Text

9

'k UNITED STATES E'Te NUCLEAR REGULATORY COMMISSION o

~

,E WASHINGTON, D. C. 20555 w.....f SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REA'CTOR REGULATION SUPPORTING AMENDMENT NO.110 TO LICENSE N0. DPR-49 10'A ELECTRIC LIGHT AND POWER COMPANY W

CENTRAL IOWA POWER COOPERATIVE CORN BELT POWER COOPERATIVE DUANE ARNOLD ENERGY CENTER DOCKET NO. 50-331 1.0 Introduction By letter dated October 5, 1984, the Iowa Electric Light and Power Company (the licensee) proposed changes to the Duane Arnold Energy Center (DAEC)

~ Technical Specifications t'o incorporate changes resulting from the licensee's commitment to njodify the (DAEC) automatic depressurization

' system (ADS) logic. The present ADS configuration will require manual actuation of the ADS in accidents which do not involve a high containment pressure. The proposed change would require automatic actuation of the ADS without the presence of containment high pressure.. A manual switch is prov,ided to permit the operators to override the automatic ADS actuation if the operators determine that ADS actuation is not needed. The proposed request will add the testing requirement for the manual override switch to the Technical Specifications.

The operation of the facility in the proposed manner would result in automatic initiation of the blowdown where manual blowdown was permitted by the plant configuations, and would require testing (during surveillance) of the manual override switches to be added to the Technical Specifications.

2.0 Evaluation By a letter dated June 6, 1984, the NRC staff informed the licensee that its commitments to modify ADS actuation logic statisfied the requirements of TMI Action Item II.K.3.18, and were acceptable.

Subsequently, by a letter dated October 5, 1984, the licensee proposed Technical Specification changes which account for the committed modifications for the ADS actuation and manual override. The licensee has indicated that the proposed modifications are planned for the forthcoming refueling outage commencing in February 1985. We have reviewed the licensee's request and find that the inclusion of the automatic actuation of ADS and the surveillance of manual override switch in the Technical Specifica'tions is consistent with the ob,iectives of the Action Item II.K.3.18. We therefore find that the proposed changes are acceptable.

3.0 Environmental Considerations This amendment involves a change in the installation or use of a facility component located within the restricted area as defined in 10 CFR Part 20.

8502140310 850201 PDR ADOCK 05000331 P

PDR

4.

..The staff has determined that the amendment involves no significant increase in the amounts, and no significant change in the types, of any effluents that may be released offsite, and that there is no significa~nt increase in indi.vidual o.r cumulative occupational radiation exposure. The Commission

'has previously issued a proposed finding that this amendment involves no 1significant hazards consideration and there has be'en no public comment on such finding. Accordingly, this amendment meets the eligibility criteria for categorical eFclusion set forth in 10 CFR 51.22(c)(0).

Pursuant to 10 CFR 51.22(b) no environmental impact statement or environmental assessment need be prepared in connection with the issuance of this amendment.

4.0 Conclusion We have concluded, based on the considerations discussed'above, that (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, and (2) such activities will be conducted in compliance with the Commission's regulations,'and the issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public.

Principal Contributor: Mohan C. Thadani

~

Dated:'~ February 1,1985 4

i O

I O

9

-