Provides Data Point Library for DC Cook Nuclear Plant in Response to 10CFR50,App E,Section VI
ML20101G231
Person / Time
Site: Cook  
Issue date: 06/17/1992
From: Fitzpatrick E
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: Murley T
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
AEP:NRC:1163A, NUDOCS 9206250360
Download: ML20101G231 (114)


Text

h Indicat %c%cn Power Company P O Bon 1(631 Cten OH 43?16 INDIANA MICHIGAN POWER AEP:NRC: 1163A 10 CPR Part 50 Donald C. Cook Nuclear Plant Units, and 2 Docket Nos. 50 315 and 50 316 License Nos. DPR 58 and DPR 74 EMERGENCY RESPONSE DATA SYSTEM (ERDS)

U. S. Nuclear Regulatory Commission Document Control Desk Washington, D. C.

20555 Attn:

T. E, Murley June 17, 1992

Dear Dr. Mutley:

This letter completes our response to the rule contained in 10 CFR Part 50, Appendix E Section VI, which establishes the Emergency Response Data System. In our initial response letter AEP:NRC: 1163 uated October 28, 1991, we stated that our specific Data Point 3

Library would be provided prior to July 1992.

.ttachment 1 to this submitta' provides the Data Point Library for Cook Nuclear Plant.

It should be noted that the radiation 1cvel of the RCS letdown line and the steam generator steam line are the only process parameters that are not included in the Data Point Library. These data are not available via the Cook Nuclear Plant radiation monitoring system.

Sincerely,

)

E. E. Fitzpatrick Vice President edg Attachment

\\

4 pem67 9206250360 ';20617 g

PDR ADOCK 05000315 p

PDR i

i

4 Dr. T. E. Murley 2-AEP:NRC: 1163A cc:

D.11. Williams, Jr.

A. A. Blind - Bridgtnan J. R. Padgett G. Charnoff A. B. Davis

  • Region III NRC Resident Iaspector Bridgman NFEM Section Chief J. Jolicoeur AEOD i

I 1

I 4

4-1 4

.t i -

f 4

i l'

s 3

6 4

m

+- -

,,w>.s-

-,w,we, y,,c,f g e,y r~,,w-,

c.m.3

-.3.,y.,..

.y,y.-g,,-.,pw.-,g.,,,+,yw,,..,-y-.,.

,,prpp,p.,,-m y m <www..-- w #.

,,v-.,n.

w

.sv.,

DATA POINT LIBRARTt COOK NUCLEAR PLANT UNIT 1 COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM

. DATA POINT LIBRARY PAGE 1 OF 112 REVISION O

_._____._m.____

i a

i j

DATE:

June 11, 1992 1

j REACTOR UMIT CK1 1.

DATA FEEDER:

N/A j

)

i NRC ERDS PARAMETER:

NI POWER RNG 4

5 POINT ID U1169 j

PLANT SPEC POINT DESC PWR RNG NUCL CHANNEL RMP AVG Q 1

J GENERIC /COND DESC:

NUCLEAR INSTRUMENTS, POWER RANGE l

j ANALOG / DIGITAL A

ENGR UNITS / DIG STATES:

l ENGR UNITS CONVERSION:

N/A i

t a

MINIMUM INSTR RANGE:

0.0 I

t 1

MAXIMUM INSTR RANGE:

120.0 I

ZERO POINT

REFERENCE:

N/A l

REFERENCE POINT NOTES:

N/A I

PROC OR SENS:

P NUMBER OF SENSORS:

4

{

HOW PROCESSED:

AVERAGE J-l SENSOR LOCATION:

OUTSIDE REACTOR VESSEL

}

l ALARM / TRIP SET POINTG 109.0 HIGH NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A j

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A j

INSTRUMENT FAILURE MODE N/A i

TEMPERATURE COMPENSATION l

FOR DP TRANSMITTER:

N/A j

LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC:

NRI-41, NRI-42, NRI-43, NRI-44 i

)

l a

COOK NUCLEAR PLANT -' EMERGENCY RESPONSE DATA SYSTEM DATA-POINT LIBRARY PAGE 2 OF-'112-j REVISION O l'

6

.~.

.-..-.,__.a._,,

DATE:

June 11, 1992 REACTOR UNIT:

CK1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

NI INTER RNG POINT ID:

UO972 PLANT SPEC POINT DESCs AVG INTERMEDIATE RANGE SIGNAL GENERIC /COND DESC NUCLEAR INSTRUMENTS, INTERMEDIATE RANGE ANALOG / DIGITAL A

ENGR UNITS /DIO STATES pAMPS ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.00001 MAXIMUM INSTR RANGE:

1000,0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

P NUMBER OF SENSORSs 2

llOW PROCESSED:

AVERAGE SENSOR LOCATION:

OUTSIDE REACTOR VESSEL ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A i

{

TEMPERATURE COMPENSATION.

i FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEGt N/A UNIQUE SYSTEM DESC:

NRI-35, NRI-36 TRIP SET POINT AT CURRENT (pAMPS)

EQUIVALENT TO LESS THAN OR EQUAL TO 25% THERMAL POWER ON EACM INPUT, TRIP MANUALLY DEFEATED AFTER 10% NIS

{

POWER 4

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA-POINT LIBRARY PAGE 3 OF 112 l

~ REVISION.O i

1

_ _ _. _ _ _. _ _. _ =.. - _ _ _ _ _. _ ~ _. _ - -..

i j

Fe '.12 June 11, 1992 j

Cc' :

'6 fV T CK1 i

DP,TA FTEDr N/A i

. J*

W.c h>u!ETER:

NI SOURCE RNG

+

{

J.r 10:

UO989 8/ AT SPEC POINT DESC: AVERAGE NIS SOURCE RANGE GENERIC /COND DESC NUCLEAR INSTRUMENTS, SOURCE RANGE ANALOG / DIGITAL:

A j

ENGR UNITS / DIG STATES:

CPS i

i ENGR UNITS CONVERSION:

N/A i

j MINIMUM INSTR RANGE:

1.0 i

MAXIMUM INSTR RANGE:

2000000.0 i

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A i

PROC OR SENS:

P i

NUMBER OF SENSORS:

2

.,i j

l HOW PROCESSED AVERAGE a

SENSOR LOCATION:

OUTSIDE REACTOR VESSEL i

l ALARM / TRIP SET N)INTS:

100000.0 TRIP NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

1.0E-10 AMPS NI DETECTOR POWER SUPPLY j

TURN-ON POWER LEVEL:

6.0E-11 AMPS INSTRUMENT-FAILURE MODE N/A i

TEMPERATURE COMPENSATION l

FOR DP TRANSMITTER:

N/A

?

LEVEL REFERENCE LEG N/A i

~

UNIQUE SYSTEM DESC -

NRI-31, NRI-32 4

4 1

6 0

l COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM-I DATA POINT LIBRARY PAGE 4 OF 112

)

REVISION O b

f

_ _ ~. ~---,

1__-_._,..a.a-.-

.___m_._.

l I

I i

DATE:

June II, 1992 f

i j

REACTOR UNIT CK1 j

DATA FEEDER:

N/A f'

)\\

NRC ERDS PARAMETER:

REAC VES LEV i

POINT ID:

U1602

]

PLANT SPEC POINT DESC: AVERAGE RVLIS NARROW RANCE t

GENERIC /COND DESC REACTOR VESSEL WATER LEVEL ANALOG / DIGITAL:

A i

ENGR UNITS / DIG STATES:

}

}

'NGR JNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 i

MAXIMUM INSTR RANGE:

120.0 ZERO POINT

REFERENCE:

COMPLX i

REFERENCE POINT NOTES:

60 % TOP OF FUEL 3

PROC OR SENS:

P l

NUMBER OF SENSORS:

2 j

HOW PROCESSED:

AVERAGE SENSOR LOCATION:

TAPS'AT BOTTOM AND TOP OF REACTOR VESSEL j

ALARM / TRIP. SET POINTS: N/A i

NI DETECTOR' POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

Y

- LEVEL REFERENCE LEG WET UNIQUE SYSTEM DESC:

NLI-110, NLI-111 ONLY VALID WHEN RCP'S ARE OFF, WILL BE PEGGED HIGH WHEN RCP'S RUNNING-i

'l BOOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM-

-l DATA POINT LIBRARY PAGE 5 of 112

~

REVISION O

DATE:

Juno II, 1992 REACTOR UNIT:

CKI DATA FEEDER:

N/A NRC ERDS PARAMETER:

REAC VES LEV POINT ID:

UI601 PLANT SPEC POINT DESC:

AVERAGE RVLIS WIDE RANGE GENERIC /COND DESC REACTOR VESSEL WATER LEVEL ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

120.0 ZERO POINT

REFERENCE:

COMPLX REFERENCE POINT NOTES:

N/A PROC OR SENS:

P NUMBER OF SENSORS:

2 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

TAPS AT DOTTOM AND TOP OF REACTOR VESSEL ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

Y LEVEL REFERENCE LEC:

WET UNIQUE SYSTEM DESC:

NLI-130, NLI-131 ONLY VALID WHEN RCP'S ARE RUNNING

,DOOKNUCLbARPLANT-EMERGENCYRESPONSEDATASYSTEM DATA POINT LIBRARY PAGE 6 OF 112 REVISION O

DATE:

June II, 1992 REACTOR UNIT:

CKI DATA FEEDER:

N/A NRC ERDS PARAMETER:

TEMP CORE EX POINT ID:

U0090 PLANT SPEC POINT DESC:

INST VALUE OF HOTTEST INCORE TC GENERIC /COND DESC:

HIGHEST TEMPERATURE AT THE CORE EXIT ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

DEGF ENGR UNITS CONVERSIONS N/A MINIMUM INSTR RANGE:

200.0 MAXIMUM INSTR RANGE:

2300.0 ZERO POINT

REFERENCE:

N/A i

REFERENCE POINT NOTES:

N/A PROC OR SENS:

P NUMBER OF SENSORS:

65 HOW PROCESSED:

HOTTEST OF 65 CORE EXIT T/C'S SENSOR LOOATION:

THROUGHOUT CORE ALARM / TRIP SET POINTS:

700.0 HIGH NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY e

TURN-OH POWER LEVEL:

N/A-INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC:

N/A

-COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM i

DATA POINT LIBRARY-PAGE 7 OF 112

-REVISION O l

t

?

~,.. - _.,

i;,

u-,.m.--.._.,

,m-.--,

m....

..-.4 1,_.-,,,-~...

-- -._ -.~.-. _ _.- - --. _..

1 l

1 l

J i

DATE:

June 11, 1992 4

REACTOR UNIT:

CKI 1

l DATA FEEDER:

N/A l

NRC ERDS PARAMETER:

SUB MARGIN POINT ID:

UO965 1

{

PLANT SPEC POINT DESC HOTTEST T/C (**RGIN TO SATURATION

)

GENERIC /COND DESC:

SATURATION TEMPERATURE - HIGHEST CET ANALOO/ DIGITAL:

A ENGR UNITS / DIG STATES: DEGF f

ENGR UNITS CONVERSION: N/A d

MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

2300.0 i

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A 3

PROC OR SENS:

P 1

j NUMBER OF SENSORS:

2

?

9 i

HOW PROCESSED:

SAT TEMP - MAX CET j-t j

SENSOR LOCATION:

T/C'S IN CORE l

ALARM / TRIP SET POINTS:

29.0 LOW 600.0 HIGH NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY i

TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A 1

j TEMPERATURE-COMPENSATION j

FOR DP TRANSMITTER:

N/A i

1 LEVEL REFERENCE LEG N/A 3

}

UNIQUE SYSTEM DESC:

U0095, U0090 SATURATION TEMPERATURE-BASED ON MINIMUM-l WIDE RANGE RCS PRESSURE MINUS THE MAXIMUM CORE EXIT THERMOCOUPLE TEMPERATURE k

i i

}l COOK NUCLEAR PLANT - EMERGENCY-RESPONSE DATA SYSTEM

}

' DATA POINT LIBRARY.

PAGE 8.0F 112 REVISION O l

4 4

~~-,m.,;

_,,--..---cm.w---

._.,--,.-,......,m,r%,,-.,

.,,J--.-.,,,J',,-----

DATE:

June 11, 1992 REACTOR UNIT CK1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

CORE FLOW POINT ID:

U1612 PLANT SPEC POINT DESC:

TOTAL RCS FLOW GENERIC /COND DESC:

TOTAL REACTOR COOLANT FLOW ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

GPM ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

-0.0 MAXIMUM INSTR RANGE:

397760.0 ZERO POINT

REFERENCE:

N/A

-REFERENCE POINT NOTES:

90400 GPM PER PUMP I

PROC OR SENS:

P NUMDER OF SENSORS:

12 HOW PROCESSED:

AVERAGE PER LOOP, SUM OF 4 LOOPS SENSOR LOCATION:

COLD LEG SUCTION LINE TO PCP'S ALARM / TRIP SET POINTS:

N/A NI DETECTOR-POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A l-INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION 4

i FOR DP TRANSMITTER:

N i

LEVEL REFERENCE LEG N/A l'

l UNIQUE SYSTEM DESC:

NFP-210, NFP-211, NFP-212, NFP-220, NFP-221, NFP-222, i

NFP-230, NFP-231, NFP-232, NFP-240, NFP-241, NFP-242 t'

f l

s l

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 9-OF 112 l

REVISION O' u,_,_-.,,____,.

,u....,.,-._ _ a

..,~2..

.a_-_.~.-._,,..__..-_...,

~ - - -.. -

I t

I I

i DATE:

June 11, 1992 i

i REACTOR UNIT CK1 i

j DATA FEEDE3 N/A NRC ERDS PARAMETER:

SG LEVEL 1/A i

1 POINT ID:

LO403A j

PLANT SPEC POINT DESC STM GEN 1 WIDE RNG L GENERIC /COND DESC STEAM GENERATOR 1 (OR A) WATER LEVEL I

ANALD0/ DIGITAL:

A I

j

~ ENGR UNITS / DIG STATES:

ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 l' -

MAXIMUM INSTR RANGE:

100.0 il r

ZERO POINT REFERENCE 4 COMPLX REFERENCE POINT NOTES: AT 0% 30.3 FT BELOW TOP OF FW INLET-PIPE PROC OR SENS:

S

(

NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A i

j SENSOR LOCATION:

38,3 FT BELOW TOP OF FW INLET PIPE ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

' N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A f

INSTRUMENT FAILURE MODE N/A i

1 TEMPERATURE COMPENSATION l

FOR DP TRANSMITTERS Y

i-l LEVEL REFERENCE LEG -

WET 1

i UNIQUE SYSTEM DESC:

bLI-110 i

s t'

a

^

COOK NUCLEAR. PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 10 OF 112 i '

REVISION O i

i i,

l' I. -..,,,.......

,...._._.._.--,..m

._.._....~..,,__-.,..,..e.

..-...m.

~.

.,m...,_...__~.

L DATE:

June 11, 1992 REACTOR UNIT:

CK1 DATA FEEDER:

N/A NRC ERDS PF iMETER:

SG LEVEL 2/B POINT ID:

LO423A PLANT SPEC Poll:T DESC STM GEN 2 WIDE RNG L GENERIC /COND DESC:

STEAM GENERATOR 2 (OR B) WATER LEVEL ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 MhKIMUM INSTR RANGE:

100.0 1

ZERO POINT REFERENCE '

COMPLX REFERENCE. POINT NOTES: AT 0% 38.3 FT BELOW TOP 0F FW INLET PIPE PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR-LOCATION:

38.3 FT BELOW TOP OF.FW INLET PIPE ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODEsN/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

Y LEVEL REFERENCE LEG WET l

UNIQUE SYSTEM DESC:

BLI-120-4 r

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA-SYSTEM

.PAGE 11 OF 112 l

DATA POINT LIBRARY li REVISION O i

l f.

p

-,J...--_.....

