PVNGS Unit 1 SG Eddy Current Exam,Third Refueling Outage, Mar 1992
ML20116K199
Person / Time
Site: Palo Verde 
Issue date: 08/12/1992
From:
ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR
To:
Shared Package
ML17306B117 List:
References
NUDOCS 9211170062
Download: ML20116K199 (62)


Text

v-p PALO VERDE NUCLEAR GENERATING STATION UNIT 1 STEAM GENERATOR EDDY CURRENT EXAMINATION 3rd REFUELING OUTAGE MARCH 1992 ARIZONA PUBLIC SERVICE P.O. BOX 52034 PI!OENIX, AZ 85072 l

1 PREPARED BY: /4.

-2 DATE: 8 kd c-v q

REVIEWED BY:

///h I M

DATE: (7-//- 8

/

g_ / ~

DATEA-M C/2 APPROVED BY: /

l I

COMMERCIAL SERVICE DATE: 1/28/86 REPORT DATE: 8/05/92 -

j 9211170062 920812 FDR -ADOCK 05000528 e

.a PDR

4 INDEX i:L4, 1.0

SUMMARY

2.0 EXAMINATION DISCUSSION 3.0 EXAMINATION RESULTS 4.0 EXAMINATION TECHNIQUES AND EQUIPMENT APPENDIX A - TUDE SUPPORT DIAGRAM APPENDIX D - EXAMINKrlON PLAN APPENDIX C -

SUMMARY

DATA SHEETS (BOBBIN)

APPENDIX D -

SUMMARY

DATA SHEETS (MRPC)

APPENDIX E -

SUMMARY

DATA SHEETS (PLP)

APPENDIX F - TUBE PLUG MAP APPENDIX G - FORM NIS-1

__ _ __ _ - _ m

UNIT 1 STEAM GENERATOR EDDY CURRENT EXAMINKrlON 1.0 Sununary The third refueling outage eddy current examinations for Unit I were conducted during March and April 1992. The initial examination plan for both steam generators was to exam-ine 30 percent of tubing fulllength, and 70 perunt part length. Additional examinations were conducted for program expansions.

The examinations resulted in both steam generators being classified in category C-2. The to-tal tubes plugged were; 23 in steam generator 11, and 18 in steam generate 12.

2.0 Examination Discussion The examination phm was developed to meet the requirements of PVNGS Technical Spect fication 4.4.4.0. The original phtn for steam generamr 11 and 12 was to inspect approxi-mately 30% of the tubing full length from the cold leg side, and 70% of the tubing part length from the hot leg side. The part length hot leg exam was deseloped to insure that all tubing be examined at locations previously found to contain axial cracking. Previous axial cracking was detected during the Unit 2 third refueling. A complete listing of the prelimi-nary examination plan is located in Appendix B.

The progression and extent of examinations for each steam generator was as follows:

Skam Geilnator # 11

- llobbin coil examinations were completed in accordance with the original in-spection plan.

- Due to six defective tubes, a piogram expansion of 760 tubes was perfonned.

- MRPC examinations were perfonned on approximately 372 tubes. Appendix D list the MRPC examination locations and results.

Steam Generator # 12

- Visual examination of the primary side tube sheet identified the existence of a foreign material in the tube sheet on the primary si.e. (Material Nonconfor-mance Report 92-RC-1008 was generated to track and report the foreign mate-rial removal)

- Bobbin coil examinations were completed in accordance with the original in-spection plan.

- A program expansion was perfonned due to defective tubes and in an attempt to locate additional foreign material. The expansion consisted of bobbin coil examination of appmximately 7600 tubes. (No additional foreign material was located by eddy current.)

- MRPC examinations were perfonned on approximately 193 tubes. Appendix 9 list the MRPC examination locations and results.

- During secondary side pressurization of steam generator 12, tube # R44-L91 was noted as dripping from the hot leg tube sheet. Subsequent MRPC exami-nation revealed a single axial indication adjacent to the tube to tube sheet weld. This indication was not detected by bobbin examination or reextanina-tion due to '.he defect location next to the tube weld.

4 3.0 Examination Results A tabulation of the examination results are located in Table 1 of this report. In addi-tion, Appendix A contains a reference drawing of steam generator support locations.

The summary data sheets of Appendix C list all tubes in each steam generator with in-dications expressed as a percent wall thickness reduction, or as an analysis code. Ap-pendix E contains summary data sheets for tubes classified as possible loose parts.

The results of specific examinations for each steam generator were as follows:

Siciun Generator # 11

- The 307c full length and 707c part length bobbin examinations resulted in six defective tubes,25 degraded tubes, and was classified in category C-2.

- The 760 tube expansion resuned in no defective tubes, four degraded tubes, and was classified in category C-1.

- The 372 MRPC examinations resulted in l uee tubes being characterized l

as having multiple axialindications located at the hot leg tube sheet. The remaining 369 tubes were characterized as NDD, PVN, PLP, or percent wall reduction.

- Analysis of bobbin and MRPC data revealed 40 tubes with possible loose parts.

Strom Generator # 12

- The 307c full length and 707c part length bobbin examinations resulted in five defective tubes,20 degraded tubes, and was classified in category C-2.

- The program expansion (approx. 7600 tubes) resulted in nine defective tubes,13 degraded tubes, and was classified in category C-2.

- No further program expansions were perfonned as essentially 1007c of tubing was inspected.

- The 193 MRPC examinations resulted in five tubes being characterized as single axial indications. The remaining 188 tubes were characterized as NDD, PVN, PLP, or percent wall thickness reduction.

- Analysis of bobbin and MRPC examinations revealed 21 tubes with pos-sible loose parts.

In regards to NRC Intormation Notice 90-49 " Stress Corrosion Cracking in PWR Steam Generator Tubing", eight tubes were identified as having axial indications in-dicative of cracking. With the exception of steam generator 12 tube number R44-L91 all axial indications were detected by bobbin examination. The MRPC examinations are summarized in appendix D.

The overall er.aminations resulted in plugging a total of 23 tubes in st: am generator number i1, and 18 tubes in steam generator number 12. All defective tubes and tubes with axial indications were plugged pursuant to technical specification requirements.

In addition, various degraded tubes were plugged as preventative measures. The maps supplied in Appendix F show the total tubes plugged to date. The NIS - I form in Ap-pendix G list each of the tubes plugged as a result of this examination.

TABLE I INDICATION

SUMMARY

INDICATION CNTEGORY STRAM GENERATOR 11 STEAM GENERATOR 12 Corner Eggerate Wear

<20%

3 0

220% <40%

3 3

240 %

1 0

Eggerate Wear (20%

22 45 220% <40%

5 6

240 %

0 0

Plow Dist I' late Wear

<20%

2 0

220% <40%

2 0

240 %

1 0

i Batwing Wear

<20%

0 4

220% <40%

2 4

l 240 %

1 0

l Vertical Strap Wear

<20%

21 30 220% <40%

13 15 l

240 %

0 0

Pasible Loose Parts l

w/ wear 5

4 wo/ wear 35 17 Axialludications l-Tube Etxt flot 1

1 Tube Sheet flot i

4

4 4.0 Examination Techniques and E,1uipment The eddy current examination was perfonned by Conam Nuclear Inc. using Zetec MIZ-18 digital data acquisition and amdysis syste:ns. The following frequencies were used for the tube examination (s):

550 KilZ NOTE:All.quencies were utilized in both 990 KIIZ differential and absolute modes.

100 KlfZ 20 KliZ All tubing was examined with Zetec manufactured bobbin coil style probes, either 0.610, 1

0.580,0.540, or 0.590 inch diameter. A 3 coil motorized rotating pancake probe was also used to characterize the indications at various locations. Data acquisition was facilitated by using Zetec SM-10 and SM-20 "no entry" probe positioning fixtures in both the cold and hot leg S/G plenums respectively. Conam Nuclear Inc. provided the primary data analysis and Combustion Engineering perfonned a complete secondary analysis. A third analysis was perfomied utilizing computer data screening (CDS) for indications.

During data analysis, a detailed evaluation was performed for possible loose parts and sludge profiling.

Each level IIA individual from Conam Nuclear Inc. and Combustion Engineering who per-formed data analysis was required to complete and pass an on-site data analysis perfor-mance examination with at least a 80% proficiency within the last year (12 months).

1 l

l l

I l

.-nm

APPENDIX A l

STEAM GENERA 10R TUBE SUPPORT DIAGRAM l

l l

t I

Appendix A-L' CE SYSTEM 80 STEAM GENERATOR TUBE SUPPORT DIAGRAM VS1 2 3 4 5 6 7 i

BW1 BW2 0911 09C 45" 0811 08C 45" 07H 07C 41" 0611 06C 42" 051!

05C 43" atti 04C 24" 03H 03C 41" 43" 02C 02H 15.5" 32.5" 0111 OIC 16.5" TUBESHEET 23.5" INLET OUTLET NOTES:

SUPPORTS OlC&0lli SUPPORTS 02 THRU 09 SUPPORTSPACINGS ARE CORNER EGGCRATE IS ARE FLOW DISTRI-ARE EGGCRATE TYPE IDENTIFIED IN INCIES COLD LEO SIDE,10 ROWS BUTION BAFFLES BETWEEN THE SUPPORT UP,20 LINES IN,02C THRU IDENTIFICATION 04C SUPPORTS Page1of1' a

- _ ~...... _..

I I

l APPENDIX B i

l j

o 1

EXAMINATION PI AN

Appendix B -

i l

Steam Generator 1 l

Cold Leg Exam Description of Groups No. of Plugged No. of Total Probe Tubes in that Tubes to Tubes Area Test 2 tubes around the outer periphery 6

745 751 610VL 1 tube around the stays 0

241 241 610UL 20 knes in ano 10 rnws up in the 1

51 52 610UL Icwer corners, trom the left corner 20 lines in and 10 rows up in the 0

56 56 610UL lower corners, from the right corner 3 tubes around the stay cylinders 5

267 272 610UL 1 tube around the plugged tubes 0

36 36 610UL Low rows (Rows 1,2 & 3) 26 182 208 610VL Extent is TEC-07H Tubes with 1" of SLG or greater in 0

67 67 610UL C/L only Prior Indications 7

92 99 610UL 0-100 %

UDI.DRI DSI DNI.DTI All prior PLPs and 1 tube around 2

5 7

610UL cach Suspect Wear Areas from Unit #2 2

1558 1560 610UL maps TOTAL TUBES 49 3300 3349-Hot Leg Exam Description of Groups No. of Plugged No. of Total Probe Tubes in that Tubes to Tubes Area Test i

All remaining tubes nct examined in -

2 7661-7663.

610VL the cold le0 Extent is TEH 02H.

Lov. Rows (Rows 1,2 & 3),

26 182 208 610UL Extent is TEH-07H TO1 AL TUBES l

28 7843 l -7871 l

I I

- (-

Page 1 of 2 w

e

m-u

~

-A Appendix B 4

Steam Generator c Cold Leg Exam Description of Groups No. of Plugged No. of Total Probe Tubes la that Tubes to Tubes Area Test 2 tubes around the outer periphery 10 726 736 610VL 1 tube around the stays 0

233 233 610 E

_20 lines in and 10 rows up in the 0

56 56 610VL lower corners, from the left corner 20 lines in and 10 rows up in the 1

55 56 610VL lower corners, from the right corner 3 tubes around the stay cylinders 1

248 249 6100L 1 tube around the plugged tubes 21 121 142 610UL Low rows (Rows 1,2 & 3) 13 195 208 610VL Extent is TEC 07H Tubes with 1* of SLG or greater in 0

49 49 010UL C/L only Prior Indications 2

115 117 610VL 0-100 %

UDI,DRI, dst,DNI DTI A!: prior PLPs and 1 tube around 0

11 11 610UL

ach l

Suspect Wear Areas from Un.: #2 0

1491 1491 610UL maps TOTAL TUBES l

48 3500 3348 Hot Leg Exam Description of Groups No. of Plugged No of Total Probe -

Tubes in that Tubes to Tubes Area Test All remaining tubes not examined in 1

7663 7664 610VL the cold leg.

Extent is TEH 02H.

Low Rows (Rows 1,2 & 31.

13 195 208 610UL Extent is TEH 07H j

l TOTAL TUBES l

14 l

7858 7872-l i

i f

l i

1 Page 2 of 2 a

n_

4

,a+4

-u 4

s, 4-

-_A.r.

k

&.m-_L 4

. se n

h W :

l I

APPENDIX C l

l

SUMMARY

DATA SHEETS BOBBIN COIL I

l l

l.

t m

LEGENJ2 ROW:

Indicates -

row number of a given tube LIN:

Indicates the column number of a given tube.

LEG:

Indicates the tube leg from which examination was performed; C is from cold leg, H is from hot leg EXAM EXTENT PROGRAM:

Indicates the tube length initially required to be examined, i.e., F/L-full length,07H-seventh suppon on hot leg side, etc.

EXAM EXTENT ACTUAL:

Indicates the tube length actually examined.

REM:

Remarks column used for comments relating to examination.

RPI = Retest Positive Identification RIC = Retest incomplete REEL:

Indicates reel number that the data was recorded on.

PROBE:

Indicates probe diameter and style used for examination.

LOCATION:

Gives indication location relative to known landmarks such as syports, vertical straps, and batwings. Typical location codes are as follows:

  1. 1 Vertical Strap.................................... VS 1
  1. 1 B at w ing..............................,......... B W l
  1. 1 Support Plate in Hot leg.............. OlH
  1. 7 Suppon Plate in Cold Leg.................. 07C Top Tube Sheet Cold Leg.................. TSC Tube End Hot Leg............................ TEH Tube End Cold Leg................................TEC i

VOLTS:

Indicates the peak-to-peak voltage of a given indication response.

DEG:

The measured phase angle of a given indication response.

The percent through the tube wall of a given indication based on the measured phase angle / amplitude and the calibration carve established for that particular channel, or analysis comment codes, e.g., PLP = Possible Loose Parts, etc.

CH:

Indicates the channel used to measure and evaluate a given indication.

MRDC:

Motorized Rotating Pancake Coil ANALYSIS CODES:

Posit ive ID............................... PID Multiple Axial Indication...................... MAI Single Axial Indication.......

. SAI Possible Loose Part.................. P LP

CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO., PALO VERDE, UNIT 1 OTEAM CENERATOR: 11 PAGE:

1 0F 4

LOCATION: ALL DATE:

07/28/92 CRITERIA: Ot TO 1001,PID,MA1,SAI T1HE:

12:39:13 l

l l

1 l

EXAM EXTENT l

l l

l l

CURRENT l

l ROW l LI N l H EATu l LEC l PROGRAM l ACTUAL l REH l Rf EL l PROB E [

LOCATION l VOLTS l MIL lDECl t lCH l l_i__I l_l l

I I

l._. __ l i

I l._._. l _ _. !

l l

4l 3l

[C l03C-03Cl03C-03ClRPIl00109l610RPl030- 0.92 l16.80l l

0l 53l 4 l l

l l

l C lTEC-TEHlTEC-TEHjRPIl00072l6100Ll03C-1.01 1 3.60l l

0l 44l18 l l

l l

l C lTEC-TEHlTEC TEH]

l00077l610ULl03C-1.04 l 5.00l l

0lPIDjl8 l l

1l 61 l C l03C 03Cl03C-03Cl lOO109l610RPl03C- 0.97 l 6.201 l

01 34l 4 l l 70l 13l lC l02C-02Cl01C-02Cl l001111610RPl01C+ 0.77

) 4.20l l 54] 28l 4 l l

l l

l C lT.?C-TEHlTEC-TEHlRPIl00066l610ULl01C+ 0.57 l 1.80l l 86l 65l17 l l

l l

[ C lTEC TEHlTEC-TEHj l00077l610UL]O1C+ 0.57

[ 1.80l l 85lPIDl17 l l 69l 141 l C lTEC-TEHlTEC TEHl l00077l6100L101C+ 1.11 l 2.301 l260lPIDl 8 l l

l l

l C l01C-01Cl01C-01Cl l00111l610RPl01C+ 1.04 l 7.30l l155l 29l 4 l l

l l

l C lTEC-TEHlTEC-TEHj l00077l610ULl01C4 0.91 l 1.20l l149] 25l 1 l l

ll 16l l C l04C-04Cl04C-04Cl l00111l610RP104C+ 1.00 l 9.20]

l

0) 22l 6 l l

l l

l C lTEC 07HlTEC-07Hl l00073l590ULl04C+ 0.81 l 1.40l l

0l 24l18 l l

2] 17l l C lTEC-07HlTEC-07Hl l00073l590ULl03C-0.24 l 0.801 l

0l<20118 l l

11 18l l C l04C-04Cic4C-04Cl l00111l610RPl04C+ 0.92 l 5.101 l127l<20] 6 l l

l l

l C lTEC-07HITEC 07Hl l000731390ULl04C+ 0.54 l 1.20l l

0l 22l18 l l 81l 18l l C lTEC-TEHlTEC-TEHj l00066l610ULlBWi+ 1.94 1 0.60l l

0l<20l18 l l 84l 19; 1 C lTEC-TEHlTEC-TEHl l00066l610ULlVS5+ 0.57 l 1.20l l

Ol 21l18 l lTEC-TEH TEC-TEHl l00098l610ULl03H+ 27.88 l 2.601 1

51<20l 1 I l108l 27l lC I

l 921 311 l C lTEC-TEHjTEC TEHj l000761610ULlBW1+ 2.25

[ 0.70l l

0l<20l18 l l 881 33l l C lTEC-TEHlTEC TEHj l00064l610ULlVS5+ 0.54 l 0.901 1

0l<20j1R l 11181 33l l C lTEC-TEHlTEC-TEHl l00098l610ULl09H+ 1,64 l 2.50l l

6l<20l17 l l 82l 35l l C lTEC-TEHlTEC-TEH[

l00063l610ULjVS3- 0.84 l 1.50l l

0l 25l18 l l

l l

lC ITEC TEHlTEC-TEHl l00063l610ULlVSS-0.84 l 1.20]

l 0l 23l18 l l111! 36l l C lTEC-TEHlTEC-TEHj l00095l610ULIVS2- 0.82 1 0.60) l 0l<20l18 l l 71l 38]

l C lTEC-TEHlTEC-TEHj l00061[610ULlBW1+ 1.73 1 0.601 1 0l<20]18 l l

l l

l C lTEC-TEHlTEC TEHj l00061l610ULjVS3-0.94 l 0.60l l

Ol<20l18 l 11091 38]

l C lTEC-TEH!TEC-TEHl l00095l610UL]VS2- 0.90 l 1.00l l

0]<20l18 l 1113l 40l l C lTEC-TEHlTEC-TEHj l00095]610ULlVS5+ 0.93 l 0.60]

l 0l<20l18 l

~

l115l 40l l C lTEC-TEH]TEC-TEHj l00095l610ULlBW1+ 3.61 l 0.60l l

0l<20l18 l l 641 43l lC lTEC TEHlTEC-TEHl l000561610ULlBW1+ 2.05 l 0.60[

]

0l<20l18 l l 65l 44l l C lTEC-TEHlTEC-TEHj l00056l610ULlBW1+ 1.53 1 0.60l l 0]<20l18 l l 881 45l lC lTEC-TEHlTEC-TEH1 l00056l610ULlBW1+ 2.05 l 0,90]

l 0l<20l18 l l 791 52l l C lTEC-TEHlTEC-TEHj l00051l610ULlVS3- 0.95 l 0.80l l

0]<20l18 l l 87l 52l l C lTEC-TEHlTEC-TEHl J00051l610ULlVS2-0.95 l 1.50l l

0[ 22l1B l l 75) 54l l C lTEC-TEHlTEC TEHl

[00051l610UL101C+ 29.52 l 2.40l l 10l 25l 1 l l 821 55l lc lTEC-TEHlTEC TEHl l00049l610ULlV53- 0.90 1 0.60l l

0l<20l18 l l 82] 57l l C lTEC-TEHITEC-TEHj l00049l610ELlVS5- 0.66 l 0.60l l 0l<20l18 l l 801 591 l C lTEC-TEHlTEC-TEHl l00048l6100LIVS5+ 0.72 l 0.80l l

0]<20118 l l 81l 60l l C lTEC TEH]TEC-TEHl l00048!610UL]VS3+ 1.01 l 2.20l l

0l 29l18 I l117) 621 l C lTEC-TEHlTEC-TEHI l 00108 l 616ULl BW1+ 2.33 l 1.10l l

0l<20l18 l l116l 67l l C lTEC TEHlTEC-TEHj l00047l610ULIVS3+ 0.81 1 0.801 l

01<20l18 l-l1541 71l l H lTSH-TSH] TEE-TSHlRPIl00086l610RPlTEH-1.34 l10.00l l241lHAIl 4 l l

l l

l C lTEC-TEHlTEC-TEHlRPIl00045l610ULlTSH-1.64 l 2.70!

l115l 54l 1 l l

l l

l C lTEC-TEHlTEC-TEHj l00090l610ULlTSH- 0.90 l 6.301 l 63]PIDl17 l l

l l

lC lTEC-TEHlTEC-TEHlRPIl00045l610ULlTSH-0.81 l 5.70l l 95l 68l 1 l l

1 I

i i

_I I

I I

I I

i 1

I l___l CONAM NUCLEAR, INC.

w___ _ __ _ -

CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SER"1CE CO., PALO VERDE, UNIT 1 STEAH CENERATOR: 11 PACE:

2 0F 4

LOCATION: A' L DATE:

07/28/92 CRITERIA: 0% TO 1004,PID,MAI,SAI T1HE:

