SOUTH CAROLINA ELECTRIC & GAS COMPANY

,OSr OFFICE 764 CotuualA. SOUTH CAROLINA 292 8 8

%T::::.:

85 JAN 8 Pl:y January I,y 1985 suct... o..=ario~s Mr. James P. O'Reilly Regional' Administrator U.S. Nuclear' Regulatory Commission Suite 2900 101 Marietta Street, NW Atlanta, GA 30323

SUBJECT:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 Special Report (SPR 84-018),

Revision 1

Dear Sir:

Attached'is Revision 1 to Special Report 84-018 for the Virgil C.

Summer Nuclear Station.

The original Report was submitted pursuant to the requirements of Technical Specification 3.4.9.3, " Reactor Coolant System - Overpressure Protection System."

This revision is being submitted to amend the Action Tcken portion of the Report.

Should there be any questions, please call us at your convenience.

very truly yours,

^

O. W i

r.

RJB:OWD/dwf Attachment cca.

V. C.

Summer K.

E. Nodland T.. C. Nichols, Jr./O. W. Dixon, Jr.

R. A. Stough E.' H. Crews, Jr.

G. Percival E.

C.; Roberts C. W. Hehl W. A. Williams, Jr.

J. B.

Knotts, Jr.

D. A. Nauman IEE Washington Document Management Branch Group Managers O. S. Bradham INPO Records Center C. A. Price ANI Library D. A. Lavigne NPCF J. F. Heilman File C. L. Ligon (NSRC)

OFFICIAL COPY h5

'(/ )7(

DR A O

I S

PDR

a.

w,

-e ;

Mr.. James P. O'Reilly

-SPR : 84-018
January 3, 1985

' EVENT ~ DESCRIPTION On-December 4,1984, with the Plant in Mode 5, Residual Heat Removal

^

~

-(RHR)

B" Train Suction Relief Valve actuated due to a Reactor Coolant System (RCS) pressure transient resulting from an isolation of letdown

+

flow.

-CAUSE OF. FAILURE

= Instrument &. Control (IEC) personnel, replacing the power supply

. drawer' to the Incore Thermocouple Separation Cabinet, inadvertently

-pinched a main power lead on the rear of the unit, shorting the lead to' ground.

The short circuit ultimately resulted in the loss of 1

Inverter:XIT-5901, which>de-energized'the distribution panel providing

'powersto. Letdown Flow. Control Valve HCV-142.

Loss of power.to control

. valve HCV-142 ' caused the valve ' to fail closed, isolating letdown flow and causing the RCS' pressure transient.

RHR " B" Train Suction Relief M

TValve actuation was' verified by the observation of the RHR discharge I ressure indicator'IPI-600B.

p L

t

. ACTION TAKEN

The'= Operator at the controls immediately. opened Pressure Control Valves-445:A.and B to maintain the'RCS de-pressurised.

ACTION TAKEN TO PRECLUDE RECURRENCE

'The11ead on 'the 7 rear-of' the power supply drawer was replaced with a

-shorterimain; power lead to prevent pinching ~during power. supply drawer t removal ' and ' replacemen t.. The! Licensee also inspected the other unit

' and -verifiedL that1the installed. lead 'was short enough to preclude pinching and; subsequent grounding.

+

-2 A

b

_i W'