-.-.e.L+._._,

-,_,4,........,J,.----,_.rm,..,.,4,,....--.J-_

,y_...,,,

m..

DATE:

June 11, 1992 REACTOR UNIT:

CK1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

SG LEVEL 3/C POINT ID:

LO443A PLANT SPEC POINT DESC:

STM GEN 3 WIDE RNG L GENERIC /COND DESC:

STEAM GENERATOR 3 (OR C) WATER LEVEL ANALOG / DIGITAL:

A ENGR UNITS /DIO STATES:

ENGR UNITS CONVERSION: N/A MINIMUM INSTR. RANGE:

0.0 MAXIMUM INSTR RANGE:

100.0 ZERO POINT

REFERENCE:

COMPLX

-REFERENCE POINT NOTES:

AT 0% 38.3 FT BELOW TOP.OF.FW INLEY PIPE PROC OR SENS:

S 1

NUMBER OF SENSORS:

I HOW PPOCESSED:

N/A SENSOR LOCATION:

38.3 FT BELOW TOP OF FW INLET PIPE ALARH/ TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A su imTr UTvH POWER SUPPLY i

TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A i

j TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

Y l

LEVEL REFERENCE LEG:

WET UNIQUE SYSTEM DESC:

BLI-130 e

i l

?

Iti.

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM

. DATA POINT LIBRARY PAGE 12 OF 112 REVISION O 1

i l'

6

.._..-,----...,;--.-,,..__,..~...,,,-._.._._,....__.__,._.a..,._...

1 DATE:

June 11, 1992 1

i REACTOR UNIT:

CK1 I

DATA FEEDER:

N/A i

NRC ERDS PARAMETER:

SG' LEVEL 4/D POINT ID:

LO463A PLANT SPEC POINT DESC:

STM GEN 4 WIDE RNG L j

j GENERIC /COND DESC:

STEAM GENERATOR 4 (OR D) WATER LEVEL j

i 4

ANALOC/ DIGITAL:

A l

j ENGR UNITS / DIG STATES:

j ENGR UNITS CONVERSION:

N/A 3

].

MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

100.0 1

j ZERO POINT

REFERENCE:

COMPLX' 4

i_

REFERENCE POINT NOTES:

AT 0% 38.3 FT BELOW TOP OF FW-INLET PIPE I

j PROC OR SENS:

.S j

j NUMBER OF SENSORS:

1 i

!!OW PROCESSED:

N/A 4

j SENSOR LOCATION:

38.3 FT BELOW TOP OF FW INLET PIPE f

i, ALARM / TRIP SET POINTS:

N/A i

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A e

NI DETECTCR POWER SUPPLY l

-TURN-ON POWER LEVEL:

N/A a

j INSTRUMENT FAILURE MODE N/A i

l TEMPERATURE COMPENSATION j

FOR DP TRANSMITTER -

Y i

l LEVEL REFERENCE LEG WET

]

-UNIQUE SYSTEM DESC:

BLI-140 J

i e

4 4j i

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM 4

j DATA POINT LIBRARY PAGE 13 OF-112 REVISION O 1

i i

l'

,. _,,. _.. ~...

,..,,,,.,-.,_,,,_.a.

.. ~ _,.

_...... u..;

u.-......,.

....,. ~..

DAth:

June 11, 1992 RE%CTOR UNIT:

CK1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

SG PRESS 1/A POINT ID:

UO414 PLANY SPEC POINT DESC:

STM GEN 1 STM P 1/2/3 AVG GENERIC /COND D.

C:

STEAM GENERATOR 1 (OR A) PRESSURE ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

PSIG ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

1200.0 ZERO POINT REFFRENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS:

P NUMBER OF SENSORS:

3

!!OW PROCESSLD:

AVERAGE SENSOR LOCATION:

OUTLET FROM SG1 TO TURBINE ALARM / TRIP SET POINTS:

500.0 LOW NI DETECTOR POWER SUPPt,Y CUT-OFF POWER LEVEL:

N/A J*-I DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMDENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC:

MPP-210, MPP-211, MPP-212 COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 14 OF 112 REVISION O

. _ -... -.-... -.. - - -. -- _._.~. -._-. -

- -....._ -.. -...~..-. - ~ _,.-

i i

i 4

DATE:

June 11, 1992 4

l REACTOR UNIT CK1 4

j DATA FEEDER:

N/A i

NRC ERDS PARAMETER:

SG PRESS-2/B i-POINT ID:

UO434 PLANT SPEC POINT DESC:

STM GEN 2 STM P Ir2/3 AVG

{

GENERIC /COND DESC:

STEAM GENERATOR 2 (OR B) PRESSURE ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

PSIG 1

ENGR UNITS CONVERSION: N/A

]

MINIMUM INSTR RANGE:

0.0 i

j MAXIMUM INSTR RANGE:

1200.0 ZERO POINT REFERENCE '

N/h.

l' 4

j REFERENCE-POINT NOTES:

N/A i

PROC OR SENS:

P i

+

l NUMBER OF SENSORS:

3 HOW PROCESSED:

AVERAGE l

SENSOR LOCATION:

OUTLET FROM SG2 TO TURBINE l

ALARM / TRIP SET POINTS. 500.0 LOW l

NI DETECTOR POWER SUPPLY l

CUT-OFF POWER LEVEL:

N/A 1

1 l

NI DETECTOR POWER SUPPLY I

TURN-ON POWER LEVEL -

N/A i

e f

l INSTRUMENT FAILURE MODE N/A i

TEMPERATURE COMPENSATION j

FOR DP TRANSMITTER:

N/A l

LEVEL REFERENCE LEG N/A f'

UNIQUE SYSTEM DESC:

MPP-220, MPP-221, MPP-222 i

o 4

f j

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA-POINT LIBRARY PAGE 15 OF~112 3

REVISION O r

~

I J. L.,,..., _, _ A.

...,,.....,,.._m-_.-,,,,,-.,.._.......,u..

.. /...

DATEt June 11, 1992 REACTOR UNIT:

CK1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

SG PRESS 3/C POINT ID:

UO454 PLANT SPEC POINT DESC:

STM GEN 3 STM P 1/2/3 AVG GENERIC /COND DESC:

STEAM GENERATOR 3 (OR C) PRESSURE ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

1200.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS:

.P NUMBER OF SENSORS:

3 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

OUTLET FROM SG3 TO TURBINE ALARH/ TRIP SET POINTS:

500.0 LOW NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEV 3L N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG:

N/A UNIQUE LYSTEM DESC:

MPP-230, MPP-231, MPP-232 COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 16 OF 112 REVISION O I

DATE:

June 11, 1992 REACTOR UNIT:

CK1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

SG PRESS 4/D POINT ID:

U0474 PLANT SPEC POINT DESC:

STM GEN 4 STM P 1/2/3 AVG GENERIC /COND DESC:

STEAM GENERATOR 4 (OR D) PRESSURE ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

PSIG ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

1200.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS:

P NUMBER OF SENSORS:

3 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

-OUTLET TO SG4 TO TURBINE ALARM / TRIP SET POINTS:

500.0 LOW NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY

=

TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A

. TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC -

MPP-240, MPP-241, MPP-242 i-COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 17 OF 112

-REVISION O

.... -.._ _... _. ~ _. _. _ _. _...

_ _. _. _. _. _.. - _ _ ~

t J

l 4

DATE:

June II, 1992 ij PEACPOR UNIT:

CK1 d.

DATA FEEDER:

N/A i

)

NRC EOS P.i.RAMETER:

MN FD FL 1/A i

POINT ID:

UO411 i

l-PLANT SPEC POINT DESC:

SG 1 FW IN CORR AVG CALC 1 MIN 7 i

i GENERIC /COND DESC:

STM GEN 1 (OR A) MAIN FEEDWATER FLOW ANALOG /DEOI1T1:

A l

j ZwGR UNITS / dig STA*rgs: MLB/HR ENPR UNITS CONVERF10N ; N/A l

l N UTMUM INSTR RANGL 0,000 t

j

. MAXIMt/h JNSTR PANCF 4.000 ZEPO POINT REFiiRhNCE,

.N/A 4

)

REFERENCE POINT NOTES: N/A i

i PROC OR SENS:-

P I

l NUMBER OF SENSORS:

2 i

i HOW PROCESSED:

AVERAGE I-SE!iSGI4 LOCATION:

INLET LINE TO SG1 0

l ALARM / TRIP SET PGINTS: N/A l

i NI DETECTOR-POWER SUPPLY l.

CUT-OFF POWER LEVEL:

N/A i.

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILUkE MODE N/A l

4 TEMPERATURE COMPEN4ATION.

l FOR DP TRANSMITTER:

Y j

LEVEL REFERENCE LEG -

N/A I

i-UNIQUE SYSTEM DESC:

FFC-210, FFC-211 l

j' COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM-DATA POINT LIBRARY PAGE 18 OF 112 REVISION O f

_~ne._,.7

....n.7

... 'm..p.wy,.,,,,._,..,%,,y,,,

.y,.-,M,,,

,m

,,3 y..

,m..,,,m,

, y.m m y,,,

,n_j,,,,,,.,,m.r.,,,

3

,g...p,.,,,,.,

_ = - -.... ~.. -.. - - -.

...-.- -.- - -..~

l

]

DATE:

June II, 1992 i

REACTOR UNIT:

CK1 ij-DATA FEEDER:

N/A j

NRC ERDS PARAMETER:

HN FD FL 2/B 1

POINT ID:

00431 PLANT SPEC POINT DEsce SG 2 FW IN CORR AVG CALC 1 MIN P j

GENERIC /COND DESC STM GEN 2 (OR B) MAIN FEEDWATER FLOW

]

l ANALOG / DIGITAL:

A i

ENGR UNITS / DIG STATES:

MLD/HR a

i ENGR UNITS CONVERSION: - N/A i

j MINIMUM INSTR RANGE:

0.000 i

4 MAXIMUM INSTR RANGE:

4.000 i

END POINT R::FERENCE:

N/A l

REFERENCE POINT *.lotSS:

N/A 2

l PROC OR SENS:

P NUMBER OF SENSORS:

2 3

I HOW PROCESSED:

AVERAGE i

SENSOR LOCATION:

INLET LINE TO SO2 ALARM / TRIP SET POINTS:

N/A 1

3 NI DETECTOR POWER SUPPLY l

CUT-OFF POWER LEVEL:

N/A I

NI DETECTOR POWER SUPPLY-l-

TURN-ON POWER LEVEL:

N/A l

INSTRUMENT FAILURE MODE N/A l

l TEMPERATURE COMPENSATION i

. FOR DP TRANSMITTER:

Y l

{

LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC FFC-220, FFC-221 4

I COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 19 OF'112 REVISION O i

4 i

i y

4-.

~ ~

,, - + -,

w-o.--,__,v,.,....-c.,,

e...

,m,.....,,---e.w.y.,,#,%w.,.,,.,~.-,..-~,,-,,,,..w,,

,,.w..v.,

y,

,w-,--.4.,r

DATE:

June 11, 1992 REACTCR UNIT CK1 DATA FEEDER:

N/A NRC ERDS PARAMMTER:

MN FD FL 3/C POINT ID:

U0451 PLANT SPEC POINT DESC - SG 3 FW IN CORR AVG ChLC 1 MIN F GENERIC /COND DESC:

STM GEN 3 (OR C) MAIN FEEDWATER FLOW ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

MLB/HR ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.000 MAXIMUM INSTR RANGE:

4.000 ZERO POINT

REFERENCE:

N/A i

REFERENCE POINT NOTES:

N/A PROC OR SENS:

P NUMBER OF SENSORS:

2 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

INLET LINE TO SG3 ALARM / TRIP SET POINTS:

N/A HI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI. DETECTOR' POWER-SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A l

l TEMPERATURE COMPENSATION y

FOR DP TRANSHITTER:

Y LEVEL-REFERENCE LEG N/A UNIQUE SYSTEM DESC:

FFC-230, FFC-231 COOK NUCLEAR PLANT - EMEnGENCY P.ESPONSE DATA SYSTEM DATA POINT-LIBRARY.

PAGE 20 OF 112 REVISION Q

. ~ c.

,a,._...s,.-..

_,.., _ _.., _. -. _.. ~. _ _ _ _ _ _. _,,....

i l

DATE:

June 11, 1992

)

REACTOR UNIT:

CF.1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

MN FD FL 4/D 1

d POINT ID:

UO471 PLANT SPEC POINT DESC:

SG 4 FW IN CORR AVG CALC 1 MIN F

]

j GENERIC /COND DESC:

STM GEN 4 (OR D) MAIN FEEDWATER FLOW ANALOG / DIGITAL:

A 1

ENGR UNITS / DIG STATES:

MLB/HR ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.000 j

MAXIMUM INSTR RANGE:

4.000 ZERO POINT REFERENCE t.

N/A

~

REFERENCE POINT NOTES:

N/A PROC OR SENS:

P A

t NUMBER OF SENSORS:

2 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

INLET LINE TO SG4 l-ALARM / TRIP SET POINTS:

N/A n.

NI DETECTOR POWER SUPPLY l

CUT-OFF POWER LEVEL.

N/A 1

4-NI DETECTOR POWER SUPPLY I

TURN-ON POWER LEVEL:

N/A i

i j

_ INSTRUMENT FAILURE MODE N/A i

i TEMPERATURE COMPENSATION 1

FOR DP TRANSMITTER:

Y j

LEVEL REFERENCE LEG N/A-UNIQUE SYSTEM DESC:

FFC-240, FFC-241

)

i i

A d

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 21 OF 112 i

REVISION O

k. -

4 i

v...

-.. -,.v %

.-m.~,,

s

-,-,v-..,

...,y,.m..,

,.c.-,%.,,,%..,..,c y.

.em.,.o,

[ 5.

g

,w

.,.,y

,r,mr 3-hm-w..,ww

,, %,u

__.__..._____.__..____._.m...-._._

__.___._m..

DATE:

June 11, 1992 REACTOR UNIT:

CK1 l

DATA FEEDER:

N/A i

NRC ERDS PARAMETER:

AX FD FL 1/A i

POINT ID:

SP009A PLANT SPEC POINT DESC AUX FEED FLOW LP1 GENERIC /COND DESC:

STM GEN 1 (OR A) AUXILIARY FW FLOW ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

KL8/HR ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

250.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

NA SENSOR LOCATION:

INLET LINE TO SG1 ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY.

I CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON-POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC tbl-21L 1

4 I

i COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 22 OF 112 j

REVISION O i<

5 a

I

DATE:

June 11, 1992 REACTOR UNIT:

CK1 DATA FEEDER:

N/A NRC ERDS PAPAMETER:

AX FD FL 2/B POINT ID:

SPO60A PLANT SPEC POINT DESC: AUX FEED FLOW LP2 GENERIC /COND DESC:

STM GEN 2 (OR B) AUXILIARY FW FLOW ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: KLB/HR 1

ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

250.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A J

l PROC OR SENS:

S j

NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A I

SENSOR LOCATION:

INLET LINE TO SG2 ALARH/ TRIP-SET POINTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE' MODE N/A TEMPERATURE COhPENSATION

-FOR DP TRANSMITlER:-

N LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC:

FFI-220 COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 23 OF 112 hEVISION O

DATE:

June 11, 1992 REACTOR UNIT:

CK1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

AX FD FL 3/C POINT ID:

SP061A PLANT SPEC POINT DESC: AUX PEED FLOW LP3 GENERIC /COND DESC:

STM GEN 3 (OR C) AUXILIARY TW FLOW ANALOG /DIC?'AL:

A ENGR UNITS / DIG STATES: KLB/HR ENGR UNITS CONVERSION: N/A i

MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

250.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS:

S

' NUMBER OF SLNSORS:

I HOW PROCESSED:

N/A SENSOR LOCATION:

INLET LINE TO SG3 ALARM / TRIP. SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A-INSTRUMENT FAILURE. MODE N/A TEMPERATURE COMPENSATION-i FOR DP TRANSMITTER:

- N l

LEVEL REFERENCE LEG

- N/A-UNIQUE SYSTEM DESC:

FFI-230 4

e l

?

j COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY DAGE 24 OF 112 3

REVISION 0-I

f. '

b y, r, m -,y h --., -ynm

,m

, ~.,v~*,,,w+,,g,w,w,,,,y,.,,,,,,,,,,,,,,.yy-,,..,

,,,,,,~,.ve--y-,-e

.- y e

,,,y,. e

,p r w.m w,w ~,., y r, ym, 2

,-w.-

4,--

DATE:

June II, 1992 REACTOR UNIT CK1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

AX FD FL 4/D POINT ID:

SP010A PLANT SPEC POINT DESC: AUX FEED FLOW LP4 GENERIC /COND DESC:

STM GEN 4 (OR D) AUXIARY FW FLOW ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: KLB/HR ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

250.0 ZERO POINT REFERENCES-N/A REFERENCE POINT NOTES: N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A EENSOR LOCATION:

INLET LINE TO SG4 ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A HI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC:

FFI-240 COOK NUCLEAR PLANT - SMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 25 OF 112 REVISION O

DATE:

June 11, 1992 REACTOR UNIT CK1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

HL TEMP 1/A POINT ID T0419A PLANT SPEC POINT DESC: RCL1 HOT TEMPERATURE GENERIC /COND DESC:

STM GEN 1 (OR A) INLET TEMPERATURE ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTESt. N/A PROC OR SENS:

S

. NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR I.OCATION:

LOOP 1 HOT LEG INLET OF SG1 ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL -

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC:

NTR-110

. COOK NUCLEAR PLANT - 4MERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 26 OF 112

REVISION 01

~

m DATE:

-June 11, 3"92-REACTOR UNIT -.

CK.'

DATA FEEDER:

N/A NRC ERDS PARAMETER:

HL TEMP 2/B POINT ID:

T0439A PLANT SPEC POINT DESC: RCL2 HOT TEMPERATURE GENERIC /COND DESC:

STM GEN 2 (OR B) INLET TEMPERATURE ANALOG / DIGITAL:

-A ENGR UNITS / DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR LOCATION:

LOOP 2 HOT LEG INLET TO SG2 ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER-SUPPLY CUT-OFF POWER LEVEL:

N/A

-NI DETECTOR POWER SUPPLY TURN-ON_ POWER _ LEVEL:

-N/A INSTRUMENT FAILURE MODE N/A

-TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG '

N/A-UNIQUE SYSTEM DESC:

NTR-120-

[ COOK' NUCLEAR PLANT - EMERGENCY RESPONSE-DATA-SYSTEM DATA POINT LIBRARY PAGE'27 OF 112.

REVISION O

.. ~ -...

.. ~.. - -.

.... - - _- - - -. - ~ -

. _... -..,, ~. ~...

1 a

i.

DATE:

June'll, 1992 REACTOR UNITa-CK1 3'

DATA FEEDER:

N/A NRC ERDS PARAMETER:

HL TEMP 3/C POINT'ID:

T0459A l

1 PLANT SPEC POINT DESC:

RCL3 HOT TEMPERATURE GENERIC /COND DESC:

STM GEN 3 (OR C) INLET TEMPERATURE ANALOG / DIGITAL:

A i

l-ENGR UNITS / DIG STATES: DEGF J

(

ENGR UNITS CONVERSION:

N/A i

- MINIMUM' INSTR RANGE:

0.0 L

MAXIMUM INSTR RANGE:

700.0 f

l ZERO POINT

REFERENCE:

N/A

}

F.EFERENCE POINT. NOTES:

N/A.

4 PROC OR-SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A 1

j SENSOR LOCATION:

LOOP 3 HOT LEG' INLET TO SG3 I

- ALARM / TRIP SET PCINTS:

N/A l

1 l-NI DETECTOR' POWER SUPPLY t

CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY l_

TURN-ON POWER LEVEL:

N/A i

INSTRUMENT FAI -IRE MODE N/A TEMPERATURE COMPENSATION-j-

FOR DP. TRANSMITTER:

N/A i-LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC '

NTR-130.

1 3~

f f

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM' y

DATA POINT LIBRARY-

.PAGE 28 OF.112-REVISION O d

i '

A 1

3.

I i-

. -, -.. - ~.... -. -,...,.,, -

1'

-j s

i I

DATE:

June 11, 1992 f

REACTOR UNIT:

CK1 -

}.

DATA FEEDER:

N/A 1

NRC ERDS PARAMETER:

HL TEMP 4/D 4

1 POINT ID:

T0479A

-1 PLANT SPEC POINT DESC: 'RCL4 HOT TEMPERATURE 1

i.

j-GENERIC /COND DESC:

STM GEN 4 (OR D) INLET TEMPERATURE s

J j

ANALOG / DIGITAL:

A i

ENGR UNITS / DIG STATES:

DEGF ENGR UNITS CONVERSION: N/A i

MINIMUM INSTR RANGE:

0.0 4

i r

j MAXIMUM INSTR RANGE:

700.0 1

ZERO POINT

REFERENCE:

N/A I

REFERENCE POINT NOTES: N/A PROC OR SENS:

S NUMBER OF SENSORS:

'l HOW PROCESSED:

N/A 4

SENSOR LOCATION:

LOOP 4 HOT LEG INLET TO'SG4

}-

ALARM / TRIP SET POINTS:

N/A I

NI DETECTOR POWER SUPPLY j

CUT-OFF POWER LEVEL:

N/A

.-j.

NI DETECTOR POWER SUPPLY a

TURN-ON POWER LEVEL:

N/A 1

l INSTRUMENT FAILURE MODE N/A 7.

r TEMPERATURE COMPENSATION-FOR DP. TRANSMITTER:

N/A i

{

LEVEL REFERENCE LEG N/A I

UNIQUE SYSTEM DESC:

NTR-140 i

e i

1 i

COOK NUCLEAR PLANT - EMERGENCY-RESPONSE DATA-SYSTEM DATA POINT LIBRARY

- PAGE'29 OF 112-REVISION-C 3-l 0

2 s

,.4

.~..,m.,~.._...-,._.....a..m.,,,,~.;.'.,..

,,, - ~ -,..

._.~.

..-. ~. _...

.. -...-.... ~

4 1

- i j.

I k

{

DATE:

June 11, 1992

)

REACTOR UNIT:

CK1 DATA' FEEDER:.

N/A l

NRC ERDS PARAMETER:

CL TEMP I/A l

POINT ID -

T0406A i-

}-

. PLANT SPEC POINT DESC: RCL1 COLD TEMPERATURE J

GENERIC /COND DESC:

STM GEN 1 (OR A) OUTLET TEMPERATURE j

ANALOG / DIGITAL:

A' i

l ENGR UNITS / DIG STATES ' DEGF l

ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0,0 MAXIMUM INSTR RANGE:

700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A-i; PROC OR SENS:.

S NUMBER OF SENSORS:

1 I

l HOW PROCESSED:

N/A 1

}

SENSOR LOCATION -

LOOP 1 COLD LEG INLET TO REACTOR 4

. ALARM / TRIP SET POINTS: N/A l

NI DETECTOR POWER SUPPLY j

CUT-OFF POWER LEVEL:

N/A i

NI DETECTOR POWER SUPPLY

!~

TURN-ON POWER LEVEL:

N/A 1

INSTRUMENT FAILURE MODE N/A

}

TEMPERATURE COMPENSATION E

FOR.DP. TRANSMITTER -

N/A r

j LEVEL REFERENCE LEG N/A 1

j UNIQUE SYSTEM DESC -

NTR-210 1

b-1 a

d 4

' COOK NUCLEAR PLANTL-EMERGENCY RESPO!;SE DATA SYSTEM DATA POINT LIBRARY PAGE 30 OF 1121 1

j REVISION O 4

1 4

i 1

,, a n,- v c,-w.,,

v,n,,--,--n-

-~r-,-,

,.,, s.e w,,

,...-.,v.

n,-=e,d,,,n,~~~,.e.,

-, n.- -,-n., n. b w m

nrnnn-,-----,~.-,..,,,n..

. ~.

l 1-

- i DATE:

June 11, 1992 j

- REACTOR UNIT:

CK1

- DATA FEEDER:

N/A 4

NRC ERDS PARAMETER:

. CL TEMP 2/B POINT-ID:

T0426A 4

t PLANT SPEC POINT DESC:

RCL2 COLD TEMPERATURE i

4 GENERIC /COND DESC:

STM GEN-2 (OR B) OUTLET TEMPERATURE ANALOG / DIGITAL A

ENGR UNITS / DIG STATES: DEGF j

ENGR UNITS' CONVERSION: N/A 4

MINIMUM INSTR RANGE:

0.0 l

MAXIMUM INSTR RANGE:

700.0 i

ZERO POINT

REFERENCE:

N/A' i

j REFERENCE POINT NOTES:

N/A i

PROC OR SENS:

S NUMBER OF SENSORS:

1 i

{,

HOW PROCESSED:

NA

{

SENSOR LOCATION:

LOOP 2 COLD LEG INLET TO REACTOR 4

l-ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A t

l NI DETECTOR POWER: SUPPLY

- TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A i

i --

TEMPERATURE-COMPENSATION

- FOR DP TRANSMITTER:

N/A 4-1 LEVEL REFERENCE LEG

- N/A

~

UNIQUE SYSTEM DESCt~

NTR-220' 4

l' I

TCOOK NUCLEAR PLANT - EMERGENCY RESPONSE-DATA SYSTEM DATA POINT LIBRARY PAGE 31 OF.112 i

REVISION O 4

4

.w g,-

ve.

y r.we, g,

,eg,%

a,,

iir..

y

.er-n m

,3.s,

,,se-..,-,

.-<pvw,r--.w y-,

,w r----e N.-

y e

-w w. - e

.'c=w..,+4

... _.... ~..

4 i

1-j.

DATE:

June 11, 1992 i

REACTOR UNIT:

CKI l

N/A DATA FEEDER:

1 j.

NRC ERDS PARAMETER:

-CL TEMP 3/C POINT ID:

T0446A PLANT SPEC POINT'DESC RCL3 COLD TEMPERATURE b

i GENERIC /COND DESC:

STM GEN 3 (OR C) OUTLET TEMPERATURE 1

l ANALOG / DIGITAL:

A 4

i ENGR UNITS / DIG STATES: DEGF i

1 ENGR UNITS CONVERSION: N/A a

MINIMUM INSTR RANGE:

0.0 l

i MAXIMUM INSTR RANGE:

700.0 i

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A

_1.

j-PROC OR siENS:

S ij.

NUMBER OF SENSORS:

1 i

y

-HOW PROCESSED:

N/A SENSOR LOCATION:

LOOP 3 COLD LEG INLET TO REACTOR ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY-TURN-ON POWER LEVEL:

-N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION-t FOR DP TRANSMITTER:

N/A i

LEVEL REFERENCE LEG N/A UNIQUE SYSTEM.DESC:

.NTR-230 i

COOK NUCLEAR PLANT EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY

PAGE 32'OF 112 i

REVISION O l

l

)

i DATES.

June 11, 1992

- REACTOR UNIT:

CK1

. DATA FEEDER:

N/A NRC ERDS PARAMETER:

CL TEMP 4/D

- \\

POINT ID:

T0466A 1

i PLANT-SPEC POINT DESC:

RCL4 COLD TEMPERATURE-GENERIC /COND DESC:

STM GEN 4 (OR D) OUTLET _ TEMPERATURE i

ANALOG / DIGITAL:

A 4

4 ENGR UNITS / DIG STATES: DEGF i

ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0,0 MAXIMUM INSTR RANGE:

700.0 ZERO POINT-

REFERENCE:

N/A REFERENCE POINT NOTES: N/A

=

PROC OR SENS:

S NUMBER OF SENSORS:

~

1 HOW PROCESSED:

N/A SENSOR LOCATION:

LOOP 4 COLD LEG INLET TO REACTOR ALARM / TRIP SET ~ POINTS: N/A j-NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A j

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A j

INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP. TRANSMITTER:

N/A

- LEVEL REFERENCE LEG N/A l-UNIQUE SYSTEM DESC:

NTR-240 f._

l t

l-4 COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM

~

I DATA-POINT LIBRARY PAGE'33 OF 112-l REVISION O I

i l

i.

,4~.

e+-~

DATE:

June 11, 1992 REACTOR UNIT:

CK1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

RCS-PRESSURE POINT ids U1313 PLANT SPEC POINT DESC: RCL SYSTEM PRESSURE GENERIC /COND DESC:

REACTOR COOLANT SYSTEM PRESSURE ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

3000.0-1 ZERO POINT

REFERENCE:

~ N/A REFERENCE POINT NOTES: N/A PROC OR SENS:

P NUMBER OF SENSORS:

2 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

LOOP 1 AND 2 HOT LEG INLET TO SG1 AND SG2 ALARM /TR"P SET POINTS:

425 LOW NI DETECTOR POWER SUPPLY CUT-OFF-POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:-

N/A

-LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC:.

NPS-121, NPS-122 COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM.

DATA POINT LIBRARY PAGE.34 OF 112 REVISION O

_a w__-.

... ~... -....

.-.. - ~.

,~

-. - -. ~....

4' 4

DATE:

June 11/ 1992 REACTOR UNIT CK1

~

j-DATA FEEDER:

N/A NRC_-ERDSIPARAMETER:

PRZR LEVEL POINT ID:

.UO483 I'

PLANT SPEC POINT DESC PRESSURIZER LEVEL 1/2/3 AVG i

GENERIC /COND DESC:

PRIMARY SYSTEM PRESSURIZER LEVEL j

ANALOG / DIGITAL:

A ENGR UNITS / DIG 'iTATES:

i f

~ ENGR UNITS' CONVERSION:

N/A j-MINIMUM INSTR 9ANGE:

0.0 i-MAX 1 MUM INSTR RANGE:

100.0 d ~

ZERO POINT

REFERENCE:

COMPLX REFERENCE POINT NOTES: AT 0% 36" ABOVE DOTTOM OF PRZR VESSEL PROC OR SENS:

P i

i NUMBER OF SENSORS:

3 f

HOW PROCESSED:

AVERAGE-

[

SENSOR LOCATION:

36" ABOVE BOTTOM OF. PRESSURIZER VESSEL i

1 ALARM / TRIP SET POINTS:

92 HIGH NI DETECTOR POWER SUPPLY l

CUT-OFF POWER LEVEL:

N/A l

NI DETECTOR POWER SUPPLY j_

TURN-ON POWER LEVEL:

,N/A

~

INSTRUMENT FAILURE MODEtN/A-l TEMPERATURE COMPENSATION 4-FOR DP-TRANSMITTER:

.Y LEVEL REFERENCE LEG WET UNIQUE SYSTEM DESC -

NLP 151, NLP-152, NLP-153 4

I

[

e l

COOK NUCLEAR PLANT -. EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 35 OF-112 E

REVISION O 1

e

,..,,,-i

,n,,.,-

~,

-.~-

,,.,e...,,...,

,;_,..,,,nrn,,,,,

,w-,..