12:39:13 l

l l

l l

EXAM EXTENT l l

l l

l CURRENT l

l ROW lLINjHEAT#lLECl PROGRAM l ACTUAL lREMI REEL lPROBEj LOCATION lVOLTSlHILIDEGl t lCill l

l __ l l

l l

l_1 1

I I

l _ i ___ I ___. l _1 l 33l 72 ] EXP 1l C l01C-02Cl01C-02Cl l00114l610RPj01C+

0.59 l 2.20]

[128l<20l 4 l l117l 74) lC lTEC TEHlTEC TEHl l00045l610UL!VS3-0.85 1 0.90l l

01<20l18 l l 38 l 77 l EXP 1 l 11 l TEH-02H l TEll- 02H j l00035l610ULl02H+ 22.86 l 3.90l l 13l 33l 1 [

j l

l l H lTEH-TEClTEH-TECl l00103l610UCl0211+ 23.35 l 3.70l l

8l 20l 1 l l1551 82l l C lTEC-TEHlTEC-TEHl l000421610ULlBW1+

1.92 l 2.70l

[

01 32l18 l l 40l 83lEXP ll H !TEH-TEClTEll TECl l00103l6100Cl04H+ 14.60 l 2.501 l 12l 30] 1 l l 42) 83 l EXP 1 ) H lTEll TEClTEH TEC[

100103l610UCl02C+ 18.82 l 2.101 l

5l<20l17 l 1110] 83l l C lTEC-TEHjTEC-TEHl l00042l610ULl"W1+ 2.32 l 0.70l l

0l<20]18 l l116l 83l l C lTEC-TEHlTEC TEHj l 00042 l 6100L10911-1.10 l 1.101 l

01<20l18 l l 36l 87l l C lTEC TEHlTEC TEHj l00034l610ULlBW1-2.00 l 1.10l l

01<20l1B l-l116] 87l lC lTEC TEHlTEC TEHj l00090l610ULl08H+ 0.79 l 0.50]

1 0l<20l18 l l

l l

l C lTEC-TEHlTEC-TEHj l00090l610UL]09H-1.23 l 1.40l l

0l 23l18 l l156l 87l l C lTEC-TEHlTEC-TEHj l000901610ULlBW1+

1.83 l 1.10l l

01<20l1B l l117l 88l l C [TFC-TEHjTEC TEHj l00087l610ULl09H-0.74 l 1.10l l

0l<20l18 l l1351 881 l 11 lTEH-02HlTEH-03Hj l00043l610ULl02H+ 38.23 l 2.00l l

5l<20[ 1 l l 38l 91l l C lTEC TElllTEC-TEHj l00034l610ULlBW1-2.03 l 1.00j l

Ol<20l18 l l1591 94l l C lTEC-TElllTEC-TEHj l00085l610ULlVS7+ 1.20 1 1.80l l

01 22l18 l l 41( 35l l C lTEC-TEHlTEC-TElij l00034l610ULlVS4-1.00 1 0.80l l

0l<20118 l l 46) !"lEXP 1l H lTEH-TEClTEH-TECl l00105l6100ClVS4+

1.07 l 0.40; I

0l<20118 l l 39l 96l l0 lTEC TEHjTEC-TEHl l00034l610ULlBW1-1.89 l 2.40l l

0l 29118 l l

l l

l H ITEH-07HlTEH-07Hj l00127l590ULlBW1-1.57 l 1.30l l

0) 29118 l l159l 961 l C (JEC-TEHlTEC-TEHj l00085l610ULlBW1+ 1.88 l 1.30l l

0l<20l18 l l 38l 97l lC lTEC-TEHlTEC-TEHl l00034l6100LlBW1-2,01 l 0.70l l

0l<20l18 l c

l l

lC lTEC-TEHjTEC-TEHl l00034l610ULjBW1+ 2.04 l 1.00l l

0l<20l18 l l

l l H lTEH-01ClTEH 01C) l00127l590ULlBW2+ 1,82 l 1.40l

[

0] 31l18 l l

j l C lTEC-TEHjTEC-TEHj l00034l610ULlBW2-1.92 l 2.50]

l 01 30l1B l l 40l 97l l C lTEC-TEHjTEC-TEHj l000341610UL]BW2-1,57 l 0.801 l

0l<20118 l 1156l 971 l C lTEC-TEHjTEC-TEHl l000851610"LjBW2+ 1.95 1 0.90l l

0l<20118 l l 75) 98l l 11 lTEH-02HlTEH 02Hj l00033l610ULlTSH+ 8.64 l 2.901 l

61<20[ 1 l l159j 98l lC lTEC-TEHlTEC-TEHI l00085l610ULlBW2+ 1.61 l 1.20]

l 0l<20l18 l l 37l100l l C lTEC-TEHlTEC-TEHl l00034l610ULlBW1-2.29 l 1.10l l

0l<20l18 l l11811011 lC lTEC-TEHlTEC-TEHl l 00083 l 610ULl 0711+ 0.89 l 0./0l l

0)<20118 l l120l101l l C lTEC-TEHjTEC TElll l00083l610ULl07H+ 0.62 l 0.501 l

0l<20)18 l l

l l

lC lTEC-TEHlTEC-TEHj l00C83l610ULl09H+ 0,87 l 0.50l l

0l<20l18 l l117l102) l C lTEC-TEHlTEC-TEHl l000831610UL109H+ 1.52 l 1.00l l

0l 20l18 l l159l102l lC lTEC-TEHlTEC-TEHlRPIl00083l610ULlBW2+ 1.06 l 2.30l l103l 46l17 l l

l l

l C lTEC-TEHlTEC-TEHj l00108l610ULlBW2-1.33 l 2.401 l100]PIDl17 l 1114l103) l C lTEC-TEHlTEC-TEHl l00083l610ULl0BH-1.02 l 0.40) l 0l<20118 l l116l103l lC lTEC-TElllTEC TEHj l00083l610ULl09H+ 0.99 l 0,60l

[

0l<20118 l l118l103l l C lTEC-TEHITEC-TEHj 100083l610ULl08H-0.92 1 0.501 l

01<20l10 l l158l103l l C lTEC-TEHjTEC-TEHl l00083}610UL}VS1-0.95 l 0.70]

l 0l<20l1B l l 35l104l

- lTEC-TEH]TEC-TEHj l00034l610ULlBW1-2.13 l 1.30) 1 0l<20l1R l l

l l

i C lTEC-TEHjTEC-TEHj l00034l610ULlBW1+ 2.19 l 0.80]

]

0)<20[18 l l113l104l l C lTEC-TEHiTEC-TEHj l00083l610ULlVS2-0.98 l 0.60l l

0l<20l18 l l119l104) l C lTEC-TEHjTEC-TEH(

l00083l610ULl09H-0 70 1 0.50l l

0l<20118 l l

1 I

I I

I I

I I

I I

i l

l l___l 1

=

CONAM NUCLEAR, INC.

CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO., PALO VERDE, UNIT 1 STEAM GENERATOR: 11 PAGE:

3 0F 4

IDCAT70N: ALL DATE:

07/28/92-CRITERIA: On TO 1004,PID,HAI,SAI TIHE:

12:39:13' l

l l

l l

EXAM EXTEUT l

l l

l l

CURRENT l

l ROW I LIN j HEAT # l LEC l PROCRAM l ACTUAL l REM l REEL l PROBE l LOCATION l VOLTS lMILIDEGl : % l CH l-l_l_I I

I l_

l_1 l__l l

I I

i l __ l -

l157l104l lC lTEC TEHlTdC TEHl l00083l610ULlBW2+ 1.36 l 1.40l-l 0l 21l18 l l 36l107l lH lTSH-TSHlTEH-TSHlRPIl00086l610RPITEH+

9.41to+ 13.74l 1.00l l 58lMAIl17 l l

l l

l C lTEC-TEHlTEC-TEHlRPIl00036l610ULlTEH+ '4.25 l 0.70l l 97l 54l17 l l

l l

l C lTEC TEHlTEC-TEHl l000741610ULlTEH+ 14.25 l 0.701 l 93lPIDl17.l 4

l l

l l C lTEC TEHlTEC-TEHl l00036l610ULlTSH-0.72 l 0.40l l125) 29l17 l

~

l l

l lC lTEC-TFHlTEC-TEHlRPIl00036l610ULlTSH- 0.11 l 0.60l l105l 47l17-l l117l108l l C lTEC-TEHITEC TEHl l00082l610ULl09H+ 0.27 l 1.40l l

0l122l18 l q l156l109]

l C lTEC-TEHlTEC-TEHl l00082l610ULlVSI- 0.91 l 0.60l l

0l<20l18 l 1

l l

l l C lTEC TEHlTEC TEHl l 00082 l 610ULl VS7 -

1.12 l 1.10l l

0l<20l18 l l

l157l110l l C lTEC-TEHlTEC TEHl l00079l610ULlVS7+ 0.69 l 1.60l l

Ol'25l18 l l

l l

lC lTEC-TEHjTEC-TEHj l00079l6100LlVS7- 0.50 l 1.60l l

Ol 24l18 ;

l l

l lC lTEC TEHlTEC-TEHj l000791610ULlBW2+ 1.67 l 0.60l l

0l<20l18 l-l l

l l C lTEC TEHlTEC-TEHj l000791610ULlBW2-1.23 l 1.80l l

0l 27l18 l-l 80l1111 lC lTEC-TEHjTEC-TEHj

[000271610ULlVS3-1,12 l 0.50l l

0l<20l18 l l111l112l l C lTEC-TEHlTEC TEHj l00079l610ULlVS3+ 0.74 l 1.50l l

0l 21l18 l l117l116l l C lTEC TEHjTEC-TEHj l00042 610ULl09H+ 0.37 l 0.70l l

0l<20[18 l l

l l

lC lTEC-TEHITEC TEHj l00042l610ULl09C. 0.34 l 0.70l l

0l<20j18 l 1151l120l l C lTEC-TEHlTEC-TEHj l 000411610ULlVS7+ 0.69 l 1.00l l

0l<20l18 l l 281121lEXP 1l H lTEH 02HlTEH-02Hj l000181610ULl0lH+ 1.40 l 2.40l-l 3l<20l 1 l l

l l

l H lTEH-02H!TEH-02Hj l 00018 l 610ULl 01H+ 5.76 l 4.20l l

7l<20l 1 l l 98l123l l C lTEC-TEHjTEC TEHl l00026l610ULl08H-0.86 l 0.70l l

0l<20l18 l l 97l124]

j C lTEC-TEHjTEC-TEHl l00026l610ULl08H- 0.96 l 1.20l 0)<20l18 l l 96l1251 l C lTEC-TEHITEC-TEHl l00025l610ULl08H-0,93 l 2.00l-l 0l 25l18 l l 94i127l l C lTEC TEHlTEC-TEHl l00025l610ULl08H- 0.98 l 1.30l l

0l<20118 l l 60l131l l H l04H-04Hl04H-04Hl l000841610RPj04H+ 10.86 l 1.20l l

0l<20l 4 l:

l 96l133l l C lTEC TEHlTEC-TEHl l00022l610ULl08H+ 0.64 l 0.80l l

0l<20l18 l l 831134l l C lTEC-TEHlTEC-TEHj

[00022l610ULlVS3+ 0.69 l 1.50l l

0l 21l18 l l 87l134) l C lTEC-TEHlTEC-TEHj l000221610ULj08H- 0.51 l 0.90l l

0l<20l18 l l145l134l l H lTSH-TSHlTEH-TSHlRPIl00084l610RPlTEH+ 21.94 l 3.60l l 52lMAIl 4 l l

l l

lC lTEC TEHjTEC-TEHj l00079l610ULlTSH.

1.00 l 1.60l l 89lPIDl17 l l

l l

lC lTEC-TEHlTEC-TEHlRPIl00040l610ULlTSH-0.96 l 1.20l l 91l 63117 l l 98[139l l C lTEC-TEHlTEC-TEHl l00019l610ULlBW1+

.'.03 l 0.50]

j. Cl<20l18 l 4

-l 59l1401 l H lTEH-02HlTEu-02Hl 100021l610ULlTSH+ 9.96 l 0.80l l

5l<20l 1-l l 78[141]

lC lTEC-TEHlTEC-TEHl l00019l610ULlVS3+ 15.97 l 1.90l l

6l<20l 1_l l

l l

l C lTEC-TEHITEC-TEHj l00019l610ULlVS3+ 22.93 l 1.80l l

8l 20l 1-l.

l 82l141l l C lTEC-TEHlTEC-TEHj l00017l610ULlVS3- 0.82 l 1.50l l

0l 23l18 l l

1l142]

l C lTEC-07HITEC 07Hl l00059l590ULl02C- 0.84 l 0.80l l -0l<20118-[.

.j~82l145l

[ C lTEC TEHlTEC-TEHl l00016[610ULlVSS- 0.91

.l 0.70l l

0l<20:18 l l 60l147l lC lTEC-TEHlTEC-TEHl l000161610ULl02C+ 7.60 l 3.50j l ~8l 20l 1 l-l 1l150l lC lTEC-07HlTEC-07Hj l00059l590ULl02C+ 0.81 l 0.60l l

0l<20l18 l 1 67l152l-l H lTEH-02HlTEH-02Hj l00012l610ULjTSH+ 1,81 l 2.70l l

2l<20) 1 l l 66l155l l C lTEC-TEHlTEC-TEHl lC0005l610ULl08H+ 0.06 l 1.50l l

0l 25l18 l l 76l159l l C lTEC TEHlTEC-TEHj l00005l610ULlVS3+ 0.50 l 1.20l

-l 0l<20l18 l l

11166l lC lTEC-07HlTEC-07H[-

l00059l590ULj02C+- 0.96 l 0.90l-l 0l<20j18 l l 76l169l l C lTEC-TEHlTEC-TEHj l 0005l610ULl753-0.57 l 1.4Cl l

0l 24[18 l l_i_1 1

I I

I I

l l

1 I

l l_l L

CONAM NUCLEAR, IFC.

l l

CUMUIATIVE REPORT 02/92, ARIZONA PUELIC SERVICE CO., PALO VERDE,' UNIT li STEAM CENERATOR: 11 PACE:

4 0F

-4.

?.IfCATION: ALL DATE:

-.07/28/92

-CRITERIA: On TO 100%,PID,MAI,SAI TIME:

12:39:13-l l

l l

l EXAM EXTENT l

l l-l l

-CURRENT

_.l

[ ROW lLINjHEAT#lLE0l PROGRAM l ACTUAL l REM l REEL l PROBE l LOCATION l VOLTS l MIL lDEGl,t lCH l1 '

l __ I l

l __ l i

l i

I I

l' I

I l

l l 78l169l l C lTEC-TEHlTEC TEHl l00005l610UL]VS3- 0.87 l 2.20l

.l 0] 31l18 l-.

l.

1l174l l C lTEC-07HlTEC-07Hl.

l00059]590ULl03C+ 0.82 l 0.80l l

0l<20l18'l l 46l175lEXP 11 H lTEH-TEClTEH TEC[

l00094l6100Ll053- 0.17 l 4.40l l 13l 33l-1 j._

l 50]175]EXP 1l H lTEH-TEClTEH-TECl l00094l610UL]O7H+ 16.43 l 0.60l

'l1471 20l20;l, i

1l176l l C-lTEC-07HlTEC 07Hl l00059l5900Ll05C+ 0.93 l- 0,70l '

l 201<20l18 l-l 33l186l l C lTSC TSCITSC TSCl l00116l610RPlTSC+ 0.41

[:2.40l-l 0j<20l 6 l l 35l1861 l C lTSC-TSCITSC TSCl l00116l610RDlTSC+ 1.05 l 2.10l l

0l<20l 4-l.

l l

l l C lTEC-TEHlTEC-TEH1 100011l610ULlTSC+ 0.96 l 1.201 l154l<20] 1-l l 39l186l' l C lTEC-TEHlTEC TEHl l00011l610ULl05C- 0.96 l 0.90l l

0l<20l18 l l_1 I

l_I I

I I

I 1

l l

1 1

I i

NUMBER OF TUBES SELECTED FROM CURRENT OUTAGE:

108 WO TREND ANALYSIS REQUESTED REPORT OPTIONS:

Only examination results matching criteria are included CONAM NUCLEAR, 1c10.

u-m e

r T

fr----

a w

=

CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO., PALO VERDE, UNIT 1 STEAH CENERATOR: 12 PAGE:

1 0F 4

LOCATION: ALL DATE:

07/27/92 CRITERIA: 0% TO 100%,PID,HAI,SAI TIME:

14:17:26 l

l l

l l

EXAM EXTENT l

l l

l l

CURRENT lL JROWlLINlEXP #l LEG l PROGRAM l ACTUAL l REM l REEL lPROBEj LOCATION l VOLTS l MIL lDECl % lCH l 1

l ___ I I

I I

I I

I I

I l___I l___l___I i

l 2l 1l l C lTEC-07HlTEC 07Hl l00131l590ULl02C- 0.45 l 1,90l l

0l 27l18 l-l l

l l C l02C 02C]02C-02Cl l00194l610RPl02C- 0,83 l 4.10l l

0l 39l18 l-l 11l 12lEXP lj H lTEH 0211lTEH-02Hl l00060l610ULlTSH- 0.52

!45,601-l 3l<20l17 l l 72l 17lEXP lj C lTEC 0811lTEC-06Hl l00106l610UClVS3+ 1,10 l 1.50l l

0l<20l18 l l 91l 181 l C lTEC-TEHlTEC-TEHl l00089l610ULl04C+ 0.00 l 0.70l l147l<20j17 l_

l 93l 20l l C lTEC TEHlTEC-TEHj l00089l610ULl0411+ 37,27 l 0,60l l141l 25]_1 l l 99l 22l lC l TEC-TElll TEC-TElll l00088l610ULl03C+ 0.86 l 1.40l l-0l 20l18-l-l 98l 23]

l C lTEC-TElllTEC-TEHl l00088l610ULl03C+ 1.00 l Oi70l-

-l 0l<20l18~l l-73l 2Bl l C lTEC TEHlTEC-TElll l00067l610ULlVS3+ 0,49 l 1.80l l

0l 21l18 l l 74l 29l lC l TEC-TElll TEC-TEH j l00069l610ULlVS3- 0,84 l 1,20l l

0l<20l18 l l 76l 29l l C lTEC-TElllTEC-TEHl l00069l610ULlVS3- 0,86

[.1,80l l

0l 21l18 [:

l 29l 38]EXP 1l 11 lTEti-07ClTEll-07Cl l00079l610UClVS4+ 0.78 l 1. 00 l.

l 0l<20l18-l_

l 81l 38l l C lTEC-TEHjTEC-TElll l00073l6100LlVS5- 0,87 l 1,80l l

0l<20l18 l l'79l 40l l C lTEC-TElijTEC-TElij l00073l610ULlVS3-1.02 l 1,80l l

0l<20l18-l l 81l 40l

! C lTEC-TElllTEC-TElll l00073l610ULlVS3-1,03 l 1,70l

-l 0l<20l18fl l 70l 41l lC lTEC-TEHjTEC-TEHj l00076l610ULl03H+ 21,31 l 4,50l l

7l<20l 11l l111l 50l l C lTEC-TEHlTEC-TElll l00053l610ULlVS3- 0,88 l 1,101 l-0l<20l18 l_

l 40l 57lEXP ll H lTEH-07ClTEH-06Cl l00068l610UClVS4+ 0,95 l 0.50l l

0l<20l18 l-l 661 57lEXP ll 11 lTEH-08ClTEH-07Cl l00068l610UCl08H. 0.81 l 0.90]

l 0l<20l18-l l112l 631 l C lTEC-TEHlTEC-TElll l00053l610ULlBW1-1.24 l 1,40l

[

0l<20l18-l l1131 70l l C lTEC-TElllTEC TEHj l00054l610ULl02C+ 14,05 l 1,80l l

6l<20l 1 l.

l l

l l C lTEC-TEHlTEC-TElll l00054l610ULl02C+ 13,78 l 2.90l l 11l 28[ 1 l l

l l

l C [TEC-TEH[TEC-TEHj l00054l610ULl02C+ 10.29

[ 3,20l l

8l 21l 1 l l115l 70l l C lTEC-TElijTEC-TEHl l00054l610ULl01C+ 12.55 l 3.30l

-l 6l<20l 1:l l_

l l-l C lTEC TEHlTEC-TEHj l00054l610ULl01C+ 8.15 l 2,00l

-l 3l<20l 1 l l

l-l l C lTEC-TElllTE ' TEHj l00054l610ULlTSC+ 11.62 l 1.80l l

4l<20lc1 l l

l l

l C lTEC-TElllTEC-TElll l00054[6100LlTSC+ 10,96 l 3,90l l _1l<20[ 1 l-l 85l 74lEXP 1l C lTEC-08HlTEC-07Hl l00162]610UClVS5- 'O,81 l 1-.30l l_ 1)l_23l18 l--

l115l 74l l C lTEC-TElllTEC-1EHl l00054l610ULl03H+ 25,25 l 2.10l l

6l<20l 1-l>

l-l l

l C lTEC-TElllTEC-TElll

[00J54l610ULl0311t :27,87 l 1.70[

-l 5l<20lL1-l; l

l l

l C lTEC-TElllTEC-TElll l00054l610ULlBW1+ 11.47 l 1.40l l

0l_22l18-l l

l l

l C lTEC-TEHlTEC-TElll l 00054 l 610'JLl BW1+ 1,91 l 1.50[

l 0l<20l18 l.

l116] 75l lC l TEC-TElll TEC-TEH l 100056 l 610UL] 0911-1.47 l 0.90l l

0l<20l18.l

'[115l 76l l C l1EC-TEHjTEC-TEHl l00056l610ULjBW1-1.98 l_1,40l-l 0l<20l18 l_

-l l

l l C lTEC-TEHlTEC-TEHl l00056l610ULlBW1+. 1.56 l 1,60l l_

0l<20l18_l l 80l 77]

lC lTEC-TEHlTEC-TEH]

l00032l610ULlVSS-1,00

-l 1.20l l

0l<20l18-l l112l 77l l C lTEC-TEHlTEC-TEHl l00056l610ULlVS2. 0.87 l:1.70l-l 0l 20l18 l l114l 79l l C lTEC-TEH]TEC-TElll

'l00056l610ULlBW1- 0.92 l 1.20l l-0l<20l18 l

~

l 29l 80l l H lTEH-TSHlTEH-TSHlRPIl00208l610RPlTSH- 0,88 l 3,10l l107lSAIl 5-l.

l 32l 83l l C lTEC-TEHlT2C-TEHl l00u37l610ULlBW2-' 1.79 l 0,80l l

0l<20l18:l l 34l185l l C lTEC-TEHlTEC-TEHl l00037l610ULlBW1-1.51 l 1.50l l

0l<20l18-l~

l150l 85lEXP 1l C lTEC-09HlTEC-09Hj l00176l610ULlVS3- 0.24 l 1.00l-l Ul<20l18 l' l159l 86) lC l TEC-TElll TEC-TEH j l00063l610ULl04C- -0.24 l_1,00l l '0l<20l18.l l158l 87l l C lTEC TEHlTEC-TEHl l00063l610ULl05C- 0.63

-l 1.30l

-l-_ 0l<20l18 l' l119l_88l l C lTEC-TEHlTEC-TEHj l00058l610ULl09H- 0.03 l 1,20l

_l 0l<20l18 l.

