly Operating Rept for Nov 1997 for Monticello Nuclear Generating Plant ML20199G7051997-11-19019 November 1997 Safety Evaluation Authorizing Relief Request 8 of Third 10 Yr Inservice Insp Interval ML20199H8181997-10-31031 October 1997 Monthly Operating Rept for Oct 1997 for Monticello Nuclear Generating Plant ML20217K2081997-09-30030 September 1997 Monthly Operating Rept for Sept 1997 for Monticello Nuclear Generating Plant ML20216H7771997-08-31031 August 1997 Monthly Operating Rept for Aug 1997 for Monticello Nuclear Generating Plant ML20217K2741997-07-31031 July 1997 Monthly Operating Rept for Jul 1997 for Monticello Nuclear Generating Plant ML20196H1081997-07-0808 July 1997 Rev 20 to Operational QA Plan ML20141B9271997-06-30030 June 1997 LOCA Containment Analyses for Use in Evaluation of NPSH for RHR & Core Spray Pumps ML20149E2921997-06-30030 June 1997 Monthly Operating Rept for June 1997 for MNGP ML20148S6341997-06-23023 June 1997 NPSH - Rept of Sulzer Bingham Pump 1999-09-30
[Table view] |
Text
f g.*' .
Northern States Power Company 414 Nicollet Mall Minneaooks. Minnesota 55401 Telephone (612) 330-5500 May 3, 1985 Director Office of Inspection and Enforcement U S Nuclear Regulatory Commission Washington, DC 20555 MONTICELLO NUCLEAR GENERATING PLANT Docket No. 50-263 License No. DPR-22 Report of Defective Components (SSH-M-85/01)
The following infomation is reported in accordance with 10 CFR Part 21, Section 21.21 (b)(3) . Northern States, Power Company has determined that components intended for the Monticello Combustible Gas Control System (CGCS) were manufactured with potential defects which may have presented a substantial safety hazard.
The defective components were supplied by the manufacturer of recombiners used in the CGCS. The defects were detected during tt . ting of the components prior to their installation during the 1984 refueling and maintenance outage.
The components were repaired prior to plant startup.
The following information is provided related to this defect:
- 1. Name and Address of Individual or Individuals Informing the Commission David Musolf, Manager-Nuclear Support Services Northern States Power Company 414 Nicollet Mall Minneapolis,.MN 55401
- 2. Identification of the Facility and Defective Components Monticello Nuclear Generating Plant Rockwell International BWR Containment Recombiners Power Cabinet Circuit Breakers (two) 224A ITE Gould Molded Case Circuit Breakers
- 3. Identification of the Firm Supplying the Defective Components Rockwell International, Energy Systems Group
[S 0{0M $$$ 3. 'b
Director-I&E,..USNRC-MayJ3, 1985 Page'2-f4. Nature of Defect The two circuit breakers had.an internal open connection on one of the phases due_to a missing screw which connects the trip device to the disconnect mechanism.
.The defects were internal to the circuit breaker.and were detected by the NSP. Electrical Construction Testing Group as part of their pre-installation testing.
- 5. Date on Which ! Information Was Obtained
! The' Electrical Construction Testing Group filed a discrepancy report describing the defect on November 24, 1984.
.A Quality' Assurance Nonconformance Report was issued on December 4, 1984 and. Technical Review' Board action was initiated on the following day.
A preliminary investigation report was issued on February,11, l 1985 and submitted'to.the plant staffffor review. ~
The requirements for reportability of this failure were discussed at length and it was unclear whether.or not a Part 21 report was appropriate. The decision was made, however, to interpret the NRC requirements conservatively
, and submit a report. NSP management was notified of this
[ -determination on May 2, 1985.
6., Number of Components and Location
, See item (2) above. A total of four circuit breakers were~ '
supplied under the-same purchase order (M13282).
' 7. Corrective Action Taken The equipment deficiencies' vere corrected prior.to installation.
8.~ Advice Related'to Defect Given to Purchasers or Licensees
~
1
-Corrective action report M-34 was issued,to Rockwell International-on January. 10, 1985 requesting Rockwell to' identify the cause of
- the defects, address -the. possibility of occurrence in
- other circuit breakers of similar type, 'and identify l actions to be taken
-to prevent future' delivery 1of. defective circuit breakers.
s Advice given_to.other purchasers or licensees by Rockwell is 1- unknown.
_.__..L_.. '
lj
- p. . e; ,
. Director-I&E,.USNRC, Northem States Power Company
.l May . 3 ; '1985 .'
-Page.3-Please contact'us;if you require additional information related to this report. . Three copies of:this report are being provided.