.. ~.. - - -..... -. -. -, -. -. - -.

i DATE:

June 11, 1992 4

REACTOR UNIT:

CK1 DATA FEEDER:

N/A l

NRC ERDS PARAMETER:

RCS CHG/MU POINT ID:

U1613 I

PLANT SPEC POINT DESC TOTAL CHARGING FLOW j

GENERIC /COND DESC:

PRIMARY SYSTEM CHARGING OR MAKEUP FLOW J

ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: GPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 3

MAXIMUM INSTR RANGE:

200.0 7ERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS:

P i

NUMBER OF SENSORS:

5 1

+

j' HOW PROCESSED:

SUM

{

SENSOR LOCATION:

DISCHARGE' HEADER OF CHARGING PUMPS AND COLD' LEG'OF ALL i

FOUR LOOPS s

{

ALARM / TRIP SET POINTS:

40.0 LOW i

f NI DETECTOR POWER SUPPLY

(

CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A-INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION j

FOR DP TRANSMITTER:

N f

LEVEL REFERENCE LEG N/A-j-

4 UNIQUE SYSTEM DESC:

QFI-200, IFI-51, IFI-52, IFI-53, IFI 3 3

4 E

' COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM-DATA POINT LIBRARY PAGE 36 OF 112 j

REVISION O e

t-4 3.

_,..-...-.m.._.,-

.~

4 DATES-June 11, 1992 REACTOR UNIT:

CK1 i

DATA FEEDER:

N/A NRC ERDS PARAMETER:

MP SI FLOW POINT ID:

U1603 1

j-PLANT SPEC POINT DESC:

TOTAL SAFETY INJECTION FLOW f

{

GENERIC /COND DESC:

HIGH PRESSURE SAFETY INJECTION FLOW f

ANALOG / DIGITAL:

A 4

ENGR UNITS / DIG STATES: GPM I

ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 6

i MAXIMUM INSTR RANGE:

1600.0 f

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A f

PROC OR SENS:

P 4

i NUMBER OF SENSORS:

2 h

j-HOW PROCESSED:

SUM i

j SENSOR LOCATION:

SI-PUMPS DISCHARGE LINE TO COLD LEGS i

l ALARM / TRIP SET POINTS:

N/A 1

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY' TURN-ON POWER LEVEL:

N/A j

INSTRUMENT FAILURE MODE:N/A

[

TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N

+

f LEVEL REFERENCE LEG N/A j

UNIQUE SYSTEM DESC:

IFI-260, IFI-266-l i

4 i

a j.

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 37 OF 112 REVISION O i-1 l.

~_

1 l

l-

'DATE:

June 11, 1992 REACTOR UNIT:

CK1 i

DATA FEEDER:

N/A NRC ERDS PARAMETER:

LP SI FLOW l

FOINT ID:

U1604 PLANT SPEC POINT DESC:

TOTAL RHR FLOW GENERIC /COND DESC:

LOW PRESSURE SAFETY INJECTION FLOW ANALOG / DIGITAL:

A i

I ENGR UNITS / DIG STATES - GPM ENGR UUITS CONVERSION: N/A l

MINIMUM INSTR RANGE:

0.0

(

MAXIMUM INSTR RANGE:

10000.0

[

ZERO POINT

REFERENCE:

N/A j

REFERENCE POINT NOTES: N/A i

PROC OR SENS:

P NUMBER OF SENSORS:

4-i HOW PROCESSED:

SELECT PROPER RANGE PER LEG, SUM LEGS 1-SENSOR LOCATION:

RHR PUMPS DISCHARGE LINE TO HOT LEGS ALARM / TRIP SET POINTS: N/A i

NI DETECTOR POWER SUPPLY i.

CUT-OFF POWER LEVEL:

N/A e

NI DETECTOR POWER SUPPLY

[

TURN-ON POWER LEVEL:

N/A INSTRUMENT-FAILURE MODE N/A TEMPERATURE COMPENSATION-l FOR-DP TRANSMITTER:

N

!~

LEVEL REiERENCE LEG:

N/A j

UNIQUE SYSTEM DESC -

IFI-310, IFI-311, IFI-320, IFI-321 i

i i

. COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 38 OF: 112 i

REVISION O 1

l

'l l

A

l DATE:

June 11, 1992 REACTOR UNIT:

CK1 DATA FEEDER:

N/A-NRC ERDS PARAMETER:

CTMNT SMP NR POINT ID:

U1605 PLANT SPEC POINT DESC: AVG CNTMT SUMP NR LEVEL GENERIC /COND DESC:

CONTAINMENT SUMP NARROW RANGE LEVEL 1

ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

f

~

ENGR UNITS CONVERSION:

0=589'-5" 100=599'-8" MINIMUM INSTR RANGE:

0.0 j -

MAXIMUM INSTR RANGE:

100.0 L

j ZERO POINT

REFERENCE:

COMPLX REFERENCE POINT NOTES: AT 0% 5 INCHES'ABOVE BOTTOM OF SUMP ii PROC OR SENS:

P i

NUMBER OF SENSORS:

2 1

l HOW PROCESSED:

AVERAGE j

SENSOR LOCATION:

LOWER CNTMT SUMP j-ALARM / TRIP SET POINTS:

83.75 HI 8.95-LOW NI DETECTOR POWER SUPPLY l

CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY-4 l

TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION j.

FOR DP TRANSMITTER:

Y LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC:

NLA-310,.NLI-311 i:

i i-COOK NUCLEAR' PLANT.- EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 39 OF 112 REVISION O 4

. ~,

.-,.a - - -..

.__.-._~_.. _ -.. __

~.

1 DATE:

June 11, 1992 1

REACTOR UNIT:

CK1 f

DATA FEEDER:

N/A-1 NRC ERDS PARAMETER:

CTMNT SMP WR POINT ID:

- U1606 1-

]

PLANT SPEC PCINT DESC AVG CTMNT SUMP WR LEVEL i

l GENERIC /COND DESC:

CONTAINMENT SUMP WIDE RANGE LEVEL ANALOG /DIGITALt A

ENGR UNITS / DIG STATES:

j

. ENGR UNITS CONVERSION:. 0=599'-3" 100=614' f

MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

100.0 j

ZERO POINT

REFERENCE:

COMPLX 1

l REFERENCE POINT NOTES. 0% AT ELEV. 599'-3"

{

PROC OR SENS:

P

- NUMBER OF SENSORS:

2 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

LOWER CNTMT SUMP ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY-CUT-OFF POWER LEVELt-N/A i'

NI DETECTOR POWER SUPPLY l _.

TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION =

FOR DP TRANSMITTER:

Y i

LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC:

NLI-320, NLI-321 t

i COOK NUCLEAR. PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT' LIBRARY PAGE 40 OF 112 h

REVISION O i

i 1

1 1

y -


,p 7

e-4 +

,we e,,w w

e--

n

--w-

_..._m j

a 1

a 1

DATE:

June 11, 1992 REACTOR UNIT:

CK1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

EFF GAS RAD POINT ID:

U1614 j

PLANT SPEC POINT DESC:

UNIT VENT EFFLUENT MONITOR i

]

GENERIC /COND DESC:

RADIOACTIVITY OF RELEASED GASES l

ANALOG / DIGITAL:

A j

ENGR UNITS / DIG STATES: pCI/HR j

ENGR UNITS CONVERSION:

N/A i

MINIMUM INSTR RANGE:

0.0 f.

~

MAXIMUM-INSTR RANGE:

3.0E+16 l

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

P NUMBER OF SENSORS:

4 i

HOW PROCESSED:

SELECTION, MULTIPLICATION i

SENSOR. LOCATION:

AUX BLDG VENT STACX ALARM / TRIP SET POINTS:

N/A

}

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY l

TURN-ON POWER LEVEL:

N/A INSTRUMENT' FAILURE MODE N/A TEMPERATURE COMPENSATION j-FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC.

VRS-1505, VRS-1507, VRS-1509,~ VRS-1510 SELECTION OF LOW, MEDIUM,-AND HIGH UNIT VENT INSTRUMENTS BASED ON

-EFFLUENT CONCENTRATION TIMES THE MEASURED FLOW RATE IN j

UNITS OF pCI/HR l

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM j

DATA POINT LIBRARY PAGE 41 OF 112 REVISION O 4

L 4

-. - ~.

+

u

.r.-

. - ~

-.--.. ~...... _...-

I, I

J DATE:

June 11, 1992 i

REACTOR UNIT:

CK1 i

j DATA FEEDER:

N/A NRC ERDS PARAMETER:

EFF LIQ RAD POINT ID:

RMS001 PLANT SPEC POINT DESC: WASTE DISPOSAL SYSTEM EFFLUENT MONITOR f

GENERIC /COND DESC:

RADIOACTIVITY OF RELEASED LIQUIDS 1-4.

ANALOG / DIGITAL:

A j

i ENGR UNITS / DIG STATES:

CPM f

i j

ENGR UNITS CONVERSIONS N/A MINIMUM INSTR RANGE:

5.0 i

MAXIMUM INSTR RANGE:

5.0E+03 i

ZERO POINT

REFERENCE:

N/A ii REFERENCE POINT NOTES: N/A fj.

PP.OC OR SENS:

S i

NUMBER OF SENSORS:

1 f

HOW PROCESSED:

N/A i

SENSOR LOCATION:

LIQUID WASTE DISPOSAL SYSTEM DISCHARGE f

ALARM / TRIP SET POINTS:

N/A 1

NI DETECTOR POWER SUPPLY l

CUT-OFF POWER LEVEL:

N/A i

l NI DETECTOR POWEP SUPPLY i

TURN-ON POWER LEVEL:

N/A i

l INSTRUMENT FAILURE-MODE N/A l

l

-TEMPERATURE COMPENSATION FOR DP. TRANSMITTER:

N/A LEVEL REFERENCE. LEG N/A UNIQUE SYSTEM DESC:

RRS-1001.

t -.

1000K NUCLEAR PLANT - EMERGENCY RESPONSE = DATA SYSTEM' R

l DATA POINT LIBRARY-PAGE 42 OF 112 T-REVISION O

?

l i-i r,

,,n p

w w.

.-a--

o

+

.,-v w

+

ww, -,-

4 4

)

j DATE:

June 11, 1992 4

-REACTOR UNIT:

CK1 DATA FEEDER:

N/A 4

NRC ERDS PARAMETER:

COND A/E RAD

+

POINT ID:

U1615 j

PLANT SPEC POINT DESC:

SJAE EITLUENT MONITOR GENERIC /COND DESC:

CONDENSER AIR EJECTOR RADIOACTIVITY ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: pCI/HR ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

3.0E+16 i

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS:

P NUMBER OF SENSORS:

4 HOW PROCESSED:

SELECTION, MULTIPLICATION SENSOR LOCATION:

CONDENSER STEAM JET AIR EJECTOR DISCHARGE VENT ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER-SUPPLY s

j CU*-OFF POWER LEVEL:

N/A i

NI DETECTOR POWER SUPPLY-TURN-ON POWER LEVEL:

N/A i

INSTRUMENT FAILURE MODE N/A h

TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A j

LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC:

SRA-7905, SRA-1907, SRA-1909, SRA-1910 SELECTION OF' 4

LOW, MEDIUM, AND HIGH SJAE MONITORS BASED ON EFFLUENT CONCENTRATION TIMES THE MEASURED FLOW RATE IN UNITS OF l

pCI/HR 4

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM i

DATA POINT LIBRARY

- PAGE 43 OF 112 REVISION O i

4

+

w e. n -

e

emw, a

v,---

w-r,,,-

,---~me-wr e-m--

-,mv

_= -... ~

.... ~

t 1

G 1

DATE:

June II, 1992 i

REACTOR UNIT:

CK1 DATA FEEDER:

N/A-

"'C ERDS PARAMETERi CTMNT RAD L

POINT ID -

RMS023 PLANT SPEC POINT DESC:

HI RANGE CTMNT AREA MONITOR 4

)

GENERIC /COND DESC:

RADIATION LEVEL IN THE CONTAINMENT i

ANALOG / DIGITAL:

A j

ENGR UNITS / DIG STATES:

R/HR l

ENGR UNITS CONVERSION - N/A 2

MINIMUM INSTR RANGE:

1.OE+00 I

MAXIMUM INSTR RANGE:

1.OE+07 i

ZERO POINT

REFERENCE:

N/A

- REFERENCE POINT NOTES:

N/A s

PROC OR SENS:

S s

NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR LOCATION:

INSIDE CONTAINMENT l

ALARM / TRIP SET POINTS:

1.OE+01 NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE-MODE N/A TEMPERATURE COMPENSATION.

FOR DP TRANSMITTER:-

N/A LEVEL REFERENCE LEG N/A' UNIQUE SYSTEM DESC:

ERS-1410 t

COOK. NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM-DATA POINT. LIBRARY-PAGE 44 OF 112 REVISION O

.._,,.,_..n...,..

...,_,.,._,,._._,_v.._,m....

..,.,._,~,_;

f

\\

I i

)

DATE:

June 11, 1992 REACTOR UNIT:

CK1 DATA FEEDER:

N/A i

l --

NRC ERDS PARAMETER:

SG BD RAD 1A j-POINT ID R0024A-j-

PLANT SPEC POINT DESC:

SG BLOWDOWN TREATMENT MONITOR q

GENERIC /COND DESC:

STM GEN 1 BLOWDOWN RAD LEVEL j

ANALOG / DIGITAL:

A j-ENGR UNITS / DIG STATES:

CPM i

ENGR UNITS CONVERSION: N/A j

MINIMUM INSTR RANGE:

10.0 i

MAXIMUM INSTR RANGE:

1000000.0 ZERO POINT

REFERENCE:

N/A 1

l REFERENCE POINT-NOTES: N/A PROC OR SENS:

S f-NUMBER s SENSORS:

1 1

HOW PROCESSED:

N/A SENSOR LOCATION:

OUTLET.0F THE STEAM GENERATOR BLOWDOWN HEADER ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY l

CUT-OFF POWER-LEVEL:

N/A UR ON PO ER E EL N/A i

INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION

- FOR'DP TRANSMITTER:

N/A LEVEL REFERENCE LEG:

IN/A J

UNIQUE SYSTEM DESC:

DRA-353 COMMON FOR SG-1,2,3,4 1-1 I

4

+

,e s COOK NUCLEAR PLANT - EMERGENCY RESPONSE. DATA SYSTEM

(,

DATA POINT LIBRARY PAGE 45-OF-112

[

REVISION O

j -

I

...s

-,-_....._a..

..... :; _4..

d I

j DATEt June 11, 1992 3

f REACTOR UNIT:

CK1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

-SG BD RAD 2B 1

POINT ID:

R0024A l

PLANT SPEC POINT DESC:

SG BLOWDOWN TREATMENT MONITOR 4

GENERIC /COND DESC:

STM GEN 2 BLOWDOWN RAD LLIEL ANALOG / DIGITAL:

A i

ENGR UNITS / DIG STATES:- CPM l.

ENGR UNITS CONVERSION: N/A 1

MINIMUM INSTR RANGE:

10.0 MAXIMUM INSTR RANGE:

1000000.0 4.

j ZERO POINT

REFERENCE:

N/A j

REFERENCE POINT NOTES: N/A 1:

PROC OR SENS:

S 5

1.

NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A 3-SENSOR LOCATION:

OUTLET OF THE STEAM GENERATOR BLOWDOWN HEADER 1

]

. ALARM / TRIP' SET POINTS: N/A f

NI DETECTOR POWER. SUPPLY l

CUT-OFF POWER LEVEL -

N/A i

NI' DETECTOR POWER SUPPLY

-TURN-ON POWER LEVEL.