I l___I I-1 I

I I

'l i

I

'l-I l_I I

CONAM NUClIAR, INC.

CUMULATIVE REPORT 02/97, ARIZONA PUBLIC SERVICE CO., PALO VERDE, UNIT 1 STEAM CENERATOR: 12 PACE:

2 0F 4

LOCATION: ALL DATE:

07/27/92 CRITERIA: 0% TO 100%,PID,MAI,SAI TIME:

14:17:26

~

l l

l l

l EXAM EXTENT l

l l

l

}

CURRENT l

l ROW lLIN! EXr #l LEG lPROCRAM] ACTUAL l REM l RLELl PROBEl LOCATION l VOLTS l MIL lDEGl % lCH l l _ I __ I ___ l.

I I

L__ l l_

I I

I I

l __ I l137l 88lEXP 1l C l02C-03Cl02C-03ClRPIl00189l610RPl02C+ 35.75 l 1.60l l 72l 43l 4 l l153l 88l l C lTEC-TEHlTEC-TEH]

l00061l6100LjVS1- 0.86

[ 1.40l l

0l<20l18 l l1561 89l lC lTEC-TEH]TEC TEll]

l 000611610ULl BW2 -

1.91 l 1.20]

l 0l<20l18 l l 44l 91l l 11 lTEll-TSHlTEH-TSillRPIl00214l 610RPlTEH- 0.00 l 2.90l l 46lSAIl 3 l

[111] 92l l C lTEC TElllTEC TEll]

l00058l610ULlVS3+ 0.27 l 1.00l

[

0l<20[18 l 1117] 92l l C lTEC-TElllTEC TEll]

l 00058 l 610UL j 0911-0.60 l 1.20[

l 0l<20l18 l l B61 93lEXP 1l C lTEC-0BillTEC-0711l l00154l610UClVS3+

1.11 l 1.10l l

0l<20l18 l l 39l 94l l C lTEC-TElllTEC-TEHj l00035l6100LlBW2+ 1.79 l 0.60]

l 0l<20l18 l 9#

l133] 96 l EXP 11 11 lTEH-09ClTEll-09Cl l 00163 l 610UL] 08H+ 0.86 l 0.80l l

0l<20l18 l 115711001 lC l TEC-TEH l TEC-TEll]

l00061l610ULlVS7- 0.97 l 1.101 l

0]<20l1C l l115l102l l C lTEC-TElllTEC TElll l000591610ULIVS6+ 0.84 l 1.00[

l O!<20l18 [

l159l1021 l C lTEC-TEHlTEC-TEHj l00061l610ULlBW2-1.73 l 1.70l l

0l 20j18 l l158l103l lC l TEC-TElll TEC-TElli l 00061l 610ULl BW2 -

2.07 l 2.30]

l 0l 26l18 l l 33l106l l C l TEC-TElll TEC-TEH j l00097l610ULlBW1-1.78 l 1.601

[ 0l 21l18 l l117l106l l C lTEC-TElllTEC-TElli l 00059 l 6100Ll 0911+ 1.23 l 1.80l l

0l 29l18 l l158l107l l C l TEC-TElllTEC-TEH j l00063l610ULlVS3-0.97 l 1.101 l

0l<20l18 l l

l l

lC l TEC-TElllTEC-TElll l00063l610ULjVS7+ 0 45 1 0.801 1

0[<20l18 l l 71l108lEXP 1l 11 lTEll-08ClTEH-09Cl l00175l610ULlVS54 0.79

[ 0.50]

l 0l<20[18 l l124l109lEXP 1l 11 lTEH 09ClTEH VS6[

l 00175 l 6100Ll OB11+ 0.88 l 0.40]

l 0l<20l18 l l148l109lEXP ll 11 lTEH-02HlTEll-02Hl l00031l610UL]TSH-0.47 l 1.80l l 97l 58l17 l l

l l

l 11 lTEH-09ClTEH-09ClPIDl00lb1l610ULlTsll- 0.45 l 1.90l l 96l 58l17 l l

l l

l 11 lTSil-TSillTSH-TSHlRrll00202 l 610RPlTSH- 0.32 l 0.90l l121lSAIl 2 l 1116l115[

lC lTEC-TEHlTEC-TEhl

[000501610ULl09H-1.02 l 0.901

[

0l<20[18 l l 93!116lEXP 1] 11 lTEH-08ClTEH-08Cl l00145l610UClTSH- 0.83 l 0.40[

l142l 31] 1 l l117l116l l C lTEC-fell lTEC-TElll l00050[610ULl09H-1.22 l 1.30]

]

Ol 21l18 l l106l117lEXP ll il lTEll-08ClTEH-07Cl l 00145 l 610UC l 0811+ 0.92 l 1.201 l

01<20l18 l l121l118lEXP 11 H lTEH 09ClTEll-08C]

l001421610UCl02H+ 7.09 l 3.801 l 17lPIDj 1 l l

l l

l H lTEH-02HlTEH-02Hj l00028l610ULl02H+ 7.70 l 4.60l l 16l 39l 1 l l

l l

l 11 l02H-03Hj 02H-0311lRPIl00206l 610RPl02H+ 7.71 1 5.10l l

4l 57l 1 l l 76l119l l C lTEC TElllTEC-TEHj l00030l610ULlVSS- 0.94 l 0.701 l

0l<20l18 l l154l119l l C lTEC-TElllTEC-TEHl l00048l610UL]O6C- 0.23 l 0.50]

l 0l<20l18 l l

l l

l C lTEC-TEHITEC-TElli l00048[610ULl03C- 0.99 l 0.50l l

01<20118 l l103l120lEXP 1l H lTEll 08ClTEH-08Cl l 00125 ] 610UL108H+ 0.92 l 0.80l l

01<20118-l l107l120lEXP ll 11 lTEH-08ClTEll-08Cl l001251610ULl08H+ 0.82

[ 0.40l l

0l<20118 l 1151l1201 l C lTEC-TEHlTEC-TElll

[00048'ol0ULl04C- 0.18 l 1.00l l

0l<20j18 l l

l l

l C lTEC-TEHlTEC-TEHl l 000481610ULl 04C-1.14 1 0.60l l

0l<20118 l l 801121l l C lTEC-TEHlTEC-TEll!

l 00030 ] 610ULl VS 5+

0.95 l 0.80]

l 0l<20l18 i

[102l121lEXP 1] H [TEll-08ClTEll-08Cl l OO1251610ULl 0811+ 0.76 l 0.701 l

0l<20l18 l l1521121[

l C lTEC-TEll[TEC-TEHl l00048l610ULlVSS- 0.97 l 0.50l l

0l<20l18 [

l l

lC lTEC-TEHlTEC-TEHl l00048l610ULlBW2+ 1,85 l 0.50]

l 0l<20l18 l l112l1'SlEXP 1l H [TEll 08ClTEll-08Cl l 001251610UL108ti+ 0.93 l 0.60l l

0l<20l18 l l100l125l l C lTEC-TEHlTEC TEHj l00027l610ULlBW1+ 1.85 l 1.40]

l 0l 24l18 l l1141125lEXP 11 H lTEll-08C[TEH-08Cl l00123l610ULlBW1+ 2.08 l 1.10, 1

0l<20!18 l l 93l1261 l C lTEC-TElllTEC-TEll[

100027l610ULl08H+ 0.77 l 0.70l l

0l<20l18 l l 97l126]

l C lTEC-TEHlTEC-TEHj l 000271610UL] 0811+ 0.00 1 0.901 l

0l<20]18 l l_I I

i l

I L_1 1

1 I

I I

l__I _ I CONAM NUCLEAR, INC.

.4 CUMULATIVE REPORT-02/92,-ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 STEAM CENERATOR: 12 PACE:

3 0F 4

I 14 CATION: ALL DATE:

07/27/92

. CRITERIA: On TO 100%.PID,MAI,$AI TIME:

14:17:26

'l l

l l

l EXAH EXTENT l l

l l

l CURRENT

_ lCH l-l l ROW lLINlEXP #l LEG lPROGR/.M] ACTUAL l REM l REEL l PROBE l LOCATION l VOLTS l MIL lDEGl t l___I___l l

l.

I I

I I

I I

I l ___ L __ I l

[ 99l126[

l C [TEC TElllTEC TEH[

l00027]6100Ll08H+ 0.00 l 0.60l l

0l<20l18 j.

[101l126l l C lTEC TElllTEC-TElll l00027l610ULl08H+ 0.36 l 0.60l l

0l<20l18 l l

l l

l C lTEC TElllTEC-TEHj l00027l610ULl03C+ 10.41 l 1.60l l

5l<20l-l'l l103l126lEXP 1l C lVS6 TElllVS6-TEHl l00027l610ULl08H+ 0.00 l24.40]

l172l<20l17 l j j 98l127l l C l TLC TElllTEC TEHl l 00027 l 610ULl 0811+ 0.00

-l 0.60l l

0l<20l18 l l 79l128]

l C lTEC TElllTEC TElll l00025l610ULlVS3- 0.90 l 0.601 l 0l<20l18 l-l l

l l C lTEC-TElllTEC-TEH j l00025l610ULlVSS- 0.97 l 0.80l l 0l<20l18'l l 81l130l l C lTEC TElllTEC TElll l00025l610ULlVS3-1.03 l 0.90l l-0l<20l18 l.

l 89l130l l C lTEC-TEHlTEC-TE!!l l00025l610ULl081t+ 0.52 l 0.90l l 0l<20l18 ;=

l 93l150l l C lTEC-TEHlTEC TElll l 00025 l 610ULl 08F+ 0.48 l 0.60l l 0l<20l18 l l 75l132l l C lTEC-TElllTEC-TElll l00024l610ULl08H+ 0.70 l 0.80l l 0l<20l18-l l 97l132l l C lTEC-TElllTEC-TEll[

l00024l6100Ll080+ 0.86

[ 0.70l l 0l<20l18 l-l 80l133l l C lTEC TulllTEC-TEHj l00022l6100LlVS3- 0;85 l 1.10l l 0l<20l18 l' l

l l

l C lTEC-TEH]TEC-TElll l00022l610ULlVS3- 0.15 l-1.10l l

0l<20jl8 l l 84l133l l C lTEC TElllTEC-TElll l00022l610ULjVS3- 0.90 l 1.30l l- 0l 20l18cl-l 86l133l l C lTEC-TEH]TEC-TEHl l00022 l 610ULl0811+ 0.61 l 1.10l l 0l<20l18 0 :

l144j135l l C l03C-03Cl03C-03C]

l00190l610RPj03C+ 1.03

'l 2.10l l 10lL22l18 [.

l l

l l C lTEC-TElijTEC TEHj l00047l6100Ll03C+ 0.86 l 1.50l l 0l 23l18 l l 79l136l l C [TEC-TElijTEC TEH j l00021l610ULlVS3-1.00 l 1.50l

[

0l 24l18 l l143l136l l C lTEC-TEHlTEC TEll[

l00047l610ULl03C+ 0.92 l 0.901 l- 0l<20l18 l l 78l137l l C lTEC-TElllTEC-TE!!j

[00021l6100LlVSS- 0.50 l 0.80l l

0l<20l18 l.

l141l138]

l C lTEC-TElllTEC TEH j lC0047l610ULl07H+ 0.08 l 0.30l l 0l<20l18 l l133l140lEXP 1l H lTEll-09ClTEH 09Cl l00126l610UClBW1+ 1.14 l_1.10l l 0l_20l18.l1 l 72[141l l C JTEC-TEHlTEC-TEHl l000201610UL]BW1+ 1.79

-l 0.50l l_ 0l<20l18 l1 l-76l141l l C JTEC-TEHlTEC TEHj l00020l610ULlVS3-0.81-l 2.00l l 0l 29l18,l l1341141l EXP 1l H [TEH-09ClTEll-09Cl l00116l610UClBW1+ 1,45 l 1.40l

l 0l7 23l18 l l-87l142l l C lTEC-TElllTEC-TEHl l00C20[610ULlVS3-0.87-l 0.'60l l

0l<20l18'l' jl21l142lEXP 1l H lTEll.0211lTEH-02Hl~

l00020l610ULlTSC+ 11:12 l 4.40l l 14l 35l 1-l.

l 9?l142l l C lTEC-TElllTEC-TEHj l00013l610ULlTS!!+ 11.29 l~2.00]

l-8l 20l 1--l

- [104l143]EXP 1l 11 lTEH-08ClTEll.07Cl l001401610UClBW1 2.00

_l 0.90l l.0l<20l19 l l 77l144l l C lTEC-TElllTEC-TElij l00018l610ULlVS3+~0.81 l 1.30l l

Ol 24l18-l l103l144lEXP_1l H lTEll-08ClTEll-07Cl l00140l610UCl08H+ 0.92

_ l 0.90l-l 0l<20l18'll l119l144lEXP 1l H lTEH-09ClTEll-08Cl l001401610UCl09H+. 1.11 l 0.80l_

l 0l<20l18 l l 78l145l_

l C lTEC-TElljTEC-TElll l00018l610ULl02H+ 28,83 l 3.90l ll 11l 28l1-l l106l149lEXP 1l 11 lTEll-08ClTEll-08C]

l00113l610UClBW1-1,68 l 0.60l l

0l<20l18 ll l 82l151l l C -lTEC-TEHlTEC-TElll l00014l610UL]VS3- 0.80 l 0.60l l

0l<20l18-l l100l151lEXP ll H lTEH 08ClTEH 08Cl l00112l610UClVS3- 0.72 l 1.1Cl l 1Dl 24l18 l' l 11{152lEXP 1l H lTEll-TSHl TEN-TSHlRPIl00206l610RPlTSH- 0.63 l 2.70lL l11RlSAIl 5 l l 50l155lEXP 1l H lTEH-07ClTEH-07Cl l00103l610UClVS4+ 0.69

_ l 1.10].

l 0l 23l18-l l 84l155l l C [TEC-TEHlTEC-TEHj l00014l610ULlVS3- 0.98 l 1.60lf l-_0l-28l18 j'

=l 88l155lEXP 1l 11 !TEH 08ClTEH-08Cl l00103l610UClBW1+ 1,80 l 1.10l l

0l 23l18 l

. [' 66l159lEXP 1[ H lTEll 08ClTEH 07Cl-l00100l610UCl08H+ _ 1,41 l 0.90l l

0l<20l18 l l 73l160l l C.lTEC TEHlTEC+TElll.

-l00012l610ULlVS5+ 0.76 l 1.40l l

0l_24l18-l.

l 72l161l l C lTEC-TEll[TEC-IEHj l00012l610ULl07C+ 21.87 l 1.80l l_ 5l<20l IJl-l l 88l161lEXP 1l H [TEll-08C[TEll-08C) l00099l610UC]BW1+.1,42 l-0.70l_

l.0l<20l18-l-_

l_l '

(

l I

l-1 I

I I

I I

I I

I I

L CONAM NUCLEAR, INC.

1 r

d CUMULATIVE REPORT i-02/92, ARIZONA PUB' ? C SERVICE CO., PAID VERDE, UNIT 1 STEAM CENERATOR: 12 PACE:

4 0F 4

-ILCATION: ALL DATE:

07/27/92 CRITERIA: On TO 1004,PID,MAI,SAI TIME:

14:17:26 l

l j

l l

EXAM EXTENT l l

l l

l-CURRENT l

l ROW lLINlEXP #lLEClPROGRAMI ACTUAL l REM l REEL l PROBE l LOCATION l VOLTS l MIL lDECl % lCH l L._I _ I I - I

_t l_1 I

I I

I I

l __ I __ I l 99 l 162 l EX P 1 l 11 l 0111 - 0211 ] O111 02 H l l 00208 l 610RP l 0111+ 2.73 l 0.60l l

0l<20[18 l l111l162l l H lTEH-TSillTEll-TSillRPIl0020ol610RPlTSH- 0.92 l 3.30l l228lSAIl18 l l

l l

lC lTEC-TEHlTEC-TEHlRP1l00042l610ULlTSH- 0.85 l 0.80l l 93l 55l17 l

-l l

l lC lTEC TElllTEC TEHj l 00179 l 610ULlTsil-0.81 l 0.90l l 88lPIDjl7 l l 70l163lEXP 1l 11 lTEll-08ClTEll 08Cl l00096l6100ClVS5+ _ 1.14 l 0.80l l

0l 20l18 l l 88l163lEXP 1l H lTEH 08ClTEH-08Cl l00096l610UCl0811+ 0.90 l 0.80l l

0l 20l18 l-l 92l163lEXP lj H lTEH-08ClTEH-07Cl l00096l610UCl0811+ 0.73 l 0.90l l

0l 20l18 l-l 87l164lEXP ll 11 lTEH-08ClTEH 08C)

[00095l610UClEW1+

1.43 l 0.60l l.0[<20l18 l-

-l 88l165lEXP ll 11 lTEll-08ClTEll 07Cl l00095l610UClBW1+ 1.07 l 1.30l l

0] 25l18-l-l 76l157lEXP 1l li lTEll-08ClTEll 07Cl l00093l6100ClVS3+

1.00 l 1.30l l

0] 25l18 l-l 66l169ltXP ll H lT"H-08ClTEll 070) l 00090l 610UCl08114 0.60

[ 0.60l l '0l<20l18 l l 29l172lEXP ll 11 [TEll-07ClTEll 07Cj l 00086 l 610UC l 02tl+ 8.31 l 2.30j j

5l<20l 1 l l 80l173l l 11 lTEll-06 ;lTEll-06Cl l00086l610UClVS5+ 0.E5 l 0.?0l l.0l<20l13 l l 76l177; l C lTEC TEHlTEC-TElll l00010l610ULiO5C+ 0.30 l 0.70; l

0l<20118 l l 43l".82l lC lTEC TElllTEC-TElll l00008l6100LlVS4+ 0.70 l 1.70l l' 0l 25l18-l 3l184l lC lTEC 07tilTEC 07Hl l000021590ULl03C+ 0.46 l 1.50]

l Ol'26l18 l l 40l185l l C lTSC-TSClTSC-TSCl1;PIl00192 l 610RPlTSC+ 0.30 l12.00l-l 0l-69l18 l l

l l

l C lTEC-TEHlTEC-TElll

[00006 l 610VLlTSC4 0.26 l 4.80l l 97l 32l20 l l 46l185l l C l02C-03Cl02C-03Cl l00192l610RPj02C+ ?5.94 l 2.10l l

0l 23l18 l l

l l

[ C lTEC-TElllTEC TElll l00006l610ULl02C+ 35.81 l 1.20l l

0l 21l18-l l 39l186l lC l TEC-TElll TEC-TEH l l00006l610ULlTSC+ 0.33 l 3.50l l124l 31l20 l l

l l

lC lTSC-TSClTSC-TSClRPIj00192l610RPlTSC+

0.22' l 6.00l l

0l 48l18-l l 4]l87l l C lTEC-TElijTEC-TEHj l00179l610ULl02C-0.91 l 1.90l l

0l 21l18 l l 12l189l lC l TEC-TElll TEC-TElli l00179l610ULl05C+ 0.00 l 1.60l l

Cl<20l18.l l

1 1

I I

I l_I I

I I

I I

l_l l

NUMBER OF TUBES SELECTED FROM CURRENT OUTAGE:

132 NO TREND ANALYSIS REQUESTED REPORT OPTIONS:

Only examination results matching criteria are included MAP OPTIONS:

Plot data from current examination only l

l CONAM NUCLEAR, INC.

{

?

APPENDIX D

SUMMARY

DATA SHEETS MRPC i

n

'*it

$ 3.

