GPU Nucleit Corporation f. k( _
g gp One Upper Pond Roed Parsippany. New Jersey 07054 201-316-7000 TELEX 136482 Wnters D: rect Dial Number Oct.ober 2, 1992 5000-92-3071 C321-92-2254 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C.
20555 Gentlemen:
Subject:
Oyster Creek Nuclear Generating Station (OCNGS)
Docket No. 50-219 Facility Operating License No. UPR-16 Oyster Creek IGSCC Examinations and Weld Overlay Repairs
References:
(1) NRC Letter, " Safety Evaluation of IGSCC Examinations and Weld Overlay Repairs (TAC No, M80558)", August 25, 1992.
(2) NRC Letter, " Review of Proposed Changes of IGSCC inspection Program for Oyster Creek Cycle 14R Refueling Outtge (TAC No. M83985)", September 30, 1992.
In th:; Reference (1) letter, the NRC reque?*ed GPU Nuclear to commit to (1) perforniing a walkdown inspection of the piping supports (for systems subject to weld shrinkage due to overlay repair) to ensure that setpoints and air gaps are properly adjusted, and (2) explain why the refracted longitudinal ' ave techaique or the '!T techniques used to inspect for IGSCC in cast stainless steel pipe in PWRs would not yield meaningful results in GPU Nuclear's specific applicatici. (for cast stainless steel components).
In response to the first NRC request, CPU Nuclear agrees to perform walkdown inspections of piping supports foi systems subject to weld shrinkage due to overlay repairs. These inspections are currently planned for completion during the upcoming 14R Outage.
In response to tne second NRC request, GPU Nuclear provides Attachment I to this letter.
This attachmant is a detailed explanation as to why current inspection methodologies would not yield meaningful-results in IGSCC inspections for cast stainless steel components.
(j b ()() G l
9210130009 921002 rw\\
n4
/
PDR ADOCK 05000219 Vg\\g\\
I' PDR
}
GPU Nuclear Corporation is a subsidwy of General Pubhc Utikties Corporation l
~
'5000-92-3071 C321-92-2254 Page 2 Currently, GPU Nuclear plans, consistent with Reference (2) requirements,. to-classify five recirculation pump casing-to-suction-elbow weld as category A (IGSCC RESISTANT) under GL 88-01.. Based on this and the fact that GPU Nuclear has determined that no reliable ultrasonic method i:: currently available,-GPU Nuclear does not plan on performing an ultrasonic testing inspection.- Should a reliable and repeatable ultrasonic examination method be developed, GPU Nuclear will reconsider-performing these examinations.
If you have'any questions ar. comments on this subrittal, please contact Mr. Michael Laggart, Manager, Corporate Nuclear Licensing at (201) 316 7968.
Very tr ly yours, I-A w J.:C De ine, Jr.
Vice President and Director Technical Functions cc: Administrator, Region 1 Senior Resident Inspector Oyster Creek NRC Project Manager
1 1
ATTACHMENT I ULTRASONIC EXAMINATION OF CAST STAINLliSS STEEL The following problems are associated with ultrasonic wave propagation of cast stainless steel.
Cast stainless stools are elastically anisotropic in nature. This causes the ultrasonic wave propagation to experience velocity changos, attonuation, beam deviation, and beam scattering. These problems are caused by the various types of grain structure produced during the cooling process. Stated in an article writtan by the EPRI NDE Center and Drexel University, "...The majority of U.T. work is based on the arrival time analysis in which wave velocity is assumed to be constant *, When the velocity and beam direction are changed, due to the cast stainless steel, the technique is no lon0er valid. To compounu the problem, it is possible to have different grain struc*ures in castings on different sides of each wold (i.e., pump to elbow).
In uder to combat this problem, first an understanding of how g,ain structures affect ultrasonic v,.tve propagation is necessary, Once this is done, then the necessary changes to equipment / transducer can be made to improve the reliability of defect detection. To date there has been some progress in this area. The EPRI NDE Center with Drexol University have made samples of various cast materials for the understanding of wave propagation parameters. lhe reruits show that identification of grain structures of materials to be inspected is very important, This is cialmed to be possible using longitudinal or in some cases shear waves.
This is just the first step. Their conclusion doos say, "...However, further lovestigation is needed in order to obtain a broader perspective for reliable field application."