N/A INSTRUMENT FAILURE MODE N/A-TEMPERATURE COMPENSATION FOR.DPl TRANSMITTER:

N/A LEVEL. REFERENCE LEG N/A j

UNIQUE SYSTEM DESC:

DRA-353 COMMON FOR SG-1,2,3'4 3

1-l --

COOK' NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE-46_OF 112;

{_

REVISION O s

1 5

4 4

4~

t.

--... - ~

I r

DATE:

June 11, 1992 i:

REACTOP UNIT CK1 l

DATA FEEDER:

N/A

,l' i

NRC ERDS PARAMETER:

SG BD RAD 3C

- t a

POINT ID:

R0024A l

PLANT SPEC POINT DESC SG BLOWDdWN TREATMENT MONITOR 1

(

GENERIC /COND DESC "

STM GEN 3 BLOWDOWN RAD LEVEL 1

i ANALOG /D7GITAL:

A i

ENGR UNITS / DIG STATES:

CPM 4-ENGR UNITS CONVERSION: : N/A-MINIMUM INSTR RANGE:

10.0 t

MAXIMUM INSTR RANGE:

1000000.0 i

I ZERO POINT

REFERENCE:

N/A REFERENCE' POINT NOTES:

N/A PROC OR SENS:

- S NUMBER OF SENSORS:

1 i

HOW PROCESSED:

N/A l

SENSOR LOCATION:

OUTLET OF THE STEAM GENERATOR BLOWDOWN HEADER t

f ALARM / TRIP SET. POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A 1

'NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A s

l INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR-DP TRANSMITTER:

N/A j:

LEVEL REFERENCE LEG:

N/A-4-

[

UNIQUE SYSTEM DESC:

DRA-353 COMMON FOR SG-1,2,3,4 l

i i

i

.-COOK NUCLEAR PLANT'- EMERGENCY RESPONSE DATA SYSTEM l

DATA POINT LIBRARY PAGE 47 OF 112 REVISION O i

i i

F

-m>-

g a

7

.,m,e---w8

-,,-~

-,v.-

e

. _.... ~ -....

. ~.

.~

.. ~,

4 E

a 4

DATE:

June 11,'1992 REACTOR UNIT:

CK1 -

DATA FEEDER.

N/A j

NRC ERDS PARAMETER:-

SG BD RAD 4D 4-POINT ID:

R0024A i

PLANT $PEC POINT DESC:

SG BLOWDOWN TREATMENT MONITOR l

l GENERIC /COND DESC:

STM GEN 4 BLOWDOWN RAD LEVEL i

ANALOG / DIGITAL:

A l-ENGR UNITS / DIG STATES - CPM i

ENGR UNITS CONVERSION: - N/A MINIMUM INSTR RANGE:

10.0 2

4-j MAXIMUM: INSTR RANGE-1000000,0 i

l ZERO POINT'

REFERENCE:

N/A REFERENCE-POINT NOTES:

N/A 4

PROC OR'SENS:

S

{

NUMBER OF' SENSORS:

1~

l HOW PROCESSED:

N/A it SENSOR LOCATION:

OUTLET OF THE STEAM GENERATOR BLOWDOWN HEADER i

ALARM /TRIPLSET POINTS:

N/A l

NI DETfCTOR POWER SUPPLY j_

CUT-OFF POWER LEVEL _

N/A

[.

NI DETECTOR POWER' SUPPLY l

TURN-ON' POWER LEVEL:

N/A 1'

INSTRUMENT FAILURE-MODE N/A

(

TEMPERATURE. COMPENSATION-i FOR DP TRANSMITTER:

N/A i

LEVEL REFERENCE LEG -

/

NA l

I-UNIQUE SYSTEM DESC:

- DRA-353 COMMON FOR SG-1,2,3,4 3

i 3

i i

COOK NUCLEAR PLANT --EMERGENCY RESPONSE DATA-SYSTEM-DATA POINT LIBRARY.

-PAGE 48 OF'112 REVISION O i

t r

- - r

,n-r.~-

r, rm,

,-,e

,,,,,ew,--w.-

.,,-x.,

m_n,,-,m.,n,,-~,

~,r-~c

+wn.,.e.,a

.,-,,nr,..,n, e,,v,,n,.,....-++...,nnnra,.,w,----

... _ ~.~ _. - -.-- -.

1-4-

i

- DATE:

June 11,.1992 REACTOR UNIT:

CK1 1

3 DATA FEEDER:

N/A NRC ERDS PARAMETER:

CNTMNT PRESS i

POINT ID -

L'1000 PLANT SPEC POINT DESC:

CONTAINMENT P 1/2/3/4 AVG GENORIC/COND DESC:

CONTAINMENT PRESSURE 4

f

' ANALOG / DIGITAL:

A i

. ENGR. UNITS / DIG STATES:

PSIG f

ENGR UNITS CONVERSION ' N/A i

1-MINIMUM INSTR RANGE:

- -5.000 i

l MAXIMUM INSTR RANGES-

12.000 l

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: ~ N/A_

^

L 3

PROC OR SENS:

P NUMBER OF SENSORS:

4.

i l

HOW PROCESSED:

AVERAGE I

SENSOR LOCATION:

INSIDE CONTAINMENT ALARM / TRIP SET POINTS:

1.1 HIGH ~

2.9'HIGH-HIGH 1

NI DETECTOR POWER SUPPLY l

_ CUT-OFF POWER LEVEL:

N/A 1

l NI DETECTOR: POWER SUPPLY-j TURN-ON POWER LEVEL:.

N/A i

j INSTRUMENT FAILURE MODE N/A i

- TEMPERATURE COMPENF*. TION

- FOR DP TRANSMITTER:

N/A LEVEL-REFERENCE LEG N/A-j-,

f UNIQUE SYSTEM DESC: _

PPP-300, PPP-301, PPP-302, PPP-303 li 4-k-

COOK NUCLEAR PLANT'- EMERGENCY RESPONSE' DATA SYSTEM f

DATA _ POINT LIBRARY PAGE 49 OF 112 REVISION O 1

4 ey 1--,

c

,s

-n

'e te 9-v

---yemcm

+-=ts-.--rw v--

p

-r m-

,y,-

-.w-r--y-w+w,-

y, yyw sge.g w -e,e t.wa-cy a-v gr e se **.re e

v.t me.y-we rr e

=w r e,- p.es W + e w w, 4 -w u d-a see

,r e - vg-se

.-~

... ~.....

I j

DATES-June 11, 1992.

REACTOR UNIT:

CK1 DATA FEEDER:

N/A 1

j NRC ERDS. PARAMETER:

-CTMNT TEMP I

POINT ID:

U1609

.f -

l PLANT SPEC POINT DESC:

MAXIMUM CONTAINMENT TEMPERATURE i

GENERIC /COND DESC:

CONTAINMENT TEMPERATURE 4

f ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

DEG F-ENGR UNITS CONVERSION:.N/A 1

[

MINIMUM INSTR RANGE:

0.00 1

MAXIMUM INSTR. RANGE:

300.00 ZERO POINT

REFERENCE:

N/A i

j REFERENCE POINT NOTES: N/A I

PROC OR SENS:

P NUMBER OF SENSORS:

15 HOW PROCESSED:

MAXIMUM

' SENSOR LOCATION:

INSIDE CONTAINMENT AT VARIOUS LOCATIONS ALARM / TRIP SET POINTS: N/A

(

NI DETECTOR POWER SUPPLY-l CUT-OFF POWER LEVEL:

-N/A I

l NI. DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT. FAILURE-MODE N/A TEMPERATURE COMPENSATION j

FOR DP. TRANSMITTER:-

N/A LEVEL REFERENCE LEG N/A i

UNIQUE SYSTEM.DESC '

ETR-102, ETR-112, ETR-12 6, ETR-122,. ETR-117, ETR-118, i

ERT-119, ETR-121,.ETR-113, ETR-127, ETR-136

!?

I f

' COOK NUCLEAR PLANT - EMERGENCY RFSPONSE DATA SYSTEM DATA POINT LIBRARY-PAGE 50 OF 112 REVISION O I

'l l-l t

1 i

i-4-

4 DATE:

June-11, 1992-.

i=

REACTOR UNIT:

CK1 l

DATA FEEDER.

N/A NRC ERDE PARAMETER:

H2 CONC POINT ID:

U1610' r

PLANT SPEC POINT DESC: AVERAGE CONTAINMENT H2 CONC GENERIC /COND DESC:

CONTAINMENT HYDROGEN CONCENTRATION 4.

ANALOG / DIGITAL:

A i

ENGR UNITS / DIG STATES:

ENGR UNITS CONVERSION: N/A MINIMUM; INSTR RANGE:

0.00 i

MAXIMUM INSTR RANGE:

30.00 ZERO POINT'

REFERENCE:

N/A

{

_ REFERENCE POINT NOTES:

N/A PROC OR SENS:

P

-NUMBER OF SENSORS:

2 i'

HOW PROCESSED:

AVERAGE l

SENSOR LOCATION:

INSIDE CONTAINMENT i

-ALARM / TRIP' SET POINTS:

N/A j

NI DETECTOR POWER SUPPLY CUT-OFF' POWER LEVEL:

N/A r

l.-

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A l

INSTRUMENT FAILURE MODE N/A l

TEMPERATURE COMPENSATION l

POR DP TRANSMITTER:

N/A a.

[

LEVEL REFERENCE LEG N/A.

UNIQUE SYSTEM DESC:

H2-AH,'H2-BH-1 I-

[

~

~

COOK NUCLEAR PLANT'- EMERGENCY RESPONSE DATA SYSTEM ~

PAGE 51 OF'112 DATA POINT LIBRARY REVISION O 4

., _ -,....., ~,, _, _........,

I 1

DATE:

June 11, 1992 1

REACTOR UNIT:

CK1 f.

DATA FEEDER:

N/A 1

NRC ERDS PARAMETER:

BWS'r LEVEL i-POINT ID -

U1611 s

PLANT SPEC POINT DESC: AVERAGE RWST LEVEL

1 GENERIC /COND DESC BORATED WATER STORAGE TANK LEVEL ANALOG / DIGITAL

A ENGR UNITS / DIG STATES:

1 ENGR UNITS COKVERSION: N/A i

MINIMUM INSTR RANGES-0.0 MAX 1 MUM INSTR RANGE:

100.0 i

l-ZERO POINT

REFERENCE:

COMPLX REFERENCE POINT NOTES: 89% = 364,434 GALLONS PROC OR SENS:

P NUMBER OF SENSORS:

2 HOW PROCESSED:

AVERAGE I

SENSOR LOCATION:

TAPS ON THE WALLS OF THE RWST i

5' ALARM / TRIP SET POINTS:

98.3 HIGH 32.2 LOW 9.1 LOW-LOW

{

NI DETECTOR POWER SUPPLY j

CUT-OFF POWER LEVEL:

N/A i

i NI DETECTOR POWER SUPPLY

{-

. TURN-ON POWER LEVEL.

N/A

[

' INSTRUMENT FAILURE MODE N/A f

TEMPERATURE COMPENSATION' FOR DP TRANSMITTER:

Y LEVEL' REFERENCE LEG WET i

UNIQUE SYSTEM DESC:

ILS-950, ILS-951 i

i 3 -.

1 I

COOK-NUCLEAR PLANT. EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 52 OF 112 REVISION O l

1 i

~,

.. a..

._&.._-m-.-.._,

I t

i DATE:

June 11, 1992 REACTOR UNIT CK1 l

DATA FEEDER:

N/A NRC ERDS PARAMETER:

WIND SPEED J-j.

POINT ID:

UO804 PLANT SPEC POINT DESC:. MIDAS WIND SPEED (10 M MAIN) 4 GENERIC /COND DESC:

WIND SPEED AT THE REACTOR SITE

~

ANALOG / DIGITAL:

A ENGR UNITF/ DIG STAT 2S MPH e

i ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

125.0 j

ZERO POINT

REFERENCE:

N/A i'

REFERENCE POINT NOTES - N/A l

PROC OR SENS:

S 4j.

NUMBER OF SENSORS:

1 l

HOW PROCESSED:

AVERAGE SENSOR LOCATION:

APPROXIMATELY 1 MILE ENE OF PLANT ALARM / TRIP SET POINTS: N/A l

NI DETECTOR POWER SUPPLY l

CUT-OFF POWER LEVEL:

N/A ii t-NI DETECTOR POWER SUPPLY f_

TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEGS.

N/A UNIQUE SYSTEM DEEC:

EFR-402, AVERAGE.OVER 15 MINUTES AND UPDATED EVERY 15.-

'IINUTES I

4 A

i-

. COOK NUCLEAR PLANT - EKERGENCY. RESPONSE DATA SYSTEM i-DATA POINT LIBRARY PAGE 53 OF 112 REVISION O 1

i 1

a i

y,. v m r..--,;

.-.m...

. ~..._,

.-ma.~

4,,

DATE:

June 11, 1992 REACTOR UNIT:

CK1 DATA FEEDER:

N/A NRO ERDS PARAMETER:

. WIND DIR-POINT ID:

U0003 PLANT SPEC POINT DESC MIDAS WIND DIRECTION-(10 M MAIN)

GENERIC /COND DESC:

WIND DIRECTION AT THE REACTOR SITE ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: DEGFR 1

ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

360.0

.ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENSt-

.S NUMBER OF-SENSORS:

1 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

APPROXIMA14LY 1 MILE ENE OF PLANT ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI. DETECTOR POWER SUPPLY..

TURN-ON POWER LEVEL:

'N/A INSTRUMENT. FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE-LEG N/A UNIQUE SYSTEM DESC:

EFR-412', AVERAGE OVER 15 MINUTES AND UPDATED EVERY 15 MINUTES I

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM

-DATA POINT LIBRARY PAGE 54 OF 112 REVISION O

a-5 DATE:

June II, 1992 i

REACTOR UNIT:

CK1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

STAD CLASS

.)

i POINT ID:

UO602

{

PLANT SPEC POINT DESC: MIDAS DELTA TEMP (MAIN)

GENERIC /COND DESC:

A!R STABILITY AT THE REACTOR SITE i

4 I

ANALOG / DIGITAL:

A ENGR UNITS /DIO STATES:

DEG F/50 M ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

-10.0 MAXIMUM INSTR RANGE:

10.0 i

PERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A-PROC Oh SENS:

P NUMRER OF SENSORSS 2

llOW PROCESSED:

SUDTRACTION SENSOR LOCATION:

APPROXIMATELY 1 MILE ENE OF PLANT ALARM / TRIP SET POINTS:

N/A l

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTPUB!ENT FAILURE MODE N/A.

'fEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC:

ETQ-403, AVERAGE OVER 15 MINUTES AND UPDATED EVERY 15 MINUTES 1

COOK NUCLEAR PLANT-- EMERGENCY RESPONSE DATA SYSTEM-l DATA POINT LIBRARY PAGE 55 OF 112-REVISION O

. _ _ - -... _,,... ~ _, _,..... _. - -.., _ _ -,,,. _ _.. -. _.