,j r

CUMULATIVE REPORT i

02/92, ARIZONA'PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 STEAH GENERATOR: 11 PAGE:

1 OF 4

LOCATION: ALL DATE:

05/01/92 CRITERIA: PROBE = 610RP, INLET ONLY TIHE 09:26:37 EXAM EXTENT CURRENT ROW LIN HEAT #

LEG PROGRAM ACTUAL REM REEL PROBE LOCATION VOLTS HIL DEG CH 54 9

H 03H-03H 03H-03H 00088 610RP NDD H

02H-02H 02H-02H 00088 610RP NDD 1

01H-01H 01H-01H 00088 610RP NDD H

TSH-T5d TSH-TSH 00088 610RP NDD

-37 10 EXP 1 H

03H-03H 03H-03H 00088 610RP NDD H

02H-02H 02H-02H 00088 610aP NDD H

01H-01H 01H-01H 00088 610RP NDD H

TSH-TSH TSH-TSH 00088 610RP NDD 49 10 EXP 1 H

03H-03H 03H-03H 00088 610RP NDD H

02H-02H O2H-02H 00088 F10R5 NDD H

O1H-OlH 01H-01H 00083 6.vRP NDD H

TSH-TSi! TEH-TSH 00088 610RP NDD 54 11 EXP'l H

03H-03H 03H-03H 00088 610RP NDD H

02H-02H 02H-02H 00088 610RP NDD H

01H-01H 01H-01H 00088 610RP NDD H

TSH-TSH TEH-TSH 00088 610RP NDD 84 19 H

01H-01H 01H-01H 00088 610RP NDD 86 19 H

01H-01H 01H-01H 00098 610RP NDD 85 20 H

03H-03H 03H-03H 00086 610RP NDD H

02H-02H 02H-02H 00086 610RP NDD H

TSH-TSH TSH-TSH 00086 610RP NDD H

01H-01H 01H-01H 00086 610RP 0)F+

1.88 3.3 84 PLP 10 87 20 H

01H-01H 01H-01H 00088 610RP NDD 42 21 H

TSH-TSH TSH-TSH 00088 610RT NDD 48 21 H

TSH-TSH TSH-TSH 00088 610R NDD i

62 21 H

TEH-TSH TEH-TSH 00088 610RP NDD l-84 21 H

01H-01H 01H-01H 00086 610RP NDD 86 21 H

01H-01H 01H-01H 00086 610RP NDD 10 27 H

02H-02H 02H-02H 00115 610RP NDD 154 72 H

03H-03H 03H-03H 00086 610RP NDD H

01H-01H 01H-01H 00086 610RP NDD H

02H-02H 02H-02H 00086 610RP NDD H

TSH-TSH TEH-TSH RPI 00086 610RP TEH-1.34 10.0 241 MAI

'4 58 73 H

03H-03H 03H-03H 00086 610RP NDD i

l H

01H-01H 01H-01H 00086 610R9 NDD l

H TSH-TSH TSH-TSH 00086 610RP NDD H

02H-02H 02H-02H 00086 610RP NDD 70 73 H

03H-03H 03H-03H 00086 610RP NDD H

02H-02H 02H-02H 00086 610RP NDD l

H 01H-01H 01H-01H 00086 610RP NDD H

TSH-TSH TSH-TSH 00086 610RP NDD 59 74 H

TEH-TSH TEH-TSH 00086 610RP NDD 85 74 H

TSH-TSH TSH-TSH 00086 610RP NDD 42

-75 H

TSH-TSH TSH-TSH 00088 610RP NDD 85

'76 H

TSH-TSH TSH-TSH 00086 610RP NDD CONAM NUCLEAR, INC.

..n,.

. +

'h :

CUHULATIVE REPORT

)

02/92,: ARIZONA PUBLIC SERVICE CO.,

FALO VERDE, UNIT 1 i

STEAM GENERATOR: 11 PAGE:

2 0F

~4 LOCATION: ALL DATE:

05/01/92

-CRITERIA: PROBE = 610RP, INLET ONLY TIME:

09:26:37 EXAH EXTENT CURRLNT ROW LIN HEAT #

LEG PROGRAH ACTUAL REH REEL PROBE LOCATION VOLTS HIL DEG Cd 28 77 H

TSH-TSH TSH-TSH 00088 610RP NDD 38 77 EXP 1 H

03H-03H 03H-03H 00088 610RP NDD H

02H-02H 02H-02H 00088 610RP NDD

-H 01H-01H 01H-01H 00088 610RP NDD H

5'H-TSH TSH-TSH 00088 610RP NDD 62 77 H

TSH-TSH TSH-TSH 00115 610RP NDD 27 78 H

TE:f-TSH TEH-TSH 00088 610RP NDD 63 78 H

TSH-TSH TSH-TSH 00115 610RP NDD 50 79 H

TSH-TSH TSH-TSH 00115 610RP NDD 64 79 H

03H-03H 03H-03H 00086 610RP NDD H

02H-02H 02H-02H 00086 610RP NDD H

01H-01H 01H-01H 00086 610RP NDD H

TSH-TSH TSH-TSH 00086 610RP NDD 49 80 H

TSH-TSH TSH-TSH 00115 610RP NDD 58 81 H

TSH-TSil TSH-TSH 00115 610RP NDD 55 82 H

TSH-TSH TSH-TSH 00115 610RP NDD

-57 82 H

TSH-TSH TSH-TSH 00115 610RP NDD' H

TSH-TSH TSH-TSH 00115 610RP NDD 51 84 H

TSH-TSH TSH-TSH 00115 610RP UDD 60 85 H

TSH-TSH TSH-TSH 00115 610RP NDD 51 86 H

TSH-TSH TSH-TSH 00115 610RP NDD 61 86 P

TSH-TSH TSH-TSH 00115 610RP NDD 42 Sl? EXP 1 H

TSH-TSH TSH-TSH 00115 610RP NDD 55 90 H

TSH-TSH TSH-TSH 00115 610RP NDD 46 95 EXP 1 H

TSH-TSH TSH-TSH 00115 610RP NDD 48 95 EXPl1 H

TSH-TSH TSH-TSH 00115 610RP NDD

'75 98 H

TSH-TSH TSH-TSH 00115 610RP NDD 77 100 H

03H-03H 03H-03H 00086 610RP NDD H

02H-02H 02H-02H 00086 610RP NDD H

TSH-TSH TSH-TSH 00086 610RP NDD H

01H-G1H 01H-01H 00086 610RP NDD 48 103 EXP 1 H

TSH-TSH TSH-TSH 00115 610RP TSH-0.00 2.6 151 PLP 7

36 107 H-03H-03H 03H-03H 00086 610RP NDD E

02H-02H 02H-02H 00086 610RP NDD H

01H-01H 01H-01H 00086 610RP NDD H

TSH-TSH TEH-TSH RPI 00086 610RP TEH+

9.41to+ 13.74 1.0 58 MAI 17 2 119 H

TEH-TSH TEH-TSH 00086 610RP NDD 4 119 H

TSH-TSH TEH-TSH 00086 610RP NDD 6 119 H

TSH-TSH TSM-TSH 00086 610RP MDD

'28 121 EXP 1 H- 03H-03H 03H-03H 00086 610RP 5

NDD I

H 02H-02d 02H-02H 00086 610RP NDD H

01H-01H 01H-01H 00086 610RP NDD g

H TSH-TSH TSH-TSH 00086 610RP NDD 78 129 H

TSH-TSH TSH-TSH 00086 610RP NDD H

01H-0111 O1H-b1H 00086 610RP 01H+

1.65 17.9 358 BLI 4

CONAM NUCLEAR, INC.

r 1.

CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1

'STEAH GENERATOR: 11 PAGE:

3 OF 4

LOCATION: ALL DATE:

05/01/92 CRITERIA: PROBE = 610RP, INLET ONLY TIME:

09:26:37 I

EXAM EXTENT CURRENT ROW LIN HEAT #

LEG PROGRAH ACTUAL REH REEL PROBE LOCATION VOLTS HIL DEG CH 78 129 H

023-02H 02H-02H 00086 610RP 02H+

8.77 26.0 359 8LI 4

H 03H-03H 03H-03H 00086 610RP 03H+

3.56 14.4 359 ULI 4

60 131 H

03H-03H 03H-03H 00084 610RP NDD H

02H-02H O2H-02H 00084 610RP NDD H

01H-01H 01H-01H 00084 610RP NDD H TSH-TSal TSH-TSH 00084 610RP NDD H

04H-04H 04H-04H 00084 610RP 04H+ 10.86 1.2 0 <20 4

145 134 H

03H-03H 03H-03H 00084 610RP NDD i

H 02H-02H 02H-02H 00084 610RP NDD H

01H-01H 01H-01F 00084 610RP NDD H

TSH-TSH TEH-TSH RPI 00084 610RP TEH+ 21.94 3.6l 52 MAI 4

71 148 H

O1H-Old 01H-01H 00084 610RP NDD 73 148 H

01H-01H 01H-01H 00084 610RP NDD 70 149 H

01H-01H 01H-01H 00084 610RP NDD 72 149 H

03H-03H 03H-03H 00084 610RP NDD H

O2H-02H O2H-02H 00084 610RP MOD H

O1H-OlH 01H-01H 00084 610RP NDD H

TSH-TSH TSH-TSH 00084 610RP NDD q

74 149 H

01H-01H 01H-01H 00084 610RP NDD 71 150 H

01H-01H 01H-01H 00084 610RP NDD i

73 150 H

01H-01H 01H-01H 00084 610RP NDD 106 153 H

TEH-TSH TEH-TSH 00084 610RP NDD 106 155 H

TEH-TSH TEH-TSH 00084 610RP NDD 81 156 H

TEH-TSH TEH-TSH 00084 610RP NDD 58 159 EXP 1 H

02H-02H 02H-02H 00084 610RP NDD 60 159 EXP 1 H

02H-02H 02H-02H 00084 610RP NDD 3

37 160 H

O2H-02H 01H-02H 00088 610RP NDD 39 160 H

02H-02H 01H-02H 00088 610RP NDD 41 160 H

02H-02H 01H-02H 00088 610RP NDD 43 160 H

02H-02H 01H-02H 00088 610RP NDD 45 160 H

02H-02H 01H-02H 00088 610RP NDD l

55 160 EXP 1 H

02H-01F 01H-02H 00088 610RP NDD 57 160 EXP 1 H

02H-02H 02H-02H 00084 610RP NDD 59 160 EXP 1 H

03H-03H 03H-03H 00084 610RP NDD H

01H-01H 01H-01H 00084 610RP NDD H

TSH-TSH TSH-TSH 00084 610RP NDD H

02H-02H 02H-02H 00084 610RP NDD 61 160 EXP 1 H

02H-02H 02H-02H 00084 610RP NDD 58 161 EXP 1 H

02H-02H 02H-02H 00084 610RP NDD 60 161 EXP 1 H

02H-02H 02H-02H 00084 610RP NDD 56 181 H

TEH-TSH TEH-TSH 00084 610RP NDD CONAM NUCLEAR, INC.

fi;c CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO.,-PALO VERDE, UNIT 1 STEAM GENERATOR: 11-PAGEs-4 OP 4

-LOCATION: ALL DATES.

05/01/92 CRITERIA' PROBE = 610RP, INLET ONLY TIMES-09:26:37

NUMBER OF TUBES SELECTED FROM CURRENT OUTAGE:

75 ENO TREND ANALYSIS REQUFSTED REPORT OPTIONS:

Only examination results matching criteria are included I

CONAM NUCLEAR, INC.

~...., _..

~

Y

.*i CUMULATIVF. REPORT-02/92, ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 3

STEAM GENERATOR: 11 PAGE:

1 OF 14

-LOCATION: ALL' DATE:

05/01/92 CRITERIA: PROBE = 610RP, OUTLET ONLY TIME:

09:27:45 EXAM EXTENT CURRENT ROW LIN HEAT #

LEG PROGRAM ACTUAL REM REEL PROBE LOCATION VOLTS MIL DEG CH 4

3 C

02C-02C 02C-02C 00109 610RP NDD C

01C-01C 010-01C 00109 610RP NDD C

TSC-TSC TSC-TSC 00109 610RP NDD C

03C-03C 03C-03C RPI 00109 610RP 03C-0.92 16.8 0

53 4

32 3

C TSC-TSC TSC-TSC 00109 610RP NDD 31 4

C TSC-TSC TSC-TSC 00109 610RP NDD 33 4

C 02C-02C 02C-02C 00109 610RD NDD C

01C-01C 01C-01C 00109 610RP NDD C

TSC-TSC TSC-TSC 00109 610RP TSC+

0.71 10.3 32 PLP 10 35 4

C 02C-02C 02C-02C 00109 610RP NDD C

01C-01C 01C-01C 00109 610RP NDD C

TSC-TSC TSC-TSC 00109 610RP TSC+

0.53 11.5 211 PLP 10 37 4

C 02C-03C 02C-03C 00109 610RP NDD C

TSC-TSC TSC-TSC 00109 610RP TSC+

0.30 5.6 215 PLP 10 39 4

C 02C-03C 02C-03C 00109 610RP NDD C

01C-01C 01C-01C 00109 610RP NDD C

TSC-TSC TSC-TSC 00109 610RP NDD 32 5

C TSC-TSC TSC-TSC 00109 610RP NDD 34 5

C TSC-TSC TSC-TSC 00109 610RP TSC+

0.31 9.0 27 PLP 10 36 5

C TSC-TSC TSC-TSC 00109 610RP TSC+

0.25 3.6 216 PLP 10 40 5

C 02C-03C 02C-03C 00109 610RP NDD C

TSC-TSC TSC-TSC 00109 610RP TSC+

0.24 6.6 18 PLP 10 44 5

C 02C-03C 02C-03C 00109 610RP NDD 46 5

C 01C-01C 01C-01C 00109 61LRP NDD C

TSC-TSC TSC-ISC 00109 610RP NDD C

02C-03C 02C-030 00109 610P.P 02C+ 35.97 18.7 213 PLP 10 1

6 C

02C-02C 02C-02C 00109 610RP NDD C

01C-01C 01C-01C 00109 610RP NDD C

TSC-TSC TSC-TSC 00109 610RP NDD C

03C-03C 03C-03C 00109 610RP 03C-0.97 6.2 0

34 4

45 6

C 02C-03C 02C-03C 00110 610RP NDD l

47 6

C 02C-03C 02C-03C 00110 610RP NDD 49 6

C-020-03C 02C-03C 00110 610RP NDD 51 6

C 02C-03C 02C-03C 00110 610RP NDD C

01C-01C 01C-01C 00110 610RP NDD C

TSC-TSC TSC-TSC 00110 610RP NDD 8

7 C

02C-02C 02C-02C 00110 610RP NDD C

01C-01C 01C-01C 00110 610RP NDD i

C TSC-TSC TSC-TSC 00110 610RP Tsc+

0.56 12.6 29 PLP 10

-50 7

C 02C-03C 02C-03C 00110 610RP CDD 52 7

C 02C-03C 02C-03C 00110 610RP NDD 66 11 C- 01C-01C 01C-01C 00110 610RP NDD L

.68 11 C

01C-01C 01C-01C 00110 610RP NDD 70 11 C

01c-01C 01C-01C 00110 610RP NDD 65 12 C

01C-01C 01C-01C 00110 610RP NDD CONAM NUCLEAR, INC.

,m.

e CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 STEAM GENERATORt 11 PAGFs 2 OF 14 LOCATION: ALL DATE:

05/01/92 CRITERIA: PROBE = 610RP, OUTLET ONLY TIME:

09:27:45

~

EXAM EXTENT CURRENT ROW LIN HEAT #

LEG PROGRAM ACTUAL REM REPL PROBE LOCATION VOLTS HIL DEG CH 67 12 C

OIC-Olc 01C-01C 00110 610RP HDD I

C 02C-02C 02C-02C 00110 610RP NDD C

TSC-TSC TSC-TSC 00110 610RP NDD l

69 12 C

01C-01C 01C-01C 00110 610RP NDD 71 12 0

01C-01C 01C-01C 00110 610RP NDD l

66 13 C

01C-01C 01C-01C 00110 610RP NDD 68 13 C

02C-02C 02C-02C 00110 610RP NDD C

TSC-TSC TSC-TSC 00110 610RP HDD C

01C-01C 01C-01C 00110 610RP 01C+

1.03 11.3 37 PLP 10 70 13 C

03C-03C 03C-03C 00111 610RP NDD C

TSC-TSC TSC-TSC 00111 610RP NDD C

02C-02C 01C-02C 00111 610RP 01C+

0.81 2.4 190 PLP 10 C

02C-02C 01C-02C 00111 610RP 01C+

0.77 4.2 54 28 4

72 13 C

010-01C 01C-01C 00111 610RP NDD' 69 14 C

TSC-TSC TSC-TSC 00111 610RP NDD C

02C-02C 02C-02C 00111 610RP NDD C

01C-010 01C-01C 00111 610RP 01C+

1.04 7.3 155 29 4

C 01C-01C 01C-01C 00311 610RP 01C+

1.04 6.1 195 PLP 10 71 14 C ' 01C-01C OIC-Olc 00111 610RP NDD 66 15 C

OIC Olc OIC-Olc 00111 610RP NDD 68 15 C

OIC Olc 01C-01C 00111 610RP NDD 70 15 C

Oli Olc 010-01C 00111 610RP NDD 1

16 C

02C-02C 02C-02C 00111 610RP NDD C

01C-01C 01C-01C 00111 610RP NDD C-TSC-TSC TSC-TSC 00111 610RP NDD C

04C-04C 04C-04C 00111 610RP 04C+

1.00 9.2 0

22 4

18 C

02C-02C 02C-00114 610RP NDD C

03C-03C 03C-1:

00111 610RP NDD C

01C-01C 01C-01C 00111 610RP NDD C

TSC-TSC TSC-TSC 00111 610RP NDD l

C-04C-04C 04C-04C 00111 610RP 04C+ 0.92 5.1 127 <20 6

l 60 31 EXP 0 C

03C-03C 03C-03C 00124 610RP NDD C

02C-02C 02C-02C 00124 610RP NDD 62 31 EXP 2 C

03C-03C 03C-03C 00124 610RP "1D0 0

02C-02C C2C-02C 00124 610RP NDD 64f 31 EXP 2 C

03C-03C 03C-030 00124 610RP NDD C

02C-02c 02C-020 00224 610PP FDD 66 31 EXP 2 C

v3C-0?C 03C-03C 00124 610RP NDD l

C 02C-02C 02C-02C 00124 610RP NDD 68 31 EXP 2 0

03C-03C ^?O-03C 00124 610RP NDD l

C *' 02C w,

.c 00124 610RF NDD 70 31 EXP 2 C

03C 030 03C 00124 610RP' NDD C

'v40-02C 02C-02C 00124 610RP NDD 72 31 EXP 2 C

03C-03C 03C-03C 00124 610RP NDD C

02C-020 02C-02C 00124 610RP NDD d

CONAM NUCLEAR, INC.

.,___u,

l CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIS 1 STEAM GENERATOR: 11 PAGE:

3 OF 14 j

LOCATION: ALL DATE:

05/01/92 CRITERIA: PROBE = 630RP, OUTLET ONLY TIME:

09:27:45 EXAM EXTENT CURRENT ROW LIN HEAT #

LEG PRCCRAM ACTUAL REM REEL PROBE LOCATION VOLTS MIL DEG CH 76 31 EXP 2 C.

03C-03C 03C-030 00124 610RP NDD C

02C-02C 02C-02C 00124 610RP NDD l

76 31 RXP 2 C

03C-03C 03C-03C 00124 610RP NDD l

C 02C-02C 02C-02C 00124 610RP NDD 78 31 EXP 2 C

03C-03C 03C-03C 00124 610RP NDD C

02C-02C 02C-02C 00124 610RP NDD s

80 31 EXP 2 C

03C-030 03C-03C 00124 610RP NDD l

C 02C-02C 02C-02C 00124 610RP NDD 61 32 EXP 2 C

03C-03C 03C-03C 00124 610RP NDD C

02C-02C 02C-02C 00124 610RP NDD 63 32 EXP 2 C

03C-03C 03C-03C 00124 610RP HDD C

02C-02C 02C-02C 00124 610RP NDD 65 32 EXP 2 C

03C-03C 03C-03C 00124 610RP NDD C

02C-02C 02C-02C 00124 610RP NDD 67 32 EXP 2 C

03C-03C 03C-03C

. 00124 610RP NDD i

C 02C-02C 02C-02C 00124 610RP HDD I

69 32 EXP 2 C

03C-03C 03C-03C 00124 610RP 5

NDD C

02C-02C 02C-02C 10G124 610RP NDD 71 3 4 EXP 2 C

03C-03C 03C-03C 00124 610R*

NDD C

02C-020 02C-02C 00124 610RP NDD 73 32 EXP 2 C

03C-03C 03C-030 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 75 32 EXP.

C 02C-02C 02C-02C 00125 610RP NDD C

03C-03C 03C-03C 00125 610RP NDL 77 J2 EXP 2 0

03C-03C 03C-030 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 79 32 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDO 60 33 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 62 33 3XP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 64 33 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 66 33 EX? 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 68 33 EXP 2

_C 03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 70 33 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 72 33 EXP 2 C-03C-03C 03C-03C 00125 610RP BDA C

03C-03C 02C-02C 00125 610RP NDD C

03C-03C 03C-03C 00129 610RP NDD 74 33 EXP 2 C

03C-03C 03C-03C 00125 610RP ND9 0

02C-020 02C-02C 00125 610RP NDD l

l

\\

CONAM NUCLEAR, INC.

