ML20101H457

From kanterella
Jump to navigation Jump to search
Application for Amend to License DPR-59,revising TSs to Add Response Time Testing Requirements for RPS & MSIV Instrumentation Including Analog Transmitter Trip Sys,In Ref to Insp Rept 50-333/91-22
ML20101H457
Person / Time
Site: FitzPatrick 
Issue date: 06/22/1992
From: Ralph Beedle
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To:
Shared Package
ML20101H453 List:
References
NUDOCS 9206290358
Download: ML20101H457 (1)


Text

. _ _ _ _ _ - -

BEFORE THE UNITED STATES NUCLEAR REGULATORY COMMISClON in the matter of

)

NEW YORK POWER AUTHORITY

)

Docket No. 50-333 James A. FitzPatrick Nuclear Power Plant

)

APPUCATION FOR AMENDMENT TO OPERATING LICENSE Tho New York Power Authority requests an amendment to the Technical Specifications contained in Appendix A to Facilito Opciating Uconto DPR-59 for the James A.

FitzPatrick Nuclear Power Plant. This application is filed in accordanco with Section 10 CFR 50.90 of the Nuclear Regulatory Commission's regulations.

The proposed amendment to the James A. FitzPatrick Technical Specifications adds susponse timo testing requirements for the reactor protection system and main steam isolation valvo actuation instrumentation including the analog transmitter trip system (ATIS). These testing requirements are applied to instrument channels for which response time is a significant input to the FSAR transient and accident analyses.

The proposed Individual responso time acceptanco critoria were developed by the General Electric Company to ensure that total instrument loop response times, including the ATTS instrumentation delay, remain within the times assumed in the FitzPatrick transient and accident analyses.

Attachment I to this application contains the proposed changes to the Technical Specifications. Attachments 11 and 111 contain the associated Safety Evaluation and a report entitled "ATTS Transmitter Responso Timo Testing Methodology" which describes and evaluated the proposed response time testing methodology.

New York Power Authority

_ [t)---

N O..

Ralph E. Beedle Executive Vice President Nuclear Generation STATE OF NEW YORK COUNTY OF WESTCHESTER Subscribed and sworn to before me this.) J ^"'

day of 56* o,

1992.

t

/bbta A bLuL

/ Notary Public GERALDINE STRAND Notary Pubhc. State of New York No 4991272 n EN's sn 2 j'

9206290358 Y20622 PDR ADOCK 05000333 P

ppg

_