. -.. _.~...,.,.. -.,_,.. _,

-.,_... __-._=

DATE:

June 11, 1992 REACTOR UNIT CKI DATA FEEDER:

N/A NRC ERDS PARAMETER:

N/A POINT ID:

K5502 PLANT SPEC POINT DESC ERDS PLANT OR_ SIMULATED DATA GENERIC /COND DESC:

N/A ANALOG / DIGITAL:

D

]

ENGR UNITS /DIO STATES:

N/A i

ENGR UNITS CONVERSION: N/A I

}

MINIMUM INSTR RANGE:

0.0

)

j MAXIMUM INSTR RANGE:

1.0 l

ZERO POINT

REFERENCE:

N/A 1

RE "5 TENCE POINT NOTES: N/A j_

PROC OR SENS:

N/A F

NUMBER OF SENSORS:

N/A 1

1 HOW PROCESSED:

N/A i

SENSOR LOCATION:

N/A ALARM / TRIP SET POINTS:

N/A l

l NI DETECTOR POWER SUPPLY l

CUT-OFF POWER LEVEL:

N/A i

I NI DETECTOR POWER SUPPLY j

TURN-O'? POWER LEVEL:

N/A a

l INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION j

FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG N/A l

UNIQUE SYSTEM DESC:

0.0 MEANS REAL PLANT DATAfl.0 MEANS SIMUALTED PLANT l

DATA I

i I

}'

i i

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM l

DATA POINT LIBRARY PAGE 56 OF'112 i

REVISION O i

i i

i

DATA Po!NT LIBRARY COOK NUCLEAR PLANT UNIT 2 l

1 s

1 i

t 4

9 COOK NUCLEAR PLANT - EMEMGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 57 OF 112 REVISION O f

., _.., _.. ~. - - - -

_ _ _ _._ _._, _ _m.

1 l

?

1 DATE:

June 11, 1992 i

REACTOR UNIT:

CK2 l

DATA FEEDER:

N/A NRC ERDS PARAMETER:

NI POWER RNG i

j POINT ID U1169 l-PLANT SPEC POINT DESC PWR RNG NUCL CllANNEL RMP AVG Q

]

GENERIC /COND DESC:

NUCLEAR INSTRUMENTS, POWER RAMGE f

l ANALOG / DIGITAL:

A r

)

ENGR UNITS / DIG STATES:

j ENGR UNITS CONVERSION: N/A I

MINIMUM INSTR RANGE:

0.0 MAXIu"M INSTR RANGE:

120.0 t

i ZEi.' Mi.4T

REFERENCE:

N/A 1

REFERENCE POINT NOTES: N/A PROC OR SENS:

P

}

NUMBER OF SENSORS:

4 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

OUTSIDE REACTOR VESSEL i

l ALARM / TRIP SET POINTS:

109.0 HIGH I

i NI DETECTOR POWER SUPPLY

{

CUT-OFF POWER LEVEL:

N/A I

NI DETECTOR POWER SUPPLY TURN-ON POWFR LEVEL:

N/A l

INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION I

FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG N/A I

UNIQUE' SYSTEM DESC NRi-41, NRI-42, NRI-43, NRI-44 J

l ll a

j COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM-DATA POINT LIBRARY PAGE 58 OF 112 REVISION O f

_, _, _ - _ _,. _.., -, _. ~ __

_. ~,..., ~, ~..... -.,., _,,,.

a.-.-...~-_-

t 1

j l

DATE:

June 11, 1992 REACTOR UNIT:

CK2 l

DATA FEEDER:

N/A a'

NRC ERDS PARNMETER:

NI INTER RNG l

j POINT ID:

U0972 l

PLANT SPEC POINT DESC:

AVG INTERMEDIATE RANGE SIGNAL i

GENERIC /COND DESC:

NUCLEAR INSTRUMENTS, INTERME'~IATE RANGE l

j ANALOG / DIGITAL:

A i

ENGR UNITS / DIG STATES: pAMPS ENGR UNITS CONVERSION:

N/A 1

MINIMUM INSTR RANGE:

0.00001 j

MAXIMUM INSTR RANGE:

1000.0 i

ZERO POINT

REFERENCE:

N/A-

)

REFERENCE POINT NOTES: N/A PROC OR SENS:

P i

NUMBER OF SENSORS:

2 f..

i HOW PROCESSED:

AVERAGE i

i SENSOR LOCATION:

OUTSIDE REACTOR VESSEL 1

ALARM / TRIP SET POINTS:

N/A

[

NI DETECTOR POWER SUPPLY

~

j CUT-OFF POWER LEVEL:

N/A-

}

NI DETECTOR POWER SUPPLY l

4 TURNuDN POWER LEVEL:

N/A

- INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

. N/A LEVEL REFERENCE Lt.G N/A 1

4-UP1QUE SYSTEM DESC:

NRI-35, NRI-36 TRIP SET POINT AT CURRENT (pAMPS).

4 EQUIVALENT TO LESS THAN OR EQUAL TO 25% TMERMAL POWER l

ON EACH INPUT, TRIP MANUALLY DEFEATED AFTER 10?. NIS POWER e

i.

l

}.

COOK. NUCLEAR PLANT - EMERGENCY-RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 59 OF 112 j

REVISION O i

)

d 4

1 +

r-q w s ey -t m-r as-o v e..*y w

--r--.

v vm m-

--owww-=v e n w w -

we-- w e g=-y-w.,

w 1,+-

-~w.w

,= w-w e-e-a rw-egewv---+------ep w-ww.*-+=*wt-=&w.yer e

+-Fora-++F**

= t-w s-ear < m s-- w w e+ 9

i i

i DATE:

June 11, 1992 j

REACTOR UNIT:

CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

NI SOURCE RNG i

j POINT ID:

UO989 4

l PLANT SPEC POINT DESC: AVERAGE NIS SOURCE RANGE 1

GENERIC /COND DESC:

NUCLEAR INSTRUMENTS, SOURCE RANGE l~

ANALOG / DIGITAL:

A l

ENGR UNITS / DIG STATES:

CPS ENGR UNITS CONVERSION:

N/A MINIMUM INSTR. RANGE:

1.0 j

MAXIMUM INSTR RANGE:

1000000.0 ZERO POINT

REFERENCE:

N/A i

i REFERENCE POINT NOTES:

N/A

}

PROC'OR SENS:

P l

NUMBER OF SENSORS:

2 1

HOW PROCESSED:

AVERAGE a

SENSOR LOCATION:

OUTSIDE REACTOR VESSEL ALARM / TRIP SET. POINTS:

100000.0 TRIP NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

1.0E-10 AMPS i

j NI DETECTOR POWER SUPPLY s

TURN-ON POWER LEVEL:

6.0E-11 AMPS i

INSTRUMENT FAILURE MODE N/A I

TEMPERATURE COMPENSATION j

FOR DP TRANSMITTER:

N/A i

LEVEL REFERENCE LEG N/A i

UNIQUE SYSTEM DESC:

NRI-31,-NRI i COOK N9 CLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM.

DATA POINT LIBRARY PAGE 60 OF 112-REVISION O

1 1

DATE:

June 11, 1992 l

l REACTOR UNIT:

CK2 l

1 j

DATA FEE 9ER:

N/A

)

i NRC ERDS PARAMETER:

REAC VES LEV i

l l

POINT ID:

U1602 1

PLANT SPEC POINT DESC: AVERAGE RVLIS NARROW RANGE

)

a GENERIC /COND DESC REACTOR VESSEL WATER LEVEL I

i 2

ANALOG / DIGITAL:

A i

l ENCR UNITS / DIG STA','ES:

i ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 y

4

{-

MAXIMUM INSTR RANGE:

120.0 f

ZERO POINT-

REFERENCE:

COMPLX j~

REFERENCE POINT NOTES:

60 % TOP OF FUEL I

i PROC OR SENS:

P i

j NUMBER OF SENSORS:

1 1

HOW PROCESSED:

AVERAGE i

i i

SENSOR LOCATION:

TAPS AT BOTTOM AND TOP OF REACTOR VESSEL ALARM / TRIP SET POINTS: N/A l-NI DETECTOR POWER SUPPLY j

CUT-OFF POWER LEVEL:

N/A j

NI DETECTOR-POWER SUPPLY

~

TURN-ON POWER LEVEL:

N/A j

INSTRUMENT FAILURE MODE N/A i

TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

Y i

LEVEL REFERENCE LEG WET UNIQUE SYSTEM DESC:

NLI-110, NLI-ill ONLY VALID WHEN RCP'S ARE OFF,=WILL BE PEGGED.HIGH WHEN RCP'S RUNNING I'

1

. COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM-l DATA POINT LIBRARY PAGE 61 OF-112 REVISION O 4

_.. ~.... _ _. - _,.,

.,m,.,._,---._y.

.-e.

-..-~._,_._cm-

-.m...

DATE:

June 11, 1992 REACTOR UNIT CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

REAC VLS LEV POINT ID:

U1601 PLANT SPEC POINT DESC:

AVERAGE RVLIS WIDE RANGE GENERIC /COND DESC:

REACTOR VESSEL WATER LEVEL ANALOO/ DIGITAL:

A ENGR UNITS / DIG STATES:

ENGR UNITS CONVERSION:

N/A LINIMUM INSTR RANGE:

0.U h.

MAXIMUM INSTR RANGE:

I20.0 ZERO POINT

REFERENCE:

COMPLX i

j REFERENCE TOINT NOTES:

N/A i

PROC OR SENS:

P i

j NUMBER OF SENSORS:

2 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

TAPS AT BOTTOM AND TOP OF REACTOR VESSEL

}

ALARM / TRIP SET POINTS:

N/A j

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A i

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION I'

FOR DP TRANSMITTERt Y

i i

LEVEL REFERENCE LEG WET i

UNIQUE SYSTEM DESC -

NLI-130, NLI-13; ONLY VALID WHEN RCP'S ARE RUNNING l

4 COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA-SYSTEM DATA POINT LIBRARY PAGE 62 OF 112 REVISION O i

. - -. - _ _ - _.. - _ -. - - - ~..

1 DATE:

Juno II, 1992 j

REACTOR UNIT:

CK2 DATA FEEDER:

N/A j

NRC ERDS PARAMETER:

TEMP CORE EX POINT ID:

UOO90 j

PLANT SPEC POINT DESC:

INST VALUE OF !bTTEST INCORE TC Ii GENERIC /COND DESC:

HIGHEET TEMPERATURE AT THE CORE EXIT 1

{

ANALOG / DIGITAL:

A j

ENGR UNITS / DIG STATES:

DEGF 1-ENGR UNITS CONVERSION:

N/A 1

l HINIMUM INSTR RANGE:

200.0 i

MAXIMUM INSTR RANGE:

2300.0 i

j ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

P l

NUMBER OF SENSORS:

65 HOW PROCESSED:

HOTTEST OF 65 CORE EXIT T/C'S j-SENSOR LOCATIONS.

THROUGHOUT CORE ALARM / TRIP SET POINTS:

700.0 HIGH

- i 7

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A i

i NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPER 7.fURE COMPENSATION j

FOR DP TRANSMITTER:

N/A-t LEVEL REFERENCE LEG:

N/A l

UNIQUE SYSTEM.DESC:

N/A J

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 63 OF 112' REVISION O.

4

.%.,_+.,s.m...

,.g_.

,.mm...

.,s_,

.-,..,,y.E,,.,,,,.

,y

~,_.'._ry.

DATE:

June II, 1992 REACTOR UNIT CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

SUB HARGIN POINT ID:

UO965 PLANT SPEC POINT DESC: HOTTEST T/C MARGIN TO SATURATION GENERIC /COND DESC:

SATURATION TEMPERATURE - HIGHEST CET ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

2300.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT t:OTES: N/A PROC OR SENS:

P NUMBER OF SENSORS:

2 HOW PROCESSED:

SAT TEMP - MAX CET SENSOR LOCATION:

T/C'S IN CORE ALARM / TRIP SET POINTS:

29.0 LOW 600.0 HIGH NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY.

TURN-ON POWER LEVEL:.

N/A INSTRUMENT FAILURE MODE:N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG N/A

-UNIQUE SYSTEM DESC:

UOO95, U0090- SATURATION TEMPERATURE BASED ON MINIMUM WIDE' RANGE RCS PRESSURE MINUS THE MAXIMUM CORE EXIT THERMOCOUPLE TEMPERATURE-COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 64 OF 112 REVISION O

DATE:

June 11, 1992 REACTOR UNIT CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

CORE FLOW POINT ID:

U1612 PLANT SPEC POINT DESC:

TOTAL RCS FLOW GENERIC /COND DESC:

TOTAL REACTOR COOLANT FLOW ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: GPM ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

403040.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

91600 GPM PER PUMP PROC OR SENS:

P NUMBER OF SENSORS:

12 HOW PROCESSED:

AVERAGE PER LOOP, SUM OF 4 LOOPS SENSOR LOCATION:

COLD LEG SUCTION LINE TO RCP'S ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON-POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION l

FOR DP TRANSMITTER:

N LEVEL REFERENCE LEG N/A UN7QUE SYSTEM DESC:

NFP-210, NFP-211, NFP-212,'NFP-220, NFP-223, NFP-222, NFP-230, NFP-231, NFP-232, NFP-240, NFP-241, NFP-242 i

i COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM i

DATA POINT LIBRARY PAGE 65 OF 112 REVISION O 1

-l i

i 1

l DATE:

June 11, 1992 REACTOR UNIT:

CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

SG LEVEL 1/A POINT ID:

LO403A PLANT SPEC POINT DESC:

STM GEN 1 WIDE RNG L GENERIC /COND DESC:

STEAM GENERATOR 1 (OR A) WATER LEVEL ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

ENGR UNITS CONVERSION: N/A i

MINIMUM INSTR RANGE:

. 0. 0 i

l MAXIMUM INSTR RANGE:

100.0 i

1 ZERO POINT

REFERENCE:

COMPLX REFERENCE POINT NOTES: AT 0% 38.3 FT BELOW TOP OF FW INLET PIPE I

PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR LOCATION:

38.3 FT BELOW TOP OF FW INLET PIPE J

I ALARM / TRIP SET POINTS:

N/A i

NI DETECTOR POWER SUPPLY l

CUT-OFF POWER LEVEL:

N/A f

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

Y 1-l LEVEL REFERENCE LEG WET UNIQUL SYSTEM DESC:

BLI-110 l

1 i

6 COOK NUCLEAR PLANT'- EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 66 OF 112' REVISION O i

4

- -. - - - - ~ - - ~.. - - - -... -... -. -. - - -

l i

1 1

4 DATE:

June II, 1992 REACTOR UNIT:

CK2 DATA FEEDER:

N/A j

NRC ERDS PARAMETER:

SG LEVEL 2/B I

j POINT ID:

LO423A j,

PLANT SPEC POINT DESC:

STM GEN 2 WIDE RNG L GENERIC /COND DESC:

STEAM GENERATOR 2 (OR B) WATER LEVEL I

ANALOG /DIJITAL:

A j

4

.\\

j ENGR UNITS / DIG STATES:

i j

ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

100.0 ZERO POINT

REFERENCE:

COMPLX REFERENCE POINT NOTES: AT 0% 38.3 FT BELOW TOP OF FW INLET PIPE i

PROC OR SENS:

S NUMBER OF SENSORS:

I HOW PROCESSED:

N/A SENSOR LOCATION:

38.3 FT BELOW TOP OF FW INLET PIPE i

ALARM / TRIP SET POINTS: N/A i-NI DETECTOR POWER SUPPLY j

CUT-OFF POWER LEVEL:

N/A i

NI DETECTOR POWER SUPPLY j

TURN-ON POWER LEVEL.

N/A l

INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION l

FOR DP TRANSMITTER:

Y LEVEL REFERENCE LEG WET.

1 j.