[

\\;

I

~

CUMULATIV2 REPORT e

02/92, ARIZONA PUDLIC SERVICE CO.,

PALO VERDB, UNIT 1 STEAM GENERATOR: 31 PAGE:

4 OF 14 LOCATION: ALL CATE:

05/01/92 CRITERIA: PROBE = 610RP, OUTLET ONLY TIME:

09:27:45 EZAH EXTENT CURRENT VOLTS lHILDEG ROW LIN HEAT #

LEO PROGRAM ACTUAL REM REEL PROF 1 LOCA710N CH 76 33 EXP 2 C

03C-03C 03C-03C 00125 6 4 0'.G HDD C

02C-020 02c-02C 00125 610RP PDD 78 33 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 80 33 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD I

61 34 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 63 34 EXP 2 C

03C-030 03C-03C 00125 610.tP NDD C

02C-02C 02C-020 00125 610RP NDD 65 34 EXP 2 C

03C-030

3C-03C 00125 610RP NDD L

02C-02C 02C-02C 00125 610RP HDD 67 34 EXP 2 C

03C-03C 03C-03C u0125 610RP NDD C

02C-02C 02C-020 00125 610HP NDD 69 34 C

03C-02C 01C-02C

'00111 610RP 01C+

9.33 2.4 325 PLP 7

71 34 C

01C-02C 01C-02C 00111 610RP 01C+

9.14 1.3 333 PLP 7

73 34 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-020 02C-02C 00125 610RP NDD

+

75 34 EXP 2 C

03C-03C 03C-C3C 00125 610RP NDD C

02C-02C 02c-02C 00125 610RP NDD 77 34 TXP 2 C

03C-03C 03C-03C 00125 610RP NDD 1

C 02C-02C 020-02C 00125 610RP NDD 79 34 EXP 2 C

03C-03C 03C-03c 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 60 35 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-020 00125 610RP NDD (2

35 EXP P C

03C-03C 03C-03C 00125 610RP NDD l C 02C-02C 02C-02C 00125 610RP NDD 64 35 EXP 2l C 03C-030 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 66 35 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 70 35 C

TSC-TSC TSC-TSC 00111 610RP NDD C

02C-02C 02C-020' 00111 610RP 02C-1.47 1.0 60 PVN 7

C 02C-02C 01C-02C 00111 610RP 01C+

9.32 5.9 168 PLP V

72 35 C

TSC-01C TSC-Olc 00111 610RP NDD C

01C-02C 01C-02C 00111 610RP NDD 74

.35 EXP 2 C

03C-030 030-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 76 35 EXP 2 C- 03C-03C 03C-030 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 78 35 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00129 610RP NDD 80 35 EXP 2 C

03C-03C 03C-03C 00125 610RP BDA C

03C-03C 02C-02C 00125 610RP WDD CONAM NUCLEAR, INC.

~

i

.v CUMULATIVE REPORT 02/92, ARIZONA PUBLIC %ERVICE CO.,

PALO VERDE, UNIT 1 STEAM GENERATOR: 11 PAGE:

S OF 14 LOCATION: ALL DATE:

05/01/92 CRITERIA: PROBE = 610RP, OUTLET ONLY TIME:

09:27:45 EXAM EXTENT CURRENT ROW LIN HEAT #

LEG PROGRAM ACTUAL REM REEL PROBE LOCATION VOLTS MIL DEC CH

~

~~~

~~~

~~

80 35 EXP 2

~~

03C-03C 03C-03C 00129 610RP NDD c

61 36 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 63 36 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C U2C-02C 00125 610RP NDD 65 36 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 67 36 EXP 2 C

03C-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD

^

69 36 C

01C-02C 01C-02C 00111 610RP NDD 71 36 C

01C-02C 01C-02C 00111 610RP NDD 73 36 EXP 2 C

03c-03C 03C-03C 00125 610RP NDD C

02C-02C 02C-02C 00125 610RP NDD 75 36 EXP 2 C

03C-03C 03C-03C 00126 61GRP NDD C

02C-020 02C-020 00126 610RP NDD 77 36 EXP 2 C

03C-030 03C-03C 00126 610RP NDD C

02c-02C 02C-02C 00126 610RP NDD 79 36 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 60 37 EXP 2 03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 62 37 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 64 37 EXP 2 C 03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 66 37 EXP 2 C

03C-030 03C-030 00126 610RP NDD C

02C-020 02C-02C 00126 610RP NDD 68 37 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 70 37 EXP 2 C

03C-03C 03C-030 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 72 37 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 74 37 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-020 00126 610RP NDD 76 37 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 78 37 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 80 37 EXP 2 C

03C-03C 03C-03C 00126 510RP NDD C

02C-02C 02C-02C

.00126 610RP NDD 61 38 EXP 2 C

03C-03C 03C-030 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD

.63 36 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-020 02C-020 00125l610RP NDD CONAM NUCLEAR, INC.

---Ceie.--4Iwe' w-ro-*

dW

+-

i

.v CUMU1hTIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO,,

PALO VERDE, UNIT 1 I

STEAM GENERATOR 11 PACE:

6 OF 14 LOCATION: ALL DATE:

05/01/92 CRITERIAs PROBE = 610RP, OUTLET ONLY TIME:

09:27:45 l

EXAM EXTENT CURRENT ROW LIN HEAT # LEG PROGRAM ACTUAL REM REEL PROBE LOCATION VOLTS MIL DEG CH

~~

65 38 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-020 00126 610RP NDD 67 38 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 69 38 EXP 2 C

03C-03r 03C-03C 00126 610RP NDD C

02C-020 02C-02C 00126 610RP NDD 71 38 EXP 2 C

03C-03C 03C-010 00126 610RP NDD C

02C-02C 02C-020 00126 610RP dDD 73 38 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-020 00126 610RP NDD 76 38 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

0,'C-02C 02C-02C 00126,610RP NDD e

77 38 EXP 2 C lP3C-030 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 79 38 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 60 39 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 62 39 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C-02C-02C 02C-02C 00126 610RP NDD 66 39 EXP 2 C

030-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 68 39 EXP 2 C

03C-03C 03C-03C 00126' 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 70 39 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 72 39 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-020 02C-02C 00126 610RP NDD 74 39 E::P 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 76 39 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 78 39 EXP 2 C

03C-03C 03C-03C 00126 610RP NDD C

02C-02C 02C-02C 00126 610RP NDD 80 39 EXP 2 C

03C-03C 03C-03C 00128 610RP NDD C

02C-020 02C-02C 00128 610RP NDD 61 40 EXP 2 C

03C-03C 03C-03C 00128 610RP NDD C

02C-02C 02C-02C 00128 610RP NDD 63 40 EXP 2 C

03C-03C 03C-03C 00118 610RP NDD C

02C-02C 02C-02C 00128 610RP NDD 65 40 EXP 2 C

03C-03C 03C-03C 00128 610RP NDD C

02C-02C 02C-02C 00128 610RP NDD 67 40 EXP 2 C

03C-03C 03C-03C 00128 610RP NDD C

02C-02C 02C-02C 00128 610RP 02C-1.20 1.5 44 PVN 4

4 69 40 EXP 2 C

02C-02C 02C-02C 00128 610RP NDD i

CONAM NUCLEAR, INC.

g g v'

w a-we s-w-w a

-p s--9a.4--r+-ea W----

.m

___.. - ~ _ _. _.

.... ~. - _ _ _ _. _. - _.. _ _

CUMULATIVE REPORT i

O2/92, ARIEONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1

+

STEAM OENERATOR: 11 PAGE:

7 0F 14 LOCATION: ALL DATE:

05/01/92 CRITER1h: PROBE = 610RP, OUTLET ONLY TIME:

09:27:45

~

EXAM EXTENT CURRENT ROW LIN HEAT #

LEG PROGRAM ACTUAL REM REEL PROBE LOCATION VDLTS MIL DEG CH 69 40 EXP 2 C

03C-03C 03C-030 00128 610RP 03C+

0.00 2.7 38 PVN 4

71 40 EYP 2 C

03C-030 03C-03C 00128 610RP HDD C

02C-02C 02C-02C 00128 610RP NDD 73 40 EXP 2 C

03C-03C 03C-03C 00128 610RP NDD C

02C-020 02C-02C 00128 610RP NDD 75 40 XP 2 C

03C-03C 03C-03C 00128 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD 77 40 EXP 2 C

03C-03C 03C-03C 00128 610RP NDD C

02C-12C 02C-02C 00128 610RP NDD 79 40 EXP 2 C

03C-03C 03C-03C 00128 610PP NDD C

02C-02C 02C-02C 00128 610RP 02C+ 0.00 7.2 224 PVN 4

1 70 C

02C-03C 02C-03C 00112 610RP NDD 3

70 C

02C-03C 02C-030 00112 610RP NDD 11 70 0

02C-03C 02C-03C 00116 610RP NDD 2

71 C

TSC-TSC TSC-TSC 00112 610RP NDD C

02C-03C 02C-03C 00112 610RP 02C+ 28.52to+ 40.90 1.0 103 PLP 10 0

01C-01C 01C-01C 00112 610RP 01C+

0.93 1.0 251 PLP 10 33 72 EXP 1 C

01C-02C 01C-02C 00114 610RP 01C+

0.59 2.2 128 <20 4

C 01C-02C 01C-020 00114 610RP 01C+

0.59 9.4 146 PLP 7

27 112 C

2SC-TSC TSC-TSC 00112 610RP NDD 24 113 C

TSC-TSC TSC-TSC 00112 610RP NDD 26 113 C

02C-020 02C-02C 00112 610RP NDD C

01C-01C 010-01C 00112 610RP NDD C

01C-CIC TSC-01C 00114 610RP TSC+

2.04 4.1

-17 PLP 10 C- 01C-01C TSC-Olc 00112 610RP TJC+

1.87 3.5 76 PLP 10 I

28 113 C

TSC-TSC TSC-TSC 00112 610RP NDD 23 114 C

TSC-TSC TSC-TSC 00112 610RP NDD 25 114 C

02C-02C 02C-02C 00112 610RP NDD C

/1C-01C 01C-01C 00112 610RP NDD C

01C-01C TSC-Olc 00112 610RP TSC+

2.22 3.0 257 PLP 10 C

01C-01C TSC-Olc 00112 610RP Tsc+

1.45 3.1 0 PLP 10 27 114 C

TSC-TSC TSC-TSC 00112 610Rp unn 24 115 C

TSC-TSC TSC-TSC 00112 610RP NDD 26 115 C

TSC-TSC TSC-TSC 00112 610RP TSC+

0.07 2.2 71 PLP 10 L

-70 135 EXP 2 C

03C-03C 03C-03C 00120 510RP NDD C

02C-02C 02C-02C 00120.10RP NDD 72 135 EXP 2 1C 03C-03C 03C-03C 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD 74 135 EXP 2 C

03C-030 03C-030 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD 76 135 EXP 2 C

03C-03C 03C-03C 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD 78 135 EXP 2 C

03C-030 03C '3C 00120 610RP NDD C

v2C-02C 02C-02C 00120 610RP NDD 80 135 EXP 2 C

03C-03C 03C-03C 00120 610RP NDD l-CONAM NUCLEAR, INC.

1.

i

.i..

,m.-.J.

CUMULATIVE REPORT 02/92, ARI2ONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 STEAM GENERATOR: 11 PAGE:

8 OF 14 LOCATION: ALL DATE:

05/01/92 CRITERIA: PROBE - 610HP, OUTLET ONLY TIME:

09:27:45

~~~I EXAM EXTE!IT'"

CURRENT ROW LIN HEAT #

LEO PROGRAM ACTUAL REM REF* PROBE LOCATION VOLTS MIL DEO

% ' CH 80 135 EXP 2 C

02C-02C 02C-02C 00120 610RP NDD 82 135 EXP 2 C

03C-03C 03C-03C 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD 84 135 EXP 2 C

03C-03C 03C-03C 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD 86 135 EXP 2 C

03C-03C 03C-03C 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD 88 135 EXP 2 0

03C-03C 03C-03C 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD E

90 135 EXP 2 C

03C-03C 03C-03C 00120 610RP NDU C

02C-02C 02C-02C 00120 610RP NDD 71 136 EXP 2 C

03C-03C 03C-03C 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD

'3 136 EXP 2 C

03C-03C 03C+03C 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP 02C+

0.18 0.9 34 PVN 17 C

02C-02C 02C-02C 00120 610RP 02"-

1.67 1.5 31 PVN 17 75 136 EXP 2 C

03C-03C 03C-03C 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD 77 136 EXP 2 C

03C-03C 03C-03C 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD 79l136 EXP 2 C

03C-03C 03C-03C 00120 610PP NDO C

02C-02C 02C-02C 00120 610RP NDD 81 136 EXP 2 C

03C-03C 03C-03C 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD 83 136 EXP 2 C

03C-03C 03C-03C 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD 85 I?G EXP 2 C

03C-03C 03C-03C 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD 87 136 EXP 2 C

02C-02C 02C-02C 00120 610RP NDD C

03C-01C 03C-03C 00120 610RP 03C-C,69 1.4 30 PVN 1

89 136 EXP 2 C

03C-03C 03C-03C 00120 610RP NDO C

02C-02C 02C-02C 00120 610RP NDD 70 137 EXP 2

vac-03C 03C-03C 00120 610RP NDD C

02 0-0';C 0? 02C 00120 610RP NDD 72 137 EXP 2 C

03C-03C 03C-03C 00120 610RP NDD x

C 02C '>2C 02C-02C 00120 610RP NDD 74 137 EXP 2 C

03r.03C 03C-03C 00120 610RP NDD C

L2C-02C 02C-02C 00120 610RP NDD i

76 137 EXP ~ c 03C-03C 03C-030 00120 610RP NDD C

02C-02C 02C-02C 00120 610RP NDD 78 137 EXP 2 C

03C-03C 03C-03C 00120 610RP NDD C

02C-020 02C-02C 00120 610RP NDD 80 137 EXP 2 C

03C-03C 03C-03C 00121 610RP 03C+

0.84 3.0 27 PVN 17 C

02C-02C 02C-02C 00121 610RP 02C-1.78 1.2 16 PVN 17 82 137 EXP 2 C

03C-03C 03C-03C 00121 610RP NDD CONAH NUCLEAR, INC.

g4 CUHULATIVE REPORT O2/92, ARIZONA PUBLIC SERV)CE CO.,

PALO VERDE, UNIT 1

+

STEAM GENERATOR: 11 PAGE:

9 OF 14 LOCATION: ALL DATE:

05/01/92-CRITERIA: PROBE = 610RP, OUILET ONLY TIME:

09:27:45 EXAM EXTENT CURRENT ROW LIN HEAT #

LEG PROGRAM ACTUAL REM REEL PRODE LOCATION VOLTS MIL DEG t

CH 02 137 EXP 2 0

02C-02C 02C-02C 00121 610RP LJL 84 137 EXP 2 C

03C-03C 03C-03C 00121 610RP NDD C

02C-02C 02C-02C 00121 610RP NDD 86 137 EXP 2 C

03C-03C 03C-03C 00121 610RP NDD C

02C-02C 02C-02C 00121 610RP NDD

[

88 137 EXP 2 C

03C-030 03C-03C 00121 610RP NDD C

02C-02C 02C-02C 00121 610RP NDD 90 137 EXP 2 C

03C-03C 03C-03C 00121 610HP NDD C

02C-020 02C-02C 00121 610RP NDD 71 138 EXP 2 C

03C-03C 03C-03C 00221

$10kP NLD C

02C 02C 02C-02C 00121 610RP NDD 73 138 EXP 2 C

C3C-030 03C-030 00121 610RP NDD C

02C-02C 02C-020 00121 610RP NDD 7B 130 EXP 2 C

03C-03C 03C-03C 00121 610RP NDD C

02C-02C 02C-02C 00121 610RP 02C+

5.04 2.0 12 PVN 17 77 138 EXP 2 C

03C-03C 03C-03C 00121 610RP NDD C

0;C-02C 02C-02C 01121 610RP NDD 79 138 EXP 2 C

03C-030 03C-03C 00121 610RP NDD C

02C-v2C 02C-02C 100121 610RP NDD 81 138 EXP 2 C

03C-03C 03C-03C 20121 610RP NDD C

02C-02C 02C-02C 00121 610RP NDD 83 138 EXP 2-C 030-03C 03C-03C 00121 610RP NDD C

02C-02C 02C-020 00121 610RP 02C-4.46 1.3 10 PVN 17 85 138 EXP 2 C

03C-03C 03Co03C 00121 610RP NDD C

02C-02C 02C-020 00121 610RP NDD 07 138 EXP 2 0

03C-03C 03C-03C 00121 610RP NDD i

C 02C-02C 02C-02C 00121 010RP NDD l

89 138 EXP 2 C

03C-03C 03C-03C 00121 610RP HDD C

02C-020 02C-02C 00121.10RF NDD 70 139 EXP 2 C

03C-03C 03C-03C 00121 610RP NDD C

02C-02C 02C-02C 00121 610RP NDD I

72 139 EXP 2 C

03C-03C 03C-030 00121 610RP NDD C

02C-02C 02C-02C 00121 610RP NDD 74 139 EXP 2 C

03C-030 03C-03C 00121 610RP NDD C

02C-02C 02C-02C 00121 610RP NDD 76 139 EXP 2

_C 03C-03C 03C-03C 00121 610RP NDD C

02C-02C 02C-02C 00121 610RP NDD 78

.;9 LEXP 2 c.

03C-03C 03C-030 00121 610RP NDD C

02C-02C 02C-02C 00121 610RP NDD 80 139 EXP 2 0

03C-03C 03C-03C 00121 610RP NDD C

02C-02C 02C-02C 00121 610RP NDD 82 139 EXP 2 C

03C-03C 03C-030 00121 610RP NDD C

02C-02C 02C-02C 00121 610RP NDD

.84 139 EXP 2 C

03C 03C 03C-030 00121 610RP NDD C

02C-02C 020-020 00121 610RP NDD d

CONAM NUCLEAR, INC.

n

?

...~-o.-

~

.., c d.=

w.,.'..

.s

.. ~.

, - ~ ~.

e._..i~,,m_+

_ _ ~ _ _ -

.-__m..

CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE Co., PALO VERDE, UNIT 1 STEAM GENERATOR: 11 PAGE:

10 OF 14 LOCATION: ALL DATE:

05/01/92

-CRITERIA: PRODE = 61GnP, OUTLET ONLY TIME:

09:27:45 EXAH EXTENT CURRENT ROW LIN HEAT #

LEG PROGRAM ACTUAL REM REEL PROBE LOCATION VOLTS MIL DE0! %

CH 86 139 EXP 2 C

03C-030 03C-03C 00121 610RP NDD C

02C-02C 02C-02C 00121 610RP NDD 68 139 EXP 2 C

03C-03C 03C-03C 00121 610RP NDD 1

C 02C-02C 02C-02C 00121 610RP NDD 90 139 EXP 2 C

03C-03C 03C-03C 00121 610RP NDD

'l C

02C-02C 02C-02C 00121 610RP NDD 71 140 EXP 2 C

03C-03C 03C-03C 00122 610RP NDD C

02C-02C 02C-02C 00122 610RP NDD 73 140 EXP 2 C

03C-03C 03C-03C 00122 610RP NDD C

02C-02C 02C-02C 00122 610RP NDD 7E 140 EXP 2 C

03C-03C 03C-03C 00122 610RP NDD C

02C-02C 02C-02C C0122 610RP NDD 77 140 EXP 2 C

03C-03C 03C-03C 00122 610RP HDD 0

02C-02C 02C-02C 00122 610RP NDD i

79 140 EXP 2 C

03C-03C 03C-03C 00122 610RP NDD C

02C-02C 02C-02C 00122 610RP NDD 81 140 EXP 2 C

03C-03C 03C-03C 00122 610RP NDD C

02C-02C 02C-02C 00122 610RP NDD 85 140 EXP 2 C

03C-03C 03C-030 00122 610RP NDD C

02C-02C 02C-02C 00122 610RP NDD 87 140 FXP 2 C

03C-03C 03C-03C 00122 610RP NDD C

02C-02C 02C-02C 00132 610RP NDD 89 140 EXP 2 C

03C-03C 03C-03C 00122 610RP NDD C

02C-02C 02C-02C 00122 610RP NDD 70 141 EXP 2 C

03C-03C 03C-03C 00122 610RP NDD

-C 02C-02C 02C-02C 00122 610RP NDD 72 141 EXP 2 C

03C-03C 03C-03C 00122 610RP NDD C

02C-02C 02C-02C 00122 610RP NDD 74 141 EXP 2 C

03C-03C 03C-03C 00122 610RP NDD C

02C-02C 02C-02C 00122 610RP NDD a

76 141 EXP 2 C

03C-03C 03C-03C 00122 b10RP NDD C

02C-02C 02C-02C 00122 610RP NDD 78 141 EXP 2

-C 03C-03C 03C-03C 00122 610RP NDD C

02C-02C 02C-02C 00122 610RP NDD i

80 141 EXP 2 C

03C-030 03C-03C 00122 610RP NDD

'C 02C-02C 02C-02C 00122 610RP

.sDD 82 141 EXP 2 C

03C-03C 03C-03C 00122 610EP NDD C

02C-02C 02C-02C 00122 610RP NDD 84 141 EXP 2 C

03C-03C 03C-03C 00122 610RP NDD C

02C-02C 02C-02C 00122 610RP NDD

-86 141 EXP 2 C

03C-030 03C-03C 00122 610RP NDD C

02C-02C 02C-02C 00122 610RP NDD 88 141 EXP 2 C-03C-03C 03C-03C 00122 610RP NDD C

02C-02C 02C-02C 00122 610RP NDD 90 141 EXP.2.c 03C-03C 03C-030 00122.610RP NDD I

CONAM NUCLEAR,-INC.

os.

~..

~

f CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 STEAM GENERATOR: 11 PAGE:

11 OF 14 LOCATION: ALL DATE:

05/01/92 CRITERIA: PROBE = 610RP, OUTLET ONLY TIME:

09:27:45 RO:tlLIN IIEAT#

EXAM EXTENT CURRENT LEG PROG RAM ACTUAL REM REEL PROBE LOCATION VOLTS MIL DEG' s CH 90 141 EXP 2 C 02C-02C 02C-02C 00122 610RP NDD 71 142 EXP 2 C

03C-03C 03C-03C 00122 610RP NDD C

02C-02C 010-02C 00122 bA0RP NDD 73 142 EXP 2 C

03C-03C 03C-03C 00122 610RP NDD C

02C-020 02C-020 00122 610RP HCJ 75 142 EXP 2 C

03C-03C 03C-03C 00122 610RP NDD C

03C-03C 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 77 142 EXP 2 C

02C-02C 02C-02C 00122 610RP NDD C

03C-03C 03C-O:C 00322 610RP 03C+

0.46 1.9 195 PVA 17 79 142 EXP 2 C

03C-03C 03C-03C 00122 610RP NDD C

02C-02C 02C-02.

00122 610RP NDD 01 142 EXP 2 C

03C-03L 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 83 142 EXP 2 C

03C-03C 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 85 142 EXP 2 C

03C-03C 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 87 142 EXP 2 C

02C-03C 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00:23 610RP NCD 89 142 EXP 2 C

03C-03C 03C-03C 00123 610RP N7D C

02C-02C 02C-02C 00123 610RP NDD 70 143 EXP 2 C

03C-03C 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 72 143 EXP 2 C

03C-030 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 74 143 EXP 2 C

03C-03C 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 76 143 EXP 2 C

03C-030 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 78 143 EXP 2 C

03C-03C 03C-Osc 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 80 143 EXP 2 C

03C-030 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 82 143 EXP 2 C

03C-03C 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 84 143 EXP 2 C

03C-03C 03C-03C 03123 610RP NDD C

^2C-02C 02C-02C 0G123 610RP NDD 86 143 EXP 2 C

03C-03C 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 88 143 EXP 2 C

03C-03C 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 90 143 EXP 2 C

03C-03C 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 71 144 EXP 2 C

03C-03C 03C-03C 60123 610RP NDD CONAM NUCLEAR, INC.

9

.e CUHULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1

-STEAM GENERATOR: 11 PAGE:

12 OF 14 LOCATION: ALL DATE:

05/01/92 CRITERIA: PRODE = 610RP, OUTLLT ONLY TIME:

09:27:45 l

EXAM EXTENT CURRENT ROW LIN HEAT #

LEG PROGRAM ACTUAL REM REEL PROBE LOCATION VOLTS MIL DEG CH 71 144 EXP 2 C

02C-02C 02C-02C 00123 610RP NDD 73 144 EXP 2 0

03C-03C 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 75 144 EXP 2 C

03C-03C 03C-030 00123 610RP NDD C

02C-02C 02C-02C 00123 6*0RP NDD 02C-02Cl 77 144 EXP 2 C

02C-02C 00123 610RP NDD C

03C-03C 03C~030 00123 610RP 03C-0.45 1.0 39 PVN 17 79 144 EXP 2 C 03C-03C 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD 81 144 EXP 2 C

03C-03C 03C-03C 00123 610RP NDD C

02C-020 02C-02C 00123 610RP NDD 83 144 EXP 2 C

03C-03C 03C-03C 00123 6',0RP NDD C

02C-02C 02C-02C 00123 610RP HDD 85 144 EXP 2 C

03c-030 03C-03C 00123 610RP-NDD C

02C-020 02C-02C 00123 610RP NDD 87.144 EXP 2 C

03C-030 03C-03C 00123 610RP NDD C

02C-02C 02C-02C 00123 610RP NDD l

89 144 EXP 2 C

03C-03C 03C-030 00123 610RP NDD C

02C-02C 02C-OPC 00123 610RP NDD 70 145 EXP 2 0

02C-02C 02C-02C 00123 610RP N9D C

03C-03C 03C-03C 00123 610RP 03C-0.61 0.8 32 PVN 17 72 145 EXP 2 C

03C-03C 03C-030 00124 610RP NDD C

02C-02C 02C-02C 00124 610RP NDD C

03C-03C 03C-03C 00128 610RP NDD C

02C-02C 02C-0?C 00128 610RP NDD 74 145 EXP 2 C

03C-03C 03C-C3C 00124 610PP NDD C

02C-02C 02C-02C 00124 610RP NDD C

03C-03C 03C-03C 00126 6?ORP NDD C

02C-02C 02C-020 00128 610RP NDD 76 145 EXP 2 C

03C-0 ' 03C-03C 00124 610RP.

NDD C

02C-02C 02C-02C 00124 610RP NDD

[

C 03C-03C 03C-03C 00128 610RP NDD C

02C-02C 02C-02C 00128 610RP NDD 78 145 EXP 2 C

03C-03C 03C-03C 00124 610RP NDD C

02C-02C 02C-02C 00124 610RP NDD l

C 03C-03C 03C-030 00128 610RP NDD

-C 02C-02C 02C-02C 00128 610RP NDD 80 145 EXP 2 C

03C-030 03C-03C 30124 610RP NDD C

02C-02C 02C-02C 00124 610RP NDD C

03C-03C 03C-03C 00128 610RP NDD C

02C-02C 02C-02C 00128 610RP NDD

-82 145 EXP 2 C

03C-03C 03C-03C 00124 610RP NDD C

02C-02C 02C-02C 00124 610RP NDD C

03C-03C 03C-03C 00128 610RP NDD C

02C-C2C 02C-02C 00128 610RP NDD CONAM NUCLEAR, INC.

.. ~ -. - - _.~ -

.... ~ - - - -

e CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 STEAM GENERATOR: 11 PAGE:

13 OF 14 LOCATION: ALL DATE:

05/01/92 CRITERIA: PRODE = 610RP, OUTLET ONLY TIME:

09:27:45 EXAM EXTENT CURRENT ROW LIN HEAT /

LEG PROGRAM ACTUAL REM REEL PROBE LOCATION VOLTS MIL DEG CH 84 145 EXP 2 C

03C-03C 03C-03C 00124 610RP NDD C

02C-020 02C-02C 00124 610RP NDD C

03C-030 03C-030 00128 610RP NDD C

02C-020 02C-02C 00128 610RP NDD 86 145 EXP 2 C

03C-03C 03C-03C 00124 610RP NDD C

02C-02C 02C-02C 00124 610RP NDD C

03C-03C 03C-03C 00128 610RP NDD C

02C-02C 02C+02C 00128 610RP NDD

[

88 145 FXP 2 C

03C-03C 03C-03C 00124 610RP NDD C

02C-02C 02C-02C 00124 610RP HDD l

C 03C-03C 03C-03C 00128 610AP NDD C

02C-02C 02C-02C 00128 610RP NDD 90 14b EXP 2 C

03C-13C 03C-03C 00124 610RP NDD C

O'C-t2C 02C-02C 00124 610RP NDD C

03C-030 03C-03C 00128 610RP NDD C

02C-020 02C-02C 00128 610RP NDD 1

158 C

02C-03C 02C-03C 00114 610RP NDD 2

159 C

02C-03C 020-03C 00114 610RP NDD 1 J60 C

02C-03C 02C-03C 00114 610RP NDD

[

C 01C-01C 01C-010 00114 610RP NDD C

TSC-TSC TSC-TSC 00134 610RP NDD

+

3 160 C

02C-03C 02C-03C 00114 610RP Nr3 2

161 C

02C-03C 02C-03C 00114 610RP 03C+

2.96 1.6 296 PLP 7

1 162 C

02C-03C 02C-03C 00114 610RP 03C+

2.30 3.0 115 PLP 7

4 1

166 C

02C-02C 02C-02C 00114 610RP NDD C

01C-01C Olc-Olc 00114 610RP NDD C

TSC-TSC TSC-TSC 00114 610RP NDD 51 182 C

TSC-TSC TSC-TSC 00116 610RP NDD 53 182 C

TSC-TSC TSC-TSC 00116 610RP TSC+

0.55 8.4 154 PLP

.7 55 180 C

TSC-TSC TSC-TSC 00116 610RP TSc+ 0.70 12.8 154 PLP 7

48 183 C

TSC-TSC TSC TSC 00116 610RP NDD 50 183 C

TSC-TSC TSC-TSC 00116 610RP NDD 52 183

-C 02C-02C 02C-02C 00116 610RP NDD C

01C-010 01C-010 00116 610RP NDD y

C TSC-TSC TSC-T*o 00116 610RP TSC+

0.57 10.1 330 PLP 7

54 183 C

020-02C 02C-02C 00116 610RP NDD

~

C 01C-01C 01C-01C 00116 610RP

, NDD 2

C TSC-TSC TSC-TSC 00116 610RP TSC+

0.21 10.5 156 PLP

-7 47 184 C

TSC-TSC TSC-TSC 00116 610RP TSC+

1.77 5.3 320 PLP 7

l 49 184 C

02C-02C 02C-02C 00116 610RP NDD C

01C-01C 01C-01C 00116 610RP NDD C

TSC-TSC TSC-TSC 00116 610RP TSC+

2.25 4.7 138 PLP 7

.C 01C-01C TSC-010 00119 610RP TSC+

1.50 4.7 144 PLP 7

C TSC-TSC TSC-TSC 00116 610RP TSC+

0.30 7.2 341 PLP 7

51 184

-C 02C-02C 02C-02C

' 00116 610RP NDD CONAM NUCLEAR,.INC.

f

.I

. -. - -. ~.

_ - -=

n. _.

CUMULATIVE REPORT 02/92, ARIEONA PUBLIC S2RVICE Co., PALO VERDE, UNIT 1 STEAM CENERATOR: 11 PAGE:

14 OF 14 LOCATION: ALL DATE:

05/01/92

' CRITERIA: PROBE = 610RP, OUTLET ONLY TIME:

09: 27:45 l~

EXAM EXTENT CURRENT ROW LIN HEAT #

LEG PROGRAM I ACTUAL REM REEL PROBE LOCATION VOLTS MIL DEG CH

.51 184 C

01C-010 01C-01C 00116 610RP NDD C

TSC-TSC TSC-TSC 00116 610RP TSC+

0.36 8.5 156 PLP 7

32 485 C

TSC-TSC TSC-TSC 00116 610RP NDD 34 185 C

TSC-TSC TSC-TSC 00116 610RP NDD 36 185 C

TSC-TSC TSC-TSC 00116 610RP NDL 46 185 C

TSC-TSC TSC-TSC 00116 610RP TSC+

1.04 3.7 139 PLP 7

31 186 C

TSC-TSC TSC-TSC 00116 610RP NDD 33 186 C

02C-02C 02C-02C 00116 610RP NDD C

01C-01C 01C-01C 00t16 610RP 01C-1.13 3.8 151 PLP 7

C TSC-TSC TSC-TSC 00116 610RP TSC+

0.41

  • 4 0 <20 6

C TSC-TSC TSC-TSC 00116 610RP TSC+

0.41 330 PLP 7

35 186 C

02C-02C 02C-02C 00116 610RP NDD C

01C-01C 01C-01C 00116 610RP Olc-1.08 2.2 135 PLP 7

C TSO-TSC TSC-TSC 00116 610RP TSC+

1.14 12.6 140 PLP 7

C TSC-TSC TSC-TSC 00116 610RP TSC+

1.05 2.1 0 <20 4

37 186 C

TSC-TSC TSC-TSC 00116 610RP NDD 32 187 C

TSC-TSC TSC-TSC 00116 616RP Tsc+ 0.22 3.2 322 PLP 7

NUMBER OF TUDES SELECTED FROM CURRFNT OUTAGE:

297 NO TREND ANALYSIS REQUESTED REPORT OPTIONS:

Only examination rs.eults me.tching criteria are included l

CONAM NUCLEAR,:INC.

=

e

,,-,--,r.

.e-

..,s

,e

-nn,

.-,-.--.--..-~~_-~...--=---._.._-_-..~-.-..--.a...

.e 6

CUMULATIVE REPORT 4

02/92, ARIEONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1

- STEAM OENERATOR: 12 PAGE:

1 0F 6

LOCATION: ALL DATE:

05/01/92 CRITERIA: PROBE = 610RP, INLET ONLY TIME:

09:35:40 PROGRAM l ACTUAL lP8rM EXAM EXTENT CURRENT ROW LIN EXP #

LEO REEL PROBE LOCATION VOLTS MIL DEG CH 3

7

~II~ 01H-02H 01H-02H

~

E0181 610RP NDD

~

~

~

j H

TSif-TSil TSH-TSH 00181 610RP NDD 39 4

11 01H-02H 01H-02H 00181 610RP NDL H

Tsfl-TSH TSil-TSil 00181 610RP NDD j

s0 5

11 01H-0211 0111-02 H 00181 610RP NDD 11 TSil-TSH TSil-TSH 00181 610RP NDD 23 6 EXP 1 11 02H-02H 02H-02H 00181 610RP HDD 11 01H-01H 01H-01H 00181 610RP NDD 11 TEll-TSH TSH-TSH 00181 610RP