In 1988, Wolf Creek Nuclear Station conducted a workshop with the EPRI NDE Center to develop and domonstrate reliable ultrasonic techniques for cast stainless steels. Wolf Creek is a PWR and has centrifugally cast stainless steel. Ail block samples were received from the Westinghouse Owners' Group, whose mah concern is PWR problems. Each sample (block) contains artificially induced mechanical or thermal fatigue cracks near the root area. Note that IGSCC cracks, which are tighter and harder to detect in homogoneous, isotropic materials let alone anisotropic materials, were not included. The inspection of these blocks was performed by nine teams which consisted of five manual and four automated ultrasonic testing teams.
The overall results of this workshop has claimed a 70-80% detection rato. It also notes a better detection rate on thermal fatigue cracks than on mechanical fatigue cracks. The tight crack openings of mechanical fatigue cracks appear to be the reason, which is similar to IGSCC cracks. Also noted was that the automated teams performed exceptiorwily botter than the manual teams and that contrifugally cast coarse grained structure was the most difficult to examine, next the statically cast and the forged was the easiest.
i This last finding is in conflict with other published articles.
l l.
EPRl's conclusion of this workshop has noted significant progress in ultrasonic examinations. But they also state, "...Because of the variety of cast stainless steel grain structures and their considerable local variations within the same structurt, the grain effects on wave parameters vary substantially. Consequently, no single technique is applicable for all conditions",
l' GPU Nuclear has been in contact with Northeast Utilities and Yankee Atomic Electric Company who are working together to hold a round robin workshop at EPRI on this same subject. Both utilities have noted that there is no reliable ultrasonic method for cast stainless steels and are tying to determine if eny vendor is capable of reliable detection of flaws.
i
,, Yankee Atomic sent a cast stainless steel block indk:atke of their p'3nt to one of the vendors who took part in Wolf Creek's Workshop. The results show a 50% detection rate. Both utilities will be inviting any vendor who claims to be aL - to C_.bly detect flaws in any type of cast stainless steel to attend. They are hoping for results of the workanoo sometime in the spring of 1993. GPU Nuclear has asked thern to keep us informed of their progress.
Recently, Niagara Mohawk's Nine Mile Point Unit 1 experienced cracking in cast stainless steel valves on the omorgency cooling condenser return line. The thermal fatigue cracks were around the valves' drain hole.
The initial detection of the crack was by visually seeing leaks through the insulation. Further characterization was performed by visual and dye penetrant examinations after the valve was disassembled. Also, some of
's cracks were detected on double wall radiographs where the lines were drained of water. A variety of nitrasonic techniques were applied by several ditforent technicians. The valve bodies measured about 1.25' in thickness. The areas of known cracking were scanned and the results of trying to characterize the length and depth was poor at best. The technicians agreed that cracks open to the inside surface were not deiectable. Very deep cracks were thought to be detected but simHar signals could be obta!ned in other areas of the valve bodies where no cracking was present.
CONCLUSIONS
- 1. At this time, due to the nature of cast dainless steels, reliable ultrasonic examination, has not been proven.
- 2. All studies to date have addressed mechanical or thermal fatigue cracks. GPU Nuclear is not aware of any studies which address lGSCC in castings.
- 3. Understanding the type of casting and the grain structure of the part to be inspectad is a must. This would be just the starting point in the process to developing a ultrasonic technique.
- 4. No two castings are alike. Even if calibration blocks are made, assurances that the actual part being inspected is similar is unlikely.
- 5. The grain structure of castings affects wave propagation such as velocity, beam skew, attenuation, and beam distortion.
- 6. Manual ultrasonic examination will yield little to no results.
- 7. Future inspection will have to be automated or semi-automated with data acquisition system with the ability to analyze signals.
l
- 8. Special transducers need to be developed to improve the signal-to-noise ratio. Although some have been developed to date, none in our judgme7t have proven to be reliable.
l
- 9. Oyster Creek's recirculation pump casing-to-elbow weld may not lend itself to auto-scanners without modifications. There are various Instrumentation lines coming out of the elbows.
l
- 10. GPU Nuclear will keep abreast of round-robin testing at EPRI, Any new developments that prove to be reliable will be considered for application by GPU Nuclear.