UNIQUE SYSTEM DESC:

BLI-120 I

l f

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM

^ DATA POINT LIBRARY l PAGE 67 OF;112 REVISION O 4

I l

Lr

j i

l DATE:

June 11, 1992 i

REACTOR UNIT:

CK2 DATA FEEDER:

N/A l

NRC ERDS PARAMETER:

SG LEVEL 3/C 1

POINT ID:

LO443A l

PLANT SPEC POINT DESC:

STM GEN 3 WIDE RNG L GENERIC /COND DESC:

STEAM GENERATOR 3 (OR C) WATER LEVEL ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

100.0 ZERO POINT REFFRENCE:

COMPLX REFERENCE POINT NOTES: AT 01 38.3 FT BELOW TOP OF FW INLET PIPE PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR LOCATION:

38.3 FT BELOW TOP OF FW INLET PIPE ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE M/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

Y LEVEL REFERENCE LEG WET UNIQUE SYSTEM DESC:

BLI-130 i

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM

. DATA POINT LIBRARY PAGE 68 OF 112 REVISION O a

f'

._._-._,a_,

.. r...

.__.._...._,.m..._,;.~,,_

-.., -,... ~.,,

1 l

DATE:

June 11, 1992 REACTOR UNIT:

CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

SG LEVEL 4/D i

POINT ID LO463A PLANT FPEC POINT DESC:

STM GEN 4 WIDE RNG L GENERIC /COND DESC:

STEAM GENERATOR 4 (OR D) WATER LEVEL ANALOG /DIGITALi-A 1

ENGR UNITS / DIG STATES:

ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

100.0 ZERO POINT

REFERENCE:

COMPLX REFERENCE POINT NOTES:

AT 0% 38.3 FT BELOW TOP OF FW INLET PIPE h

PROC OR SENS:

NUMBER OF SENSORS:

1 I

HOW PROCESSED:

N/A SENSOR LOCATION -

38.3 FT BELOW TOP OF FW INLET PIPE ALARM / TRIP SET POINTS:

N/A i

NI DETECTOR POWER SUPPLY l

CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY I

TURN-ON POWER LEVEL:

N/A

[

INSTRUMENT FAILURE MODE N/A j:

TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

Y l

I LEVEL REFERENCE LEG WET UNIQUE SYSTEM DESC BLI-140

-9 l

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM l

DATA POINT LIBRARY PAGE 59 OF 112 REVISION 0-m*.

+

,+9.-.---,-yv,w yg

-- -h-y

,-,p.-ry, 7U-y

,,,a en wm wn e

g

.my n - g.- yv W

o =www w w--ry-e r y, eiiw'y-n yg,w,-+pe

'e

- - vr y we-yv y

Y-P v'w v w s-iwmv y r w w*

v

DATE:

June 11, 1992 REACTOR UNIT CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

SG PRESS 1/A POINT ID:

UO414 PLANT SPEC POINT DESC:

STM GEN 1 STM P 1/2/3 AVG GENERIC /COND DESC STEAM GENERATOR 1 (OR A) PRESSURE j

ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

PSIG ENGR UNITS CONVERSION: -N/A j

MINIMUM INSTR RANCEt 0.0 i'

]

MAX 1 MUM INSTR RANGE:

1200.0 i

ZERO POI.fT REFERENCEt N/A

-l REFERENCE POINT NOTES: N/A l

PROC OR SENSt P

l NUMBER OF SENSORS:

3 l

MOW PROCESSED:

AVERAGE 1'

SENSOR LOCATION:

OUTLET FROM SGI TO TURBINE t

l ALARM / TRIP SET POINTS:

600.0 LOW i

NI DETECTOR POWER SUPPLY

,j' CUT-OFF POWER LEVEL:

N/A i

i NI DETECTOR' POWER SUPPLY.

l TURN-ON POWER LEVEL:

N/A 4

l INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A 4

i LEVEL REFERENCE LEG N/A l

UNIQUE SYSTEM DESC MPP-210, HPP-211, MPP-212 l

!=

I COOK NUCLEAR' PLANT - EMERGENCY RESPONSE DATA SYSTEM i

DATA POINT LIBRARY PAGE-70 OF'112 l

REVISION O i

t 1.....-,...,.-..,.,--

.-..~..... _

DATE:

June 11, 1992 REACTOR UNIT:

CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

SG PRESS 2/B POINT ID:

UO434 PLANT SPEC POINT DESC:

STM GEN 2 STM P 1/2/3 AVG GENERIC /COND DESC:

STEAM GENERATOR 2 (OR B) PRESSURE ANALOG / DIGITAL:

A ENGR UNITS /DIC STATES:

PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 j

i MAXIMUh INSTR RANGE:

1200.0 EERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS:

P NUMBER OF SENSORS:

3 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

OUTLET FROM SG2 TO TURBINE ALARM / TRIP SET POINTS:

600.0 LOW NI DETECTOR. POWER SUPPLY CUT-OFF POWER LEVEL:

N/A i

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A e

l l

INSTRUMENT FAILURE MODE N/A f

TEMPERATURE COMPENSATION

{

FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC:

MPP-220, MPP-221, MPP-222 n

i 4

k

)

l COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM-DATA' POINT LIBRARY PAGE-71 OF-112

{L REVISION O o

-#.~,,

,_.~,,,.-.,,m..

... # M

.m

~,..,,.oa..,.

I i

DATE:

June 11, 1992 PEACTOR UNIT:

CK2 DATA FEEDER:

N/A

~!

NRC ERDS PARAMETER:

SG PRESS 3/C POINT ID UO454 PLANT SPEC POINT DESC:

STM GEN 3 STM P 1/2/3 AVG GENERIC /COND DESC:

STEAM GENERATOR 3 (OR C) PRESSURE ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

PSIG r

ENGR UNITS CONVERSION:

N/A L

MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

1200.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

P i

i NUMDER OF SENSORS:

3 l

i HOW PROCESSED:

AVERAGE i

SENSOR LOCATION:

OUTLET FROM SO3 TO TURBINE' 1

ALARM / TRIP SET POINTS:

600.0 LOW t

{

NI DETECTOR POWER SUPPLY f

CUT-OFF POWER LEVEL:

N/A i

i NI DETECTOR POWER SUPPLY j

TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A i

TEMPEN.TURE COMPENSATION FOR DP TRANSMITTER:

N/A j

LEVEL REFERENCE LEG N/A l

UNIQUE SYSTEM DESC:

HPP-230, MPP-231, MPP-232 i.

i l

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM l'

DATA POINT LIBRARY' PAGE 72 OF 112 l

REVISION O i

gt m,.

...~ ~ - _ -

.~

...~.-- -. -

i i

1 i

I l

DATE:

June 11, 1992 1

REACTOR UNIT:

CK2 1

j DATA FEEDER:

N/A 1

j NRC ERDS PARAMETER:

SG PRESS 4/D j

POINT ID' U0474 PLANT SPEC POINT DESC:

STM GEN 4 STM P I/2/3 AVG f

i

)

GENERIC /COND DESC STEAM GENERATOR 4 (OR D) PRESSURE l

ANALOG / DIGITAL:

A 1

j ENGR UNITS /DIO STATES:

PSIG j

ENGR UNITS CONVERSION: N/A i

MINIMUM INSTR RANGE:

0.0 a

}

MAXIMUM. INSTR RANOE:

1200.0 s.

f ZERO POINT

REFERENCE:

N/A REFERENCE POINT NcaES: N/A 1

l PROC OR SENS:

P i

i NUMBER OF SENSOnSt 3

4 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

OUTLET TO SQ4 TO TURDINE ALARM / TRIP SET POINTS:

600.0 LOW i

NI DETECTOR POWER SUPPLY-CUT-OFF POWER LEVEL:

N/A i

-NI DETECTOR POWER SUPPLY j

TURN-ON POWER LEVEL:

N/A 1

l INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION

~

FOR DP TRANSMITTER:

N/A l-LEVEL REFERENCE LEG N/A 4j' UNIQUE SYSTEM DESC:

MPP-240, MPP-241, MPP-242 i

i i

{l

~

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY-PAGE 73 OF,112 REVISION O 1

5

,.._.;.2__:_._..

.,,-,e.,,_,,.,-.,..

.w...,__._....,_._._..~

J.,,.,_,.

DATE:

June 11, 1992 REACTOR UNIT CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

MN FD FL 1/A POINT ID:

U0411 PLANT SPEC POINT DESC SG 1 FW IN CORR AVG CALC 1 MIN F GENERIC /COND DESC:

STM GEN 1 (OR A) MAIN FEEDWATER FLOW ANALOG / DIGI"AL:

-A-ENGR UNITS / DIG STATES:

MLB/HR ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.000 MAXIMUM INSTR RANGE:

4.000 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

P NUMBER OF SENSORS:

2 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

INLET LINE TO SG1 ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER. LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSHITTER:

N/A LEVEL REFERENCE LEGt N/A UNIQUE SYSTEM DESC FFC-210, FFC-211 COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA' SYSTEM DATA POINT-LIBRARY PAGE 74 OF: 112 REVISION O i

I DATE:

June 11, 1992 REACTOR UNIT CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

MN FD FL 2/B POINT ID:

U0431 PLANT SPEC POINT DESC:

SG 2 FW IN CORR AVG CALC 1 MIN F GENERIC /COND DESC STM GEN 2 (OR B) MAIN FEEDWATER FLOW ANALOG / DIGITAL:

A h

ENGR UNITS / DIG STATES:

MLD/MR ENGR UNITS CONVERSION:

N/A HINIMUM INSTR RANGE:

0.000 MAXIMUM INSTR RANGE:

4.000 ZERO POINT

REFERENCE:

N/A

~

REFERENCE POINT NOTES:

N/A PROC OR SENS:

P NUMBER OF SENSORS:

2 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

INLET LINE TO SG2 ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A ill DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A T*.MPERATURE COMPENSATION FOR DP TRANSMITTER:

Y LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC:

FFC-220, FFC-221 COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY-Pl.GE 75 OF 112 REVISION O

DATE:

June 11, 1992 REACTOR UNIT:

CK2 l

DATA FEEDER:

N/A j

NRC ERDS PARAMETER:

MN FD FL 3/C POINT ID:

UO451 1

i PLANT SPEC POINT DESC:

SG 3 FW IN CORR AVG CALC 1 HIN F 4

f GENERIC /COND DESC:

STM GEN 3 (OR c) MAIN FUEDWATER FLOW ANALOG / DIGITAL:

A f.

ENGR UNITS /DV, STATES: MLD/HR j

ENGR UNITS CONVERSION: N/A MINIMUM INSTh RANGEi 0.000 MAXIMUM INSTR RANGE:

.4.000 ZERO POINT REFERENCES.

N/A j

j REFERENCE POINT NOTES:

N/A PROC OR SENS:

P I

NUMBER OF SENSORS:

2 1

{

HOW PROCESSED:

AVERAGE t

SENSOR LOCATION:

INLET _LINE TO SG3

)

ALARM / TRIP SET POINTS:

N/A i

j NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY j

TURN-ON POWER LEVEL:

_N/A INSTRUMENT FAILURE MODE:N/A 1

i j

TEMPERATURE COMPENSATION j

FOR DP TRANSMITTER:

Y 4

j LEVEL REFERENCE LEG N/A t

)

UNIQUE SYSTEM DESC -

FFC-230,-FFC-231 i

i 1

?

J 3

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 76 OF 112-l REVISION 0 i

l a

i

-.--,-,.--x,

.,, +

.c,..u,-

-.., -..., ~., - -.,.

4 h4 4 he was. 4 e6AAW5A.s.-.W4AEhJ==+Eh+h4sMI+ N iJ4h--aw-M 11'---e.4Lvamh-

44-.==A46& L 48hh 4

J+ 4 hee.-.EA&s'M#Ah M.A_ & & mMad, A AhJz.4.4._h'"

l 1

i DATE:

- June 11, 1992 e

l REACTOR UNIT:

CK2 i

i DATA FEEDER:

N/A NRC ERDS PARAMETER:

HN FD FL 4/D POINT ID:

UO471 4

j PLANT SPEC POINT DESC:

SG 4 FW IN CORR AVG CALC I MIN F 1

GENERIt. : )ND DESC:

STM GEN 4 (OR D) MAIN FEEDWATER FLOW i

j ANALOG / DIGITAL:

A-ENGR UNITS / DIG STATES: MLD/HR 4

ENGR UNITS CONVERSION: N/A i

i MINIMUM INSIR RANGE:

0.000 I

l MAXIMUM INSTR RANGE:

4.000 1

1 i-ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A I

PROC CR SENS:

P i

4j.

NUMBER OF SENSORS:

2 1

{

HOW PROCESSED:

AVERAGE l

SENSOR LOCATION:

INLET LINE TO SG4 l

ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY j

CUT-OFF POWER LEVEL:

N/A l

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILUF2 MODE N/A

}

TEMPERATURE COMPENSATION j

FOR D

TRANSMITTER:

Y t

j LEVEL REFERENCE LEG N/A i

d i

i UNIQUE SYSTEM DESC FFC-240, FFC-241

)

i

\\

a COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY

'PAGE 77 OF 112 F2 VISION O-4 4

I t

... ---,.~. --. -, ~,.,_. -,

...., -.., ~..em..

r,.,. -,, -,.,.-

.~.v..,,

.m.-.n.-r-y,,E,

m 8

DATE:

June 11, 1992 4

j REACTOR UNIT:

CK2 l

i l

l DATA FEEDER:

N/A l

NRC ERDS PARAMETER:

AX FD FL 1/A i

8 POINT ID:

SP009A PLAN' SPEC POINT DESC: AUX FEED FLOW LP1 i

GENERIC /COND DESC:

STM GEN 1 (OR A) AUXILIARY FW FLOW j

ANALOG / DIGITAL:

A t

l ENGR UNITS / DIG STATES:

KLB/HR t

ENGR UNITS CONVERSION: N/A l

MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGES-250.0 1

ZERO POINT

REFERENCE:

N/A L

l REFERENCE POINT NOTES: N/A i

i PROC OR SENS:

S 1

f NUMBER OF SENSORS: !

HOW PROCESSED:

NA j

SENSOR LOCATION:

INLET LINE TO S01 t

ALARM / TRIP SET POINTS: N/A 1

NI DETECTOR POWER SUPPLY l

CUT-OFF POWER LEVEL -

N/A.

i NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A f

j INSTRUMENT FAILURE MODE N/A l-TEMPERATURE COMPENSATION 1

FOR DP TRANSMITTER:

N f

LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC:

FFI-210-2 a

1i l

COOK NUCLEAR PLANT.- EMERGENCY RESPONSE DATA' SYSTEM i

F DATA POINT LIBRARY PAGE 78 OF 112 REVISION 0-l 4

ni i

,..+

,re.---+..

...ww-,~,,.,--,---.--

tw r

-mou--,,.-..

.-,-,m-,

-wmy,.-

u r v.,~.-*wm,,7.--,.

y-_,,-e-,,_

DATE:

June II, 1992 REACTOR UNIT:

CK2 DATA FEEDER:

N/A NRC ER00 PARAMETER:

AX FD FL 2/B POINT ID:

SP060A PLANT SPEC POINT DESC: AUX FEED FLOW LP2 GENERIC /COND DESC STM GEN 2 (OR B) AUXILIARY FW FLOW AhALOG/ DIGITAL:

A ENGR-UNITS / DIG STATES:

KLB/HR ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 I

MAXIMUM INSTR RANGE:

250.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 IlOW PROCESSED:

N/A SENSOR usCATIONs.

INLET LINE TO SG2 ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC:

FFI-220-.