!!DD i

il TEH-TSH TEH-TSH RIC 00184 610RP NDD 11 12 EXP 1 11 02H-02H 02H-02H 00181 610RP NDD 11 01H-0111 0111-01H 00181 610RP NDD H

TSH-TSH TSH-TSH 00181 610RP NDD TSi -TSH 00208 610RP NDD 5

20 11 TSil-TSil t

65 34 11 02H-02H 02H-02H 00181 610RP NDD H

01H-01H 01H-01H 00181 610RP NDD TSH-TSH TSH-TSit 00181 610RP NDD 82 37 H

O2H-02il 02H-02H 00181 610RP NDD ll 01 H-0111 01;f-01H OM81 610RP NDD H

TSH-TSH TSil-TSH 00181 6103P UDD 11 38 EXP 1 H

TEH-TSH TEH-TSH 00181 610RP NDD 12 39 EXP 1 11 TEll-TSH T5tH-TSH 00181 610RP NDD 20 39 EXP 1 H

TEH-T5H TEH-TSH 00181 610RP NDD 35 42 EXP 1 H

TEH-TSil TEH-TSH 00181 610RP NDD 40 43 EXP 1 H

TEH-TSH TFH-TSH 00181 610RP NDD 41_

44 EXP 1 H

TEH-TSH TEH-TSH 00181 610RP NDD 46 45 EXP 1 H

TEH-TSH TEH-TSH 00181 610RP NDD 25 48 EXP 1 0211-02 H 02H-02H 00181 610RP NDD H

01H-01H 01H- 01H 00181 610RP NDD 11 TSH-TSH TSH-TSH 00381 610RP NDD 93 56 H

06H-0711 06H-07H 00181 610RP NDD H

TSil-TSil TSH-TSH 00181 610RP NDD 95 56 H

06H-07H 06H-07H 00208 610RP NDD H

TSH-TSH TSH-TSH C6200 610RP NDD 92 57 H

0611-07H 06H-07H 00184 610RP NDD H-TSH-TSH TSH-TSH 00184 610RP NDD 94 57 H

06H-07H 06H-07H 00184 610RP NDD H

02H-02H 02H-02H 00184 610RP NDD 01H-01H 01H-01H 00iB4 610RP NDD u

i TSH-TSH TSH-TSH 00164 610RP NDD

+

96 57 h

OUH-07H ')6H-07H 00184 610RP NDD

[

H TSH-TSH TSH-TSH 00184 610RP NDD 93 58 H

06H-07H 06H-07H 00184 610RP NDD H

TSH-TSH T8H-TSH 00184 610RP NDD 95 158 H

06H-07H 06H-07H 00184 610RP NDD l

CONAM NUCLEAR, INC.

l l

y.--=-

im4sw--g g

y.pwgi-g-e-nm

=--.

y-p

,isy y

ert--

aaev y =

6 CUMULATIVE REPORT i

i D2/92, ARIZONA PUDLIC SERVICE CO.,

PALO VERDE, UNIT 1-STEAM GENE.:ATOR: 12 PA0Es 2 OF 6

LOCATION: ALL DATE:

05/01/92 CRITERIA: PROBE = 610RP, INLET ONLY TIMEt 09:35:40 REM l REEL EXAM EXTENT CURRENT ROW LIN EXP #

LEG PROGRAM ACTUAL PROBE LOCATION VOLT 8 MIL DEG CH 95 58 H

TSH-TSH TSH-TSH 00184 610RP IIdD

~

37 60 L'XP 1 11 02H-0211 0?H-0211 00184 610RP NDD H

0111-01H 01H-01H 00184 610RP NDD 11 TSH-TSH TSH-TSH 00184 61CRP NDD l

42

,,1 EXP 1 H

02H-02H 0211-02H 00184 610RP Hl/D 11 01H-01H 0111-01H 00184 610RP NDD H

TSii-TSH TSil-TSH 00184 610RP NDD 63 62 EXP 1 H

0211-02H 02H-02H 00184 610RP MDD H

Olli-O1H 0111-01H 00184 610RP NDD TSH-TSil TSH-TSH 00184 610RP NDD 41 64 EXP 1 H

02H-0211 02H-02H 00184 610RP NDD H

01H-01H 01H-01H 00184 610RP NDD H

TSH-TSH TSH-TSH 00184 610ttP NDD 111 66 H

0211-02 H 02 H-0211 00184 610RP NDD 11 01H-0111 01H-01H 00184 610RP NDD H

TSil-TSH TSli-TSH 00184 610RP NDD 40 67 EXP 1 H

0211-02 H 02H-02H 00184 610RP NDD H

0111-01H OIH-01H 00184 610RP NDD H

TSH-TSH TSH-TSH 00184 610RP NDD 46 67 EXP 1 H

02H-02H 02H-02H 00184 610RP NDD 11 01H-0111 01H-01H 00184 610RP NDD 11 TGil-TSH TSH-TSH 00184 610RP NDD 87 72 EXP 1 H

TEH-TSH TEti-TSH 00386 610RP NDD 88 73 EXP 1 H

TEH-TSH TEH-TSH 00186 610RP NDD 87 74 EXP 1 H

TEH 'tdH TF11-TS!!

00186 610RP NDD 89 74 EXP 1 H

TEH-TSH TEH-TSH 00186 610RP NDD 30

'75 EXP 1 h

02H-02H OMi-02H 00*84 610RP NDD H

01H-01H 01H-01H 00136 610RP NDD H

TSH-TSH TLH-TSH 00186 610RP NDD l

87 76 EXP 1 H

TEH-TSil TSH-TSH 00196 610RP NDD H

TEH-TSH TEH-TSH RIC 00208 610RP NDD 155 76L 11 03H-04H 03H-04H 00208 610RP NDD H

TSH-TSH TSH-TSH 00208 610RP NDD 156 77 H

03H-04h 03H-04H 00186 610RP NDD l

H TSP-TSH TSH-TSH

' 00186 610RP NDD l

61 78 EXP 1 H

021:-02H 02H-02rl 00186 610RP NDD l:

H' 01H-01H 01H-01H 00186 610RP NDD j

TSH-TSH TSH-TSH 00186 610RP NDD l

157

'78 H

03H-04H 03ff-04H 00186 610RP NDD l

11 02H-02H 02H-02H 00186 610RP NDD l-11 01H-01H 01H-01H 00186 610RP NDD L

H TSH-TSH TSH-TSH 00186 610RP NDD 48.79 EXP 1 H

02H-02H 0211-02H 00186 610RP NDD H

01H-01H 01H-01H 00186 610RP NDD I

H TSH-TEH TSH-TSH 0018C 610RP NDD 1

i 1-l CONAM NUCLEAR, INC.

l.

i g

.,-+-

.g y.

m.

,.,,y.yg m

.o.,..,._y..

...g,,,,_

,m'cm.,.u_,.,,,,

,u.

,,r,

i a

.s CJHULi.TIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 STAAH GENER!< TOR: li PAGE:

3 OF 6

LOCATION: ALL DATE:

05/01/92 i

CRITERIA: PROBE - 610RP, INLET ONLY TIMES 09:35:40 f

EXAH EXTENT CURRENT ROW LIN EXP #

LEG PROGRAM ACIUAL REM REEL PROBE LOCATION VOLTS HIL DEG O

CH 156 79 H

03fi-04H 03H-04H 00208 610RP NDD 11 TS}l TSH Tsil-TSH 00208 610RP NDD 29 80 11 0211-02 H 02H-02H 00186 610RP NDD H

01H-01H 01H-01H 00186 610RP NDD H

TEH-TSH TSH-TSil 00186 610RP NDD H

TEll-TSH TEH-TSH RPI 00208 610RP TSH-0.88 3.1 107 SAI 5

157 80 11 03H-04H 03H-04H 00208 610RP NDD H

TSH-TSH TSH-TSH 00208 610RP NDD 30 81 H

TEll-TSil TEH-TSH 00186 610RP NDD 90 85 EXP 1 H

0211-02 H 02H-0211 00186 610RP NDD H

0 11 - 0 111 01H-0111 00186 61DRP NDD H

TSil-TSH TSH-TSH OC186 610RP NDD 44 91 H

06H-0711 06H-0711 00213 6AORP NDD H

0$H-06H 05H-06H 00213 610RP NDD H

04 H-0511 04H-05H 00213 610RP NDD 11 03H-04H 03H-04H 00213 610RP NDD H

02H-03H 02H-03tl 00213 610RP NDD 11 0 5.Il-02 H 01H-0211 00213 610RP NDD 11 TSH-0111 TSH-O1H 00223 610RP NDD 11 TEll-TSH TE!!-TSH RPI 0021.

610RP TEH-0.00 2.9 46 SAI

~3 43 92 H

06H-0711 06H-07H 00214 610RP NDD 11 05H-0611 0511-06H 00214 610RP NDD H

04H-0511 04H-05H 00214 610RP 1;DD r

H 0311-04 H 03H-04H 00214 611RP NDD H

0211- 0311 02H-03H 00214 610RP NDD H

0 111- 0211 01H-02H 00214 610RP NDD 11 TSH-01H TSH-O1H 00214 610RP NDD H

TEll-TSH TEH-TSil 00214 610RP NDO H

TEH-TSli TEH-TEH 00216 610RP NDD 111 98 11 02H-02H 02H-02H 00202 610RP NDD 11 0111-01H 0 111- 0 111 002; 610RP NDD H

TSH-TSH TSH-TSH 00202 610RP NDD 145 100 EXP 1 H

TEll-TSH TSH-TS!!

00202 610RP NDD H

TEH-TSH TEH-TSil RIC 00210 610RP NDD 33 106 H

0211-02 H 0211-02 H 00202 610RP NDD 11 01H-01H 01H-01H 00202 610RP NDD H

TSH-TSH TSH-TSH 00202 610RP-NDD 117 106 H

02H-02H 02H-02tl 00202 610RP NDD H

01H-01H 01H-0;F 00202 610RP NDD H'

TSH-TSH TSH-TS11 00202 610RP NDD 145 106 EXP 1 11 TEH-TSU TEH-TSi 00202 610RP NDD 58 109 EXP 1 H

02 H-0211 02H-02H 00202 610RP NDD H

01H-01H Olli-O1H 00202 610RP NDD H

TSH-TSH TSH-TSH 00202 610RP NDD 136 109 EXP 1 H

01H-01H 01H-01H 00202 c10RP NDD CONAM NUCLEAR, INC.

5

=

=

,s CUMULATIVE REPORT 02/92, ARITONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 STEAM GI 4VPOR: 12 PAGPs 4 OF 6

LOCATION: ALL DATE:

05/01/92 CRITERIAs PROBE = 610RP, INLET ONLY TIME:

09:35:40 EXAM EXTENT

..RRENT ROW LIN EXP #

LEG PROGRAM ACTUAL REM REEL PROBE LOCNTION VOLTS MIL DEG CH 136 109 EXP 1 H

TSH-TSH TSH-Tall 00202 610RP

~

NDD H

02H-02H 02H-02H 00202 610RP NDD 148 109 EXP 1 0211- 0211 02H-02H 00202 610RP NDD H

01H-01H 01H-01H 00202 610RP NDD J

H Tsit-TSH TS!!-TSil RPI 00202 610RP TSH-0.32 0.9 121 LAI 2

93 110 EXP 1 11 TEH-TSl! TEH-TSli 00202 610RP NDD 28 111 H

TEH-TSil TEH-TSH 00210 610RP NDD 128 111 EXP 1 H

TE51-TSil TEH-TSH 00202 610RP NDD 93 112 EXP 1 H

TEll-TSH TEH-TSH 00202 610RP NDD H

02H-02H 02H-02H 00202 610RP NDD H

01H-0111 01H-01H 00202 610RP NDD 93 114 EXP 1 H

TEH-TSH TEH-TSH 00202 610RP NDD 127 114 EXP 1 H

TEH-TSH TEH-TSil 00202 610RP NDD 90 115 EXP 1 H

TEH-TSH TEH-TSH 00202 610RP NDD 89 116 EXP 1 H

TEH-TSH TEH-TSH 00202 610RP NDD 93 116 EXP 1 H

TEH-TSH TEH-TSH 00202 610RP NDD H

02il-02H 0 211- 0 211 00202 610RP NDD 1

H 011.-01H 01H-01H 00202 610RP NDD 117 116 H

0211-0211 02H-02H 00202 610RP NDD H

01H-01H 01H-01H 00202 610RP NDD

.H TS!'-TSH TSil-TSH 00202 610RP NDD 93 119 EXP 1 TEH-TSil TEH-TSH 00206 610RP NDD 1.11 118 EXP 1 H

01H-01H 01H-01H 00206 610RP NDD TSH-TSH TSH-TSH 00206 610RP NDD H

02H-0311 02H-03H RPI 00206 610RP 02H+

7.71 5.1 4

57 1

93 122 H

TElf-TSH TEH-TSH 00210 610RP NDD 93 124 H

TEH-TSH TEH-TSH 00206 610RP NDD 100 125 H

02H-02H 02H-02H 00206 610RP NDD H

01H-0111 01H-0111 00206 610RP NDD 1

H TSH-TSH TSH-TSH 00206 610RP NDD 93 126 11 TEH-TSH TEH-TSH 00206 610RP NDD 50 12S EXP 1 H

02H-02H 0211-02H 00206 610RP NDD H

01H-01H 01H-0)H 00206 610RP NDD H

TSil-TSH TSH-TSli 00206 610RP NDD l

71 130 H

02H-02H 02H-02H 00206 610hP NDD H

0111-01H 01H-01H 00206 610RP NDD H

TSH-TSH TSH-TSH 00206 610RP NDD 79 136 H

02H-02H 02H-02H 00206 610RP NDD H

01H-01H 01H-01H 00206 610RP NDD H-TSH-TSH TSH-Tsil 00206 610RP NDD 133 140 EXP 1 H

02H-02hl02H-02H l00206 610RP NDD H

01H-01H 01H-01H 100406 610RP NDD S

TSH-TSH TSH-TSH 00206 610RP NDD 76 141 H

0211- 0211 02H-02H 00208 610RP NDD H

01H-01H 01H 01H 00208 610R?

NDD

_~

CONAM NUCLEAR, INC.

L

_. - ~ ~ - -

. ~ - -

CUMULATIVE REDORT o

02/92, ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 STEAM GENERATOR: 12 PAGE:

5 OF 6

LOCATION: ALL DATE:

05/01/92 CRITERIA: PROBE - G10RP, INLET ONLY TIME:

09:35:40 EXAH EXTENT CURRENT ROW LIN EXP # LEG PROGRAM ACTUAL REM REEL PROBE LOCATION VOLTS HIL D3G Cll 76 141 H

TSH-TS?? TSil-TSH 00208 610RP NDD 13t 141 EXP 1 11 02H-02H 02H-02h 00206 610RP NDD 11 01H-0111 01H-01H 00206 610RP NDD 11 TLil-TSH TSH-TSH 00206 610RP NDD i

121 142 EXP 1 H

TSil-TSH TSil-TSil 00206 610RP.

NDD H

01H-02H 0311-02H 00206 610RP 01H+ 10.98 1.8 3

PVN 2'

46 145 EXP 1 H

TEll-TSil TEll-TSH 00206 610RP NDD 35 148 EXP 1 11 TEH-TSH TEH-TSH 00206 610RP NDD 9

152 EXP 1 11 TEH-TSH TEll-TSH 90206 610RP NDD 11 152 EXP 1 11 02 $1-0211 0211-02 H 00206 610RP NDD H

01H-01H 0111-01H 00206 610RP NDD H

TEH-TSH TEH-TSH RPI 00206 610RP T8H-0.63 2.7 118 SA!

5 84 155 H

02il-02H O2H-02H 00206 610RP NDD H

01H-0111 0111-0111 00206 610RP NDD 11 TSii-TSH TSH-TSH 00206 610RP NDD 88 155 EXP 1 H

02 H-0211 02H-02H 00208 610RP NDD 11 01H-01H 01H-0111 00208 610RP HDD H

T8H-TSli Talt-TSli 00208 610RP NDD 54 157 LXP 1 H

TEll-TSil TEll-TSH 00208 610RP NDD 111 160 H

TPH-TSH TEli-TS!!

00008 610RP NDD 98 161 EXP 1 H

01 H-02}i 0111-02H 00210 610RP NDD 100 161 EXP 1 H

01H-0211 01H-0211 00210 610RP l'DD i

97 162 EXP 1 ll 0111-02H 01H-02H 00210 610RP l

NDD 99 162 EXP 1 H

TSH-TSH TSil-TS11 00208 610RP NDD 11 0111-0211 01H-0211 00208 510RP 0111C 2 73 0.6 0 <20 18 H

0111-02H 01H-02H 00208 61C, ' 01H+ 2.73

-1.4 0

PLP 10 101 162 EXP 1 11 01H-02H 01H-0211 00210 610RP 3DD 111 162 li 02 H-0211 0211-02H 0020r 610RP NDD H

0111- 0 111 01H-01H 002/0 010RP NDD H

TEll-TS11 TEll-TSil RPI 00208 610RP TSII-0.02 3.3 228 SAI 18 98 163 EXP 1 H

0 111- 0 211 0111-02H 00210 610RP NDD 100 163 EXP 1 11 01H-02H 01H-0211 00210 610RP NDD 88 165 EX1 1 H

02H-02H 02H-02H 00208 610RP NDD 11 01H-0111 0111-01H 00'0B 610RP NDD i

H TSil-TSH TSH-TGH L 208 610RP NDD 32 177 EXP 1 H

02 H-0211 02H-02H 00202 610RP NDD 11 01H-0111 01H-01H 002D2 610RP NDD H

TSli TSH TSH-TSH 00202 610RP NDD 25 188 H

TEH-TSli TEH-TSH 00202 610RP NDD i

l CONAM liUCLEAR, INC.

-h

- ~.

.r.

CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 STEAM CENERATOR: 12 PAGEs.

6 OF 6

LOCATION: ALL DATE:

05/01/92 CRITERIA: PROBE = 610RP, IHLET ONLY-TIME:

09:35:40 HUMBER OF TUBES SELECTED FROM CURRENT OUTAGE:

98 NO TREND ANALYSIS REQUESTED

. REPORT OPTIONS:

Only examination resulta matching criteria acs included i

CONAM NUCLEAR, INC.

_ _ _ +

==

-=i I

l

~

4

CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 6

STEAM OENERATOR: 12 PAGE:

1 OF 4

LOCATION: ALL DATE:

05/01/92 CRITERIT PROBE = 610RP, OUTLET ONLY TIME:

09: 37:08

~

EXAM EXTENT CURRENT ROW LIN EXP #

LEO PROGRAM ACTUAL REM REEL PROBE LOCATION VOLTS MIL DEG CH 2

1 C

TSC-TSC TSC-TSC 00194 610RP NDD l

C 02C-02C C20~02C 00194 610RP 02C 0.83 4.1 0

39 18 1

23 2

C 02C-030 02C-03C 00194 610RP NDD j

2$

2 C

TSJ-TSC TSC-TSC 00194 610RP HDD C

02C-03C 02C-03C 00194 610RP 02C+ 36.50 PLP 10 26 3

C-02C-03C 02C-03C 00194 610RT NDD 49 10 C

TSC-Olc TSC-01C 00195 610RP NDD 51 10 C

TSC-Olc TSC-Olc 00195 610RP TSC+

0.63 4.5 90 PLP 10 48 11 C

Tsc-Olc TSC-Olc 0019b 610RP NDD 50 11 C

TSC-Olc TSC-0.C 00195 610RP TSC+

4.57 4.6 0 PLP 10 52 11 C

TSC-Olc TSC-Olc 00195 610RP TSc+ 2.12 4.4 271 PLP 10 58 11 C

TSC-Olc TSC-Olc 00195 610RP NDD 60 11 C

TSC-Olc TSC-Olc 00195 610RP NDD 47 12 EXP 1 C

TSC-Olc TSC J1C 00195 610RP NDD 49 12 C

TSC-Olc TSC-Olc 00197 610RP TSC+

8.62 4.6 87 PLP 10 51 12 C

TSC-Olc TSC-Olc 00197 610RP TSc+ 6.61 4.5 90 PLP 10 53 12 EXP 1 C

TSC-Olc TSC-Olc 00199 610RP NDD 57 12 EXP 1 C

TSC-Olc TSC-Olc 00199 610RP NDD 59 12 EXP 1 C

TSC-01C TSC-01C 00199 610RP T6s 0.55 3.1 80 PLP 10 61 12 C

TSC-Olc TSC-01C 00199 610RP TSC+ 0.42

.1.6 83 PLP 10 48 13 EXP 1 C

TSC-Olc TSC-01C 00199 610RP NDD 50 13 EXP 1 C

TSC-01C TSC-01C 00199 610RP NDD

$2 13 EXP 1 C

TSC-Olc TSC-01C 00199 610RP ND' 58 13 EXP 1 C

TSC-01C TSC-01C 00199 610RP NDD 60 13 EXP 1 C

TSC-01C TSC-Olc 00199 610RP TSC+

0.37 2.1 82 PLP 10 S

li-C TSC-TSC TSC-TSC 00194 610RP NDD 62 27 EXP 1 C

06C-07C 06C-07C 00195 610RP NDD 64 27 EXP 1 C

06C-07C 06C-07C 00195 610RP NDD 57 28 EXP 1 C

06C-07C 060-07C 00195 610RP NDD 59 28 EXP 1 C

06C-07C 06C-06C 00195 610RP NDD C

06C-07C 06C-07C RIC 00197 610RP NDD 61 28 C

06C-07C 06C-07C 00195 610RP NDD 63 28 C.

TSC-TSC TSC-TSC 00195 610RP NDD C

06C-07C 060-07C 00197 610RP NDD 65 28 C

06C-07C 06C-07C 00197 610RP NDD l_

32 29 EXP.1 C

04C-05C 04C-05C 00194 610RP NDD l

34 29 EXP 1 C

04C-05C 04C-05C 00195 510RP NDD 56 29 EXP 1 0

06C-07C 06C-07C 00197 610RP NDD 58 29 EXP 1 C TSC-TSC TSC-TSC 00197 610RP NDD f

60 29 C 06C-07C 06C-07C 00197 610RP NDD j

62 29 C

060-07C 06C-07C 00197 610RP NDD L

64 29-C 06C-07C 05C-07C 00197 610RP NDD i

106 29 EXP-1 C

06C-07C 06C-07C 00201 610RP NDD 108 29 C

06C-07C 060-07C 00201 610RP NDD 31 30 EXP 1 C

04C-05C 04C-050 00194 610RP NDD 4

CONAM NUCLEAR, INC.

~..

~

-t CUMULATIVM REPORT 02/92, ARIEONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 STEAM GENERATOR: 12 PAGE:

2 OF 4

LOCATION: ALL DATE:

05/01/92 CRITERIA: PROBE = 610RP, OUTLET ONLY TIME:

09:37:08 i

EXAM EXTENT CUkRENT ROW LIN EXP #

LEO PROGRAM ACTUAL REM REEL PROBE LOCATION VOLTSIAIL DEO CH C.

_..30 EXP 1 TSC-TSC TSC-TSC 00194 s.0RP NDD 33 C

C 04C-05C 04C-05C 00194 610RP 04C+ 36.95 1.1 78 PLP 10 35 30 EXP 1 C

04C-05C 04C-05C l00194 610dP NDD 57 30 EXP 1 C

06C+07C 06C-0/C 00199 610RP NDD

$9 30 EXP 1 C

TSC-TSC TSC-TSC 00201 610RP NDD C

06C-07C 06C-07C 00201 610RP NDD 61 30 C

06C-07C 06C-07C 00199 610RP NDD 105 30 EXP 1 C

06C-07C 06C-O'c 00199 610RP NDD 107 30 EXP 1 C

TSC-TSC TSC-TSC 00199 610RP NDD C

06C-07C 06C-07C 00199 610RP NDD 109 30 C

06C-07C 06C-07C 00199 610RP NDD 32 31 EXP 1 C

04c-05C 04C-05C 00144 610RP NDD 34 31 EXP 1 C

04C-05C 04C-05C 00194 610PP NDL 58 31 EXP 1 C

06C-07C 06C-07C 00201 610RP NDD 60 31 C

06C-07C 06C-07C 00203 610RP NDD 106 31 EXP 1 C

06C-07C 06C-07C 00201 610RP NDD 108 31 EXP 1 C

06C-07C 06C-07C 00201 610RP NDD 10$

34 EXP 1 C

TSC-Olc TSC-Olc 00201 610RP NPD 107 34 EXP 1 C

TSC-Olc TSC-Olc 00201 610RP TSC+ 13.48 0.6 19 PLP 10 104 35 txP 1 C

TSC-Olc TSC-01C 00201 610RP NDD 106 35 EXP 1 C

TSC-Olc TSC-01C 00209 610RP.TSC+ 13.38 1.0 261 PLP 10 108 35 EXP 1 C

TSC-Olc TSC-Olc 00201 610RP TSC+ 13.59 0.7 7e PLP 10 122 35 C

TSC-TSC TSC-TSC 00201 610RP NDO 105 36 EXP 1 C

TSC-Olc TSC-Olc 00201 610RP NDD 107 36 EXP 1 C

TSC-Olc TSC-Olc 00203 610RP NDD C

TEC-TSC TEC-TSO 00203 610RP NDD 125 42 EXP 1 C

06C-07C 06C-07C 00184 610RP NDD 127 42

- C 06C-07C 060-07C 00ks 4 610RP NDD 124 43 EXP 1 C

06C-07C 06C-07C 00189 610RP NDD 126 43 EXP 1 C

TSC-TSC TSC-TSC 00189 610RP NDD C

06C-07C 06C-07C 00187 610RP NDD 125 44 EXP 1 C

06C-07C 06C-07C 00189 610RP NDD 127 44 EXP 1 C

060-07~ 06C-07C 00189 610RP NDD 60 51 C TEC-TSC TEC-TSC 00193 610RP NDD l

99 54 C

TEC-01C TRC-02C 00189 610RP NDD i

C TSC-TSC TSC-TSC 00189 610RP NDD C

TEC-01C TEC-010 00190 610RP NDD C

TSC-TSC TSC-TSC 00190 610RP NDD 39 62 EXP 1 C

TSC-TSC TSC-TSC 00189 610RP NDD 150 85 EXP 1 C

TSC-TSC TSC-TSC 00189 610RP NDD C

03C-04C 03C-040 00189 610RP 03C+ 18.31 1.0 74 PVN, 18 L

158 87 C

TSC-TSC TSC-TSC 00189 610RP NDD L

137 88 EXP 1 C

TSC-TSC TSC-TSC 00189 610RP NDD C

02C-03C 02C-03C RPI 00189 610RP 02C+ 35.75 1.6 72 43 4

144 135 C

TSC-TSC TSC-TSC 00190 610RP NDD l

CONAM NUCLEAR, INC.

l en..

e

,--l

__.__m g

CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO. Pl.LO VERDE, UNIT 1 STEAM GENERATOR: 12 PAGE:

3 OP 4

LOCATION: ALL DATE:

05/01/92 CRITERIA: PdOBE = 610RP, OUTLET ONLY TIME:

09:37:08 l

~~

EXAM EXTENT CURRENT ROW LIN EXP #

LEG PROGRAM ACTUAL REM P"EL PROBE LOCATION VOLTS HIL DEG CH 144 135 C

03C-03C 03C-03C 00190 610RI 03C+

. 03 2.1 0

22 18 97 142 C

TSC-01C TSC-TSC 00190 610RP NDD C

TSC-Olc TSC-Olc RIC 00193 610RP TSC+ 10.90 5.2 10 PVN 2

63 180 C

02C-03C 02C-03C 00190 610RP NDD 65 180 C

02C-030 020-03C 00190 610RP NDD 62 101 C

02C-03C 02C-03C 00190 610RP NDD 64 181 C

TSC-Olc TSC-Olc 00190 610RP-hDD C

02C-03C 02C 03C 00190 610RP 02C+ 36.13 4.7 276 PLP 10 50 183 C

02C-03C 02C-03C 00190 610RP HDD

$2 ?93 C

02C-03C 02C-03C 00193 610RP NDD 39 184 C

03C-0JC 03C-03C 00190 610RP NDD C

02C-02C 02C-02C 00190 61CRP NDD C

TSC-TSC TSC-TSC 00190 610RP NDD 41 184 C

TSC-TSC TFC-TSC 001.90 010RP NDD C

03C-03C 03C-03C 00192 610RP Nt; C

02C-02C 02C-02C 00192 610RP NDD 43 184 C

03C-03C 03c-0!C 00192 610RP NDD C

02C-02C 02C-02C 00192 610RP NDD C

TSC-TSC TSC-TSC 00192 61DRP NDD 45 184 C

03C-03C 03C-03C 00192 610RP NDD C

02C-02C 02C-02C 00192 610RP NDD C

TSC-TSC TSC-TSC 00192 610RP NDD 47 184 C

03C-03C 03C-030 00192 610RP NDD C

02C-02C 02C-02C 00192 610RP NDD C

TSC-TSC TSC-TSC 00102 610RP NDD 49 184 C

02C-03C 02C-03C 00192 610RP NDD 51 184 C

TSC-TSC TSC-TSC 00192 610RP NDD C- 02C-030 02C-03C 00192 610RP 02Ct 36.45 2.5 277 PLP 10 40 185 C

iSC-TSC TSC-TSC 00192 610RP Tsc+

0.40 5.0 89 PLP 10 C

TSC-TSC TScrTSC RPI 00192 610RP TSC+

0.30 12.0 0

69 18 42 185 C

TSC-TSC TSC-TSC 00192 610RP TSC4 0.96 0.5 264 PLP 10 44 185 C

TSC-TSC TSC-TSC 00192 610RP TSC+

0.97 0.9 262 PLP 10 46 185 C

TSC-TSC TSC-TSC 00192 610RP NDD C

02C-03C 02C-03C 00192 610RP 02C+ 35.94 2.1 0

23 18 l

C 02C-03C 02C-030 00192 610RP 02C+ 35.58 4.0 96 PLP 10 39 186 C

03C-03C 03C-030 00192 610RP NDD C

02C-02C 32C-020 00192 610RP NDD C

TSC-TSC TSC-TSC 00192 610RP TSC+

0.32 6.4 89 PLP 10 C

TSC-TSC TSC-TSC RPI 00192 610RP TSC+

0.22 6.0 0

48 18 CONAM NUCLEAR, INC.

CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 STEAM GENERATOR: 12 PAGE:

4 OF 4

LOCATION: ALL DATE:

05/01/92 CRITERIA: PRODE = 610RP, OUTLET ONLY TIME:

09:37:08 NUMBER OF TUBES SELECTED FROM CURRENT OUTAGE:

95 NO TREND ANALYSIS REQUESTED REPORT OPTTONS:

Only examination resulto matching criteria are included na.

t 1

i

?

l CONAM NUCLEAR, INC.

l l'

i 1

i l

APPENDIX E

SUMMARY

DATA SIIEETS PLP

~~ "

t '.

Ej CUHULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 STEAM GENERATOR: 11 PAGE:

3 OF 2

LOCATION: ALL DATE:

04/01/92 CRITERIA: PLP TIME:

19:54:25 EXAM EXTENT CURRENT ROW LIN HEAT /

LEG PROGRAH ACTUAL REM REEL PROBE LOCATION VOLTS MIL DEG CH 33 4

C TEC-TEH TEC-TEH 00077 610UL TSC+

0.71 2.3 212 PLP 8

C TSC-TSC TSC-TSC 00109 610RP TSC+

0.71 10.3 32 PLP 10 C

TEC-TEH TEC-TEH 00070 620UL TSC+

0.55 0.5 50 PLP 7

35 4

C TEC-TEH TEC-TEH 00070 620UL TSC+

0.87 2.1 183 PLP 8

C TEC-TEH TEC-TEH 00077 610UL Tsc+

0.74 2.1 168 PLP 8

C TSC-TSC TSC-TSC 00109 610RP TSC+

0.53 11.5 211 PLP IO 37 4

C TSC-TSC TSC-TSC 00109 610RP TSC+

0.30 5.6 215 PLP 10 39 4

C TEC-TEH TEC-TEH 00068 610UL L2C+ 36.34 1.2 301 PLP 8

C TEC-TEH TEC-TEH 00077 610UL 02C* 36.34 1.1 302 PLP 8

34 5

C TSC-TSC TSC-TSC 00109 610RP TSC+

0.31 9.0 27 PLP 10 36 5

C TSC-TSC TSC-TSC 00109 610RP Tsc+

0.25 3.6 216 PLP 10 40 5

C TSC-TSC TSC-TSC 00109 610RP TSC+

0.24 6.6 18 PLP 10' 46 5

C TEC-TEH TEC-TEH 00077 610UL 02C+ 36.40 1.7 256 PLP 8

C TEC-TEH TEC-TEH 00068 610UL 02C+ 36.38 2.1 235 PLP 8

C 02C-03C 02C-03C 00109 610RP 02C+ 35.97 18.7 213 PLP 10 51 6

C TEC-TEH TEC-TEH 00068 610UL 02C+ 36.32 1.2 255 PLP' 8 C

TEC c"i TEC-TEH 00077 610UL 02C+ 36.28 1.3 253 PLP 8

8 7

C TSC-TSC TSC-TSC 00110 610RP TSC+

0.56 12.6 29 PLP 10 C

TEC-TEH TEC-TEH 00077 6100L TSC+

0.54 0.7 280 PLP 8 68 13 C

TEC-TEH TEC-TEH 00066 610UL 01C+

1.23 5.7 262 PLP 8

C TEC-TEH TEC-TEH 00077 610UL 01C+

1.22 2.4 228 PLP 8

C TEC-TEH TEC-TEH 00066 610UL 01C+

1.20 0.3 0 PLP 18 C

01C-01C 01C-01C 00110 610RP 01C+

1.03 11.3 37 PLP 10 70 13 C

TEC-TEH TEC-TEH 00066 610UL 01C+

1.23 0.6 203 PLP 8

C 02C-02C 01C-02C 00111 610RP 01C+ 0.81 2.4 190 PLP 10 69 14 C

01C-01C 01C-01C 00111 610RP 01C+

1.04 6.1 195 PLP 10 C

TEC-TEH TEC-TEH 00066 610UL 01C+

0.96 1.0 197 PLP 8

85 20 C

TEC-TEH TEC-TEH 00077 610UL 01H+

1.74 0.8 186 9LP 8

C TEC-TEH TEC-TEH 00070 620VL 01H+

1.75 0.9 188 PLP 8

H 01H-01H 01H-01H 00C36 610RP 01H+

1.88 3.3 54 PLP 10 10 27 H

TEH-02H TEH-02H 00078 610UL 02H+

4.79 0.7 166 PLP 8

69 13 4 C

01C-02C 01C-02C 00111 610RP 01C+

9.33 2.4 325 PLP 7

71 34 C

01C-02C 01C-02C 00111 610RP 01C+

9.14 1.3 333 PLP 7

70 35 C

02C-02C 01C-02C 00111 610RP 01C+

9.32 5.9 168 PLP 7

C TEC-TEH TEC-TEH 00063 6100L 01C+

6.99 0.8 338 PLP 6

2 71 C

TEC-07H TEC-07H 00073 5900L 02C+ 41.09 PLP 8

C 02C-03C 02C-03C 00112 610RP 02C+ 28.52to+ 40.90 1.0 103 PLP 10 C

01C-01C 01C-01C 00112 610RP 01C+

0.93 1.0 251 PLP 10 33 72 EXP 1 C

01C-020 01C-02C 00114 610RP 01C+

0.59 9.4 146 PLP 7

48 103 EXP 1 H

TSH-TSH TSH-TSH 00115 610RP TSH-0.00 2.6 151 PLP 7

26 113 C

01C-01C TSU-01C 00114 610RP TSC+

2.04 4.1 17 PLP 10 C

TEC-TEH TEC-TEH 00036 610UL TSC+

2.00 1.2 40 PLP 8

C 01C-01C TSC-Olc 00112 610RP TSC+

1.87 3.5 76 PLP 10 25 114 C

01C-01C TSC-Olc 00112 610RP TSC+

2.22 3.0 257 PLP 10 C

TEC-1EH TEC-TEH 00036 610VL TSC+

1.65 0.9 30 PLP 8

l_.

CONAM NUCLEAR, INC.

t I

(

)

CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICE CO.,

PALO VERDE, UNIT 1 STEAM GENERATOR: 11 PA0E 2 OF 2

LOCATION: ALL DATE:

04/01/92 CRITERIA: PLP TIME:

19:54:25 EXAM EXTENT l

CURRENT ROW LIN HEAT #

LEG PROGRAM ACTUAL REM REEL PROBE LOCATION VOLTS MIL DEG CH 25 114 C

01C-01C TSC-Olc 00112 610RP TSC+

1.4f 3.1 0 PLP 10 26 115 C

TSC-TSC TSC-TSC 00112 610RP TSC+

0.07 2.2 71 PLP 10 72 149 C

TEC-TEH TEC-TEH 00014 610UL 01H+

2.88 3.9 154 PLP 6

1 160 C

TEC-07H TEC-07H 00059 590UL 02C+

5.70 0.6 129 PLP 8

59 160 EXP 1 H

TEH-02H TEH-02H 00009 610UL 02H+

1.87 1.8 107 PLP 6

2 161 C

02C-03C 02C-03C 00114 610RP 03C+

2.96 1.6 296 PLP 7

1 1(.

C 02C-03C 02C-03C 00114 610RP 03C+

2.30 3.0 115 PLP 7

53 182 C

TSC-TSC TSC-TSC 00116 610RP TSC+

0.55 8.4 154 PLP 7

55 162 C

TSC-TSC TSC-TSC 00116 610RP TSC+

0.70 12.8 154 PLP 7

52 183 C

TEC-TEH TEC-TEH 00010 610UL TSC+

0.70 6.7 PLP 8

C TSC-TSC TSC-TSC 00110 010RP TSC+

0.57 10.1 330 PLP 7

54 183 C

TEC-TEH TEC-TEH 00010 6100L TSC+

0.75 10.1 PLP 8

C TSC-TSC TSC-TSC 00116 610RP Tsc+

0.21 10.5 156 PLP 7

47 184 C

TSC-ISC TSC TSC 00116 610RP TSC'

. 77 5.3 320 PLP 7

49

104, C

TSC-TSC TSC-TSC 00116 610RP TSC+

2.25 4.7 138 PLP 7

C 01C-01C TSC-Olc 00119 610RP TSC+

1.50 4.7 144 PLP 7

C TEC-TEH TEC-TEH 00010 610UL TSC+

0.54 7.3 PLP 8

C TSC-TSC TSC-TSC 00116 610RP TSC+

0.30 7.2 341 PLP 7

51 184 C

TEC-TEH TEC-TEH 00010 6100L TSC+

0.45 6.3 PLP P

C TSC-TSC TSC-TSC 00116 610RP TSC+

0.36 8.5 156 PLP 7

46 185 C

TSC-TSC TSC-TSC 00116 630RP Tsc+

1.04 3.7 139 PLP 7

i 33 196 C

01C-01C 01C-01C 00116 610RP 01C-1.13 3.8 151 PLP 7

C TEC-TEH TEC-TEH 00011 610UL TSC+

0.99 9.8 PLP 8

C TSC-TSC TSC-TSC 00116 610RP TSC+

0.41 13.3 330 PLP 7

35 186 C

01C-01C 010-01C 00116 610RP Olc-1.08 2.2 135 PLP 7

C TSC-TSC TSC-TSC 00116 610RP TSC+

1.14 12.6 140 PLP 7

C TEC-TEH TEC-TEH 00011 610UL TSC+

0.96 1.1 184 PLP 8

32 187 C

TSC-TSC TSC-TSC 00116 610RP TSC+

0.22 3.2 322 PLP 7

NUMBER OF TUBES SELECTED FROM CURRENT OUTAGE:

40 l

NO TREND ANALYSIS BEQUESTED REPORT OPTIONS:

Only examination resulto matching criteria are included MAP OPTIONS:

i l

Plot data from curront examinr. tion only CONAM NUCLEAR, INC.

_.___,___.___..-m

_mm._.

w s

t CUMULATIVE REPORT 02/92, ARIZONA PUBLIC SERVICT CO.,

PALO VERDE, UNIT 1 STEAM GENERATOR: 12 PAGE:

~1 OF 2

i LOCATION: ALL DATE:

04/04/92 CRITERIA: PLP TIME:

03:08:31 f

EXAM EXTENT CURRENT RCW LIN EXP #

LEO PROGRAM ACTUAL REM REEL PROBE LOCATION VOLTS HIL' DEG CH l

25 2

C 02C-03C 02C-03C 00194 610RP 02C+ 36.50 PLP 10 C

TEC-TEH TEC-TEH 00092 610UL 02C+ 36.45 1.5 226 PLP 8

51 10-C TSC-Olc TSC-Olc 00195 610RP TSC+

0.63 4.5 90 PLP 10 50 11 C

TEC-TEH TEC-TEH 00091 610UL T5C+

6.01 PLP 8

C TSC-Olc TSC-Olc 00195 610RP TSC+

4.57 4.6 o PLP 10 52 11 C

TSC-01C TSC-01C 00195 610RP Tsc+ 2.12 4.4 271 PLP 10 49 12 0

TEC-TEH TEC-TEH 00091 6100L TSC+

8.66 1.1 188 PLP 8

C TSC-Olc TSC-Olc 00197 610RP TSC+ 8.62 4.6 87 PLP 10 51 12 C

TEC-TEH TEC-TEH

'00091 610UL TLCr 7.58 1.3 190 PLP 8

C TSC-Olc TSC-01C 00197 610RP TSc+ 6.G1 4.5 90 PLP 10 59 12 EXP 1 C

TEC-07H TEC-07H 00102 6100C Tsc+

1.19 17.2 157 PLP 8

C TSC-Olc TSC-Olc 00199 610RP TSC+

0.55 3.1 80 PLP 10

'61 12 C

TSC-Olc TSC-Olc 00199 610RP TSC+

0.42 1.6 83 PLP 10 60 13 EXP 1 C

TSC-01C TSC 010 00199 610RP TSC+

0.37 2.1 82 PLP 10 33 30 EXP 1 C

04C-05C 04C-05C 00194 610RP 04C+ 36.95 1.1 78 PLP 10 C

TEC-07H TEC-07H 001; 6100C 04C+ 36.41 0.7 326 PLP 6

107 34 EXP 1 C

TSC-01C TSC-01C 00201 610RP TSC+ 13.48 0.6 79 PLP 10 106 35 EXP 1 C

TEC-08H TEC-VS2 00115 6100C TSC+ 13.52 0.4 157 PLP 6

C TSC-Olc TSC-Olc 00209 610RP TSC+ ?3.18 1.0 261 PLP 10 108 35 EXP 1 C

TSC-01C TSC-Olc 007.01 610RP TSC+ 13.59 0.7 78 PLP 10 99 162 EXP 1 H

01H-02H 01H-02H 00208 610RP 01H+

2.73-1.4 0

PLP 10 64 181 C

02C-03C 02C-03C 00190 610RP 02C+ 36.13 4.7 276 PL? 10 C

TEC-TEH TEC-TEH 00008 6100L 02C+ 35.76 1.2 241 PLP 6

51 184 C

02C-03C 02C-03C 00192 610RP 02C+ 36.45 2.5 277 PLP 10 C

TEC-TEH TEC-TEH 00006 610UL 02C+ 35.85 1.4 245 PLP 8

40 185 C

TEC-TEH TEC-TEH 00006 610UL TSC+

0.47 5.5 PLP 8

C TSC-TSC TSC-TSC 00192 610RP TSC+

0.40 5.0 89 PLP

',0 42 185 C

TSC-TSC TSC-TSC 00192 610RP TSC+

0.96 0.5 264 PLP 10 C

TEC-TEH TEC-TEH 00006 610UL TSC+

0.84 PLP 8

4e 185 C

TSC-TSC TSC-TSC 00192 610RP TSC+

0.97 0.9 262 PLP 10 C

TEC-TEH TEC-TEH 00006 6100L TSC+

0.87 PLP 8

46 185 C-TEC-TEH TEC-TEH 00006 610UL 02C+ 35.81 1.8 241 PLP 8

C 02C-030 02C-03C 00192 610RP 02C+ 35.58 4.0 96 PLP 10 C

TEC-TEH TEC-TEH 00006 610UL 02C+

9.11 10. 6 87 PLP 8

39 186 C

TEC-TEH TEC-TEH 00006 610UL TSC+

0.72 0.8 155 PLP 8

C TSC-TSC TSC-TSC 00192 610RP TSC+

0.32 6.4

.89 PLP 10 l

I l

L I

l CONAM NUCLEAR,-INC.

^

l

~

\\

i l _s -

-. :..-... =.. -

=

=.---.= -

.a a. -.

. ~ -

.i..

a. '

CUMULATIVE REPORT.

PALO VERDE, UNIT 1 02/_92, ARIZONA PUBLIC SERVICE CO.,

' STEAM GENERATOR: 12 PAGE:.

2 OF 2

-LOCATION:=ALL DATE:

04/04/92-CRITERIA: PLP TIME:

03:08:31 HUMBER OF TUBES SELECTEt, FROM CURRENT OUTAGE:

21

' - NO TREND ANALYSIS REQUESTED

-REPORT OPTIONS:

-Only examination results matching critoria are included

-MAP OPTIONS Plot data from current examination only 3

i Il 4

i CONAM NUCLEAR,.INC.

~.

=

vNv

-N m a v

e

-1 e

e i

i APPENDIX F l

TUI3E PLUG MAP 1

a

it,, -

{*

aff C$Ui 8 { " Ij {* [ ~

t i

Ap.8BEkhy lI h

=! !!

psp.epw.

~d;jn!! kh [o$ihi$ h:fs.o&,F, s

i hs h h.d E

lf$,N NhN'f${ %.; 3.UN$' $f'DU ';

ssfer. s 3,.

r n

m h

U

  • h a

i E

fSk'A t:

e $ f W.B

. t b,

t m,4.,,,.......

..,3.

,.,,r.,

l l '.

0, it,. :,3 ' 4.. 6..,;,,s

.a Y,.........i.

g 1.3 o

g o

7, ?..'.l....:...

,4 y.j,4,

.v.)

f" g

ifi.

' w:

!s B

a...,..

i, g

ga_

,p.q,

. g

.7..

g 3

. S ',

,< s

\\

m a

c, f,-

r

^ ~.^c

., p,.., p;.,;egs;3l 5

o (gs g

g s

y g.h g

-=

s j

g, 3

g g.{,,g4[ z 3! [ Ua...:

['

h s

..:4*.

a vo.

s.

y o, <.<..s o } '

p;

'Y 5

hM a..'. D

,,...d 4

o gl p$ md W "

ii!

a

$d l j

a i

a e r; h la e a E g h p k. g b 3

-i

'j

_t.',

. d

. $ -' #d f(. h - [ - n f

(j

- h h $.. [ * $ ' (, [- N o o o o ya l

T

! i 9;

a u

zu w

g g-x ER 0

t. s t.~

m.

-g n

U in t-h

((i

~

C o

~

b k --

E

~}6 o

a

'd I

a 0

2 F2 g_

pg.

I m

ia

=

.g.

o-p;-

A m

X.

  • 9

'?

E

-)

i(

y 9.

k o

o i

ji n-

+4 O 8, a. **

t y [,

DD t

g>

a

-l h

i L

s q.

l' l

i c

$.' N l".h.h. $N.. [

?

o r

x a

.=.

,1 O

A: PENDIX O FORM N15-1 l --

t-l 4

I l.

i.

I l

l L.

APS NIS-1 FORM

~

OWNERS' DNTA REPORT FOR INSERVICE INSPECTIONS

]

1.

OWNER ARIZONA PUBLIC SERVICE COMPANY, et al ADDRESS PO. BOX 52034; PIIOENIX, AluZ.ONA 2.

PLANT PALO VERDE NUCLEAR GENERATING STATION ADDRESS 4 MILES SOUTH WINTERSBURG, ARIZONA 3.

UNIT NUMBER: 1 4.

OWNERS CERTIFICATE OF AUTHORIZATION NONE 5.

COMMERCIAL SERVICE DATE;

!/28/86 6.

COMPONENTS INSPECTED:

COMPONENT OR MANUFACTUR ER SERIAL STATE OR NATIONAL APPURTENANCE OR INSTALLER NUMBER PROVINCE BOARD NO IMRCEE01A COMBUSTION 78273-1 N/A 22499 STEAM GENERATOR 11 ENGINEERING TUBING 1MRCEE0iB COMBUSTION 78273-2 N/A 22500 STEAM GENERATOR 12 ENGINEERING TUBING Page 1 of 3 '

i' APS NIS-1 BACK

~

OWN12S' DATA REPORT FOR INSERVICE INSPECTIONS 7.

EXAM DNTES 03/IML._ TD

-(u!!JaL 8.

INSPECTION INTERVAL FROM 01/28/86

'ID 03/17/97 9.

ABSTRACF OF EXAMINATIONS. INCLUDE A LIST OF EXAMINATIONS AND A STATEMENT CONCERNING STATUS OF WORK REQUIRED FOR CURRENT INTERVAL in steam generator 11 a total of 4076 iubes were examined full length, arvj all remaining tubes were examined part length. For steam generator 12 a total of 3804 tubes were examined f""'

eth, and all remaining tubes were exam.

ined part length. Several degraded / defective tubes were ob.scs....

'a3 and they are dc:umented in Appervlix C, D, and E of this report. The tutes identified on the folhwing pages were plugged arul/or staked as a sesult of this examinatiott TUDES PLUGGED:

SG 11 = 23 SG 12 = 18 WE CERTIFY TilAT Tile STATEMENTS MADE IN Tills REPORT ARE CORRECT AND TIIE EXAMINNrlONS AND CORRECrlVE MEASURES TAKEN CONFORM TO Tile RULES OF TIIE ASME CODES SECTION XI DATEA-A -Y 1_ SIGNED: ARizoN., PtidWC SihCE CmtPANY BY y

CERTIFICATE OF INSERVICE INSPECTION

1. Tile UNDERSIONED, flOLDING A VALID COMMISSION ISSUED BY THE NATIONAL BOARD OU BOILER AND PRESSURE VESSEL INSPECIURS AND THE STATE OF PROV!NCE OF ARIZONA EMPLOYED BY llSDI '

& ! CO. OF ll ARTFORD, CONNECTICUT IIAVE INSPECYED Tile COMPONENTS n5iSCRIB ED IN THIS OWN.

ERS REPORT DURING THE PERIOD te v2 TO wo

. AND STATETilA

,0 TILE BEST OF MY KNOWLEDGE AND BEllhF, TIIE OWNER llAS PERFORMED EXAMINATIONS AND TAKEN CORRECITVB MEASURES DESCRIBED 1N TlllS OWNERS REPORT IN ACCORDANCE WITI! THE REQUIREMENTS OFTHE ASME CODE, SECTION XI. BY SIGN'NG Tills CERTIFICATE NEITilER THE INSPECTOR NOR HIS EMPLOY-'

ER hl AKES A NY WARRANTY, EXPRESSED OR IMPLIED, CONCERNING Tile EXAMINATIONS AND COR.

RECMVE MEASURES DESCRIBED IN THIS OWNERS REPORT, RIRTilERMORE, NEITHER THE INSPECTOR NOR lilS EMPLOYER SilALL BE LI ABLE IN ANY MANNER FOR ANY PERSONALINJURY OR PROPERTY DAMAGE OR A LOSS OF ANY KIND ARISING FROM OR CONNECTED WITilTIES INSPECrlON.

INSPECIOR _.

T' LOMMISSIONS M #EM Y bM D

NAT' BOARD. STATE, PROVINCE DAlli SW j

i Page 2 of 3

j

.i

\\

)

STEAM GENERATOR 11

. STEAM GENERATOR 12-

.i l

BD.E LWE RQE ImE 4

3 3

184 68 13 46 185 70 13 99 162 69 14 40 185 1

16 42 185 1

18 44 185 33 4

39 186-35 4

4 187 37 4

33 106 34 5

29 80 36 5

137 88-40 5

93 116 33 186 11 152 35 186 148 109 32 157 121 118 33 72 44 91-39 96 111 162 38 97 2

1 36 107 154 71 159 102 145 134 1

6 l

i.

e.

V Page 3 of 3 1.