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY

- PAGE 79.0F 112 REVISION'O L

e.-94 y

y-99 9-u+w1egq+q---pwg.--

--g-

y-3 w,-w,

.m,m mQ-y..

p,.4e.--

w

-wy-m

,,w,---,m.._.,_,,,-----y

~.---... - -. - __.-.~ -.-. - ~ ~ -

1 i

i

)

DATE:

June 11, 1902 REACTOR UNIT:

CK2 i

i DATA FEEDER:

N/A NRU ERDS PARAMETER:

AX FD FL 3/C POINT ID:

SP061A PLANT SPEC POINT DESC:

AUX FEED FLOW LP3 i

i GENERIC /COND DESC:

STM GEN 3 (OR C) AUXILIARY FW FLOW j

j ANALOG / DIGITAL:

A 3

i' i

ENGR UNITS /DIO STATES:

KLB/HR l

ENGR UNITS. CONVERSION: -N/A j

MINIMUM INSTR RANGE: ~

0.0 l-MAXIMUM INSTR RANGE:

250.0 l-ZERO POINT

REFERENCE:

N/A j

REFERENCE POINT NOTES:

N/A i

i PROC OR SENS:

S NUMBER OF SENSORS:

I HOW PROCESSED:

N/A l

SENSOR LOCATION:

INLET.LINE TO SG3 1

ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY j

CUT-OFF POWER LEVEL:

N/A i

l NI DETECTOR POWER SUPPLY t

TURN-ON POWER LEVEL:

N/A j

INSTRUMENT FAILURE MODE:N/A TEMPERATURE COMPENSATION r

- FOR DP TRANSMITTER:

N LEVEL REFERENCE LEG -

. N/A-UNIQUE SYSTEM DESC-FFI-230 i,

i

. COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA-SYSTEM DATA POINT LIBRARY

- PAGE 80 OF 112-REVISION O i

,----3-yi-r g--

f--,=

c.--[r r -e we

.,.e.,m-.,-,-,

,.y'

,r nw

-,w, w--e.,

w-3 me

..,,y.g r

4 e+#

  • mme--we*

de twe ' FT e - ""t = h r

-N*

'*""f

"*'"T'W"

~.

- ~. - -. - -. _... -.. -. - -. -. - _.. - - ~. -. -

_ - ~. - -

4!

I j

DATE:

June 11, 1992 i

j PEACTOR UNIT:

CK2 i

DATA FEEDER:

N/A 1

]

NRC ERDS PARAMETER:

AX FD FL 4/D i

POINT ID:

SP010A j

PLANT SPEC POINT DESC: AUX FEED FLOW LP4 GENERIC /COND DESC:

STM GEN 4 (OR D) AUXILIARY FW FLOW 9

}

ANALOG / DIGI'AL A

ENGR UNITS / DIG STATES) KLB/HR ENGR UNITS CONVERSION: N/A j

MINIMUM. INSTR RANGE:

0.0 j

MAXIMUM INSTR RANGE:

250.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS:

S t

NUMBER OF SENSORS:

I 1

l HOW PROCESSED:

N/A l

SENSOR LOCATION:

INLET LINE TO SG4 ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY j

CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY j

TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A i

4 TEMPERATURE COMPENSATION f

FOR DP TRANSMITTER:

N t

LEVEL REFERENCE LEG N/A

}

UNIQUE SYSTEM DESC:

FFI-240 i

t I

4 4

i 2

COOK NUCLEAR PLANT ~ EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 81 OF 112 REVISION O l

L t.

g-

,,-n.w,,

- -+

..g,

-..w,.,,-.,

,,,__.,,_..,,,-._a,,

,,,.w, n,

-. ww,,,.,

n,,=

i DATE:

June 11, 1992 REACTOR UNIT CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

HL TEMP 1/A POINT ID:

T0419A PLL T SPEC POINT DESC RCL1 HOT TEMPERATURE GENERIC /COND DESC:

STM GEN 1 (OR A) INLET TEMPERATURE ANALOG / DIGITAL:

A ENGR UNITS /DIO STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A i

PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR LOCATION:

LOOP 1 HOT LEG INLET OF SG1 ALARM / TRIP SET F01NTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWEM LEVEL:

- N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP 'J ANSMITTER:

N/A f

LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC:

NTR-110 COOK NUCLEAR-PLANT EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 82 OF 112 REVISION O t'

v-n

-[ w r-r w e w &w m t.rv w 's a ww n~~-

r-*

t--.r~,w<

+

te,--c--m--r

- - + +

s w *rew-

  • - - -. =,,s -v y,

w. -m ov y-w-+,e e-

,.we-

+r-w o-rw.4e

,eew

--w---.

-.- ~. -.- --.

- ~

.. -.. - - --.. -.. _ -. ~.. -

-... -.. - ~ ~ -., - ~. - - -. ~..

2 i.

l 1

4 1

i

+.

4 DATE:

June 11,-1992

.t REACTOR UNIT:

CK2 DATA FEEDER:

N/A NRC.ERDS PARAMETER:

HL TEMP 2/B l

i POINT ID -

T0439A-PLANT SPEC POINT DESC1 RCL2 HOT TEMPERATURE

{

GENERIC /COND DESC:

STM GEN 2 (OR B) INLET TEMPERATURE i

ANALOG / DIGITAL:

A j

ENGR UNITS / DIG STATES _ DEGF ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 i

MAXIMUM INSTR RANGE:

700.0-

~

- ZERO 204NT RF~TRENCE:

N/A l

REFERENCE POINT NOTES: N/A 1.

PROC OR SENS:

S

{

NUMBER OF SENSORS:

. 1 HOW PROCESSED:

N/A 4

SENSOR LOCATION:

LOOP 2 HOT LEG INLET To SG2 t

{

ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A

)

NI DETECTOR POWER SUPPLY-5 TURN-ON POWER LEVEL:

N/A 1

INSTRUMENT FAILURE MODE N/A 1

-- TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL HEFERENCE LEGt N/A i

j --

UNIQUE SYSTEM DESC:

N*7- ? ? n '

h

? -':

i

- COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 83 OF 112 REVISION O J

5 4

i-

-an,'.m'.-

-.e,.-~~

. +. +

DATE:

June 11,-1992 REACTOR UNIT:

CK2 DATA FEEDER:

N/A

'NRC ERDS PARAMETER:

HI 'EMP 3/C POINT ID:

T0459A PLANT SPEC POINT DESC RCL3 HOT TEMPERATURE GENERIC /COND DESC:

STM GEN 3 (OR C) INLET TEMPERATURE ANALOG / DIGITAL:

A ENGR UNI'.~S/ DIG STATES:

DEGF ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

E NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR LOCATION:

LOOP 3 HOT LEG INLET TO SG3 ALARM / TRIP SET POINTS:

N/A NI "ETECTOR POWER SUPPLY C'

" 5' POWER LEVEL:

N/A l

"OR POWER SUPPLY iT % 'OWER L""EL:

N/A

K 4T FAILC.sE MODE:N/A ifh+d?A?JRE COMPENSATION FOa 1RANSMITTER:

N/A LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC NTR-130 ii COOK NUCLEAR PLANT - EMERGENCY RESPONSE. DATA SYSTEM DATA POINT LIBRARY

-PAGE 84-OF 112 r

REVISION-0 1

.J I

Ji l

l

_ _ _. ______3

.-~ ~.

-., - =...

--..._ _. -.~..-_.

-, ~. -. - -. ~. -._.- -.

6 1

i l

DATE:

June 11, 1992 j.'

REACTOR UNIT:

CK2

. 1 l.

DATA FEEDER '

N/A NRC ERDS PARAMETER:

HL TEMP 4/D i

POINT ID:

T0479A i

j PLANT SPEC POINT DESC: RCL4 HOT TEMPERATURE GENERIC /COND DESC

- STM GEN 4 (OR'D) INLET TEMPERATURE l

ANALOG / DIGITAL:

A ENGR UNITS / DIG STETES:

DEGF i

. ENGR UNITS CONVERSIONS. N/A MINIMUM INSTR f.ANGE:

0,0 i

i MAXIMUM INSTR RANGE:

700.0 1

1 i

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A I

PROC OR SENS:

S NUMBER OF SENSORS:

1 4

j HOW PROCESSED:

N/A SENSOR LOCATION:

LOOP 4 HOT LEG INLET TO SG4 i

ALARM / TRIP SET POINTS: N/A l

NI DETECTOR.' POWER SUPPLY j

CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY

+

[

TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION

.FOR DP TRANSMITTER:

N/A sl' LEVEL REFERENCE LEG N/A

).

UNIQUE SYSTEM DESC:

NTR-140 4

d l

COOK NUCLEAR PLANT - EMERGENCY RESPONSE' DATA SYSTEM 4

DATA POINT LIBRARY PAGE 85 OF 112 REVISION O 4

^

r ww t w mewr w' van -w *

-- e r 1 5 v

+'-*Tr*-'rT-m- e

  • w-r -

79

- o'w* e t w -w

+ww---

vv 1"'

ewev

't"*'e i--

t-w w

"+-'s-1 w

e-v v

ww w-se v re

.~..,..

t i

).

DATE:

June 11, 1992 REACTOR UNIT:

CK2 4

{.'

DATA FEEDER:

N/A

?~

NRC ERDS PARAMETER:

CL TEMP 1/A l

POINT ID:

T0406A f

PLANT SPEC POINT DESC:

RCL1 COLD TEMPERATUPE GENERIC /COND DESC:

STM GEN 1 (OR A) OUTLET TEMPERATURE i

ANALOC/ DIGITAL:

A ENGR UNITS / DIG STATES: DEGF ENGR UNITS CONVERSION: N/A j

MINIMUM INSTR RANGE:

0.0 s

MAXIMUM INSTR RANGES.

700,0 ZERO POINT REFERENCES-N/A 4

l

_ REFERENCE' POINT NOTES: N/A PROC OR SENS:

S j

NUMBER OF SENSORS:

1 l-HOW PROCESSED:

N/A E

SENSOR LOCATION:

LOOP 1 COLD LEG INLET TO REACTOR.

4 l

ALARM / TRIP SET POINTS: N/A NI DETECTOR POWEd SUPPLY 1-CUT-OFF POWER LEVEL:

N/A 1

l!

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A I

}

TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG N/A j.-

UNIQUE SYSTEM DESC -

-NTR-210 i

s i

!~

4 COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM i

DATA POINT LIBRARY PAGE 86 OF-112

+

REVISION O i

1 l

li e

W 4

v.

c.-..

.e,

+...

r

  1. y-a p.-...,

,., _. +.,.,, -.

e.,,,.

,,r,e, p

,e

..,w..~,s

,h-m --

. E E-,-

,4,

.. -~

DATE:

June 11, 1992 i

REACTOR UNIT:

CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

CL TEMP 2/B POINT IDt T0426A PLANT-SPEC POINT DESC:

RCL2 COLD TEMPERATURE c

GENERIC /COND DESC STM GEN 2 (OR B) OUTLET TEMPERATURE ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

DEGF ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCOSSED:

NA SENSOR LOCATION '

LOOP 2 COLD LEG' INLET TO REACTOR ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEV 3La N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LFG:

N/A UNIQUE SYSTEM DESC -

NTR-220 COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 87 OF 112~

REVISION O f --

R I

k s

..-.u...

--.~,;

..-_~,;,-,,-a.~_.

j DATE:

- June 11, 1992

- REACTOA UNIT:

CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

CL TEMP 3/C

?

POINT ID:

T0446A PLANT SPEC POINT DESC:

RCL3 COLD TEMPERATURE I.

GENERIC /COND DESC:

STM GEN 3 (OR C) OUTLET TEMPERATURE ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

DEGF 4

i j

ENGR UNITS CONVERSION:

N/A 4

i MINIMUM INSTR RANGE '

O.0 j

MAXIMUM INSTR RANGE:

700.0 f

ZERO POINT

REFERENCE:

N/A t

REFERENCE POINT NOTES:

N/A

?> ROC OR SENS:

S NU"BER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR LOCATION:

LOOP 3 COLD LEG INLET TO REACTOR j --

ALARM / TRIP SET POINTS:- N/A l-.

NI DETECTOR POWER SUPFLY f

CUT-OFF POWER LEVEL:

N/A i

NI DETEOTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A i-INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG N/A j.

UNIQUE SYSTEM DESC:

NTR-230 4

l-COOK NU2 LEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM l

DATA POINT LIBRARY PAGE 88 OF 112 REVISION O

!~

I f

-m-

--e,e y

,,mi

,E,-,

.3--

,w+,

37--

,-.-ver, 9-ere --

5 e-u---9

- -.. --. -...... =

...- - ~_-

- ~..

- ~. _. _. ~. -

i -

1 i

DATES.

June.11,.1992 4

i REACTOR UNIT CK2 I

i, DATA FEEDER:

N/A CL TEMP 4/D NRC ERDS PARAMETER POINT ID:

T0466A i

j PLANT SPEC POINT DESCt RCL4 COLD TEMPERATURE

+

GENERIC /COND DESC:

STM GEN 4-(OR D) OUTLET TEMPERATURE ANALOG / DIGITAL:

A j

ENGR UNITS / DIG STATES: DEGF t

i ENGR UNITS CONVERSION: N/A i

}

MINIMUM INSTR RANGE:

J.0

{

MAXIMUM INSTR RANGE:

700.0 j

ZERO POINT

REFERENCE:

N/A f

REFERENCE-POINT NOTES: N/A PROC OR SENS:

S i

NUMBER OF SENSORS:

1 1

HOW PROCESSED:

N/A SENSOR LOCATION:

LOOP 4 COLD LEG INLET TO REACTOR ALARM / TRIP SET POINTS: N/A 4

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A l-NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A l

TEMPERATURE COMPENSATION 2

FOR DP TRANSMITTER:

N/A 5

LEVEL REFERENCE LEG -

N/A UNIQUE-SYSTEM DESC:

NTR-240 t

i f

l-i 1

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM l

DATA POINT LIBRARY PAGE 89 OF 112 REVISION O l

ji

.... - ~.. ~... - ~. ~. _ _ _ ~. - - -. ~. _ --

.. - ~.. -

.- ~

1 1

4 DATE:

June 11, 1992 f

REACTOR UNIT CK2 j

DATA FEEDER:

N/A 1

NRC ERDS PARAMETER:

RCS PRESSJRE i

POINT ID:

U1313 3

PLANT SPEC POINT DESC:

RCI SYSTEM PRESSURE 4

l GENERIC /COND DESC:

TEACTOR COOLANT SYSTEM PRESSUPE

?

ANALOG / DIGITAL:

J.

ENGR UNITS / DIG STATES:

PSIG

{

ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM-INSTR' RANGE:

3000.0 t

j ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A f

f PROC OR SENS:

P l

NUMBER OF SENSORS:

2 HOW PROCESSED:

AVERAGE l

l SENSOR LOCATION:

LOOP 1 AND 2 HOT LEG INLET TO SGI AND SG2 ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY l

CUT-OFF POWER. LEVEL -

N/A 4

1 NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A g.

l INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A i'

LEVEL REFERENCE LEG '

U/A i:-

[-

UNIQUE SYSTEM DESC:

NPS-121, NPS-122 p-1 I

U 4

E P-

-COOK NUCLEAR PLANT - EMERGENCY. RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE.90 OF 112'

. REVISION O

=-

V' l-l s

': )

$I

- ~. -.. -... -.

i; i

DATE:

June 11',

1992 3-REACTOR UNIT:-

- CK2 i

DATA FEEDER:

N/A i

NRC ERDS PARAMETER:

PRZR LEVEL 3

POINT ID:

UO483 j

PLANT SPEC POINT DESC:

PRESSURIZER LEVEL 1/2/3 AVG l

j-GENERIC /COND DESC:

PRIMARY SYSTEM PRESSURIZER LEVEL 4-ANALOG / DIGITAL:

A j

I ENGR UNITS / DIG STATES:

ENGR UNITS CONVERSION: N/A t

1 4

- MINIMUM INSTR RANGE:

0.0 J

MAXIMUM-INSTR RANGE:

100.0 ZERO POINT

REFERENCE:

COMPLX i

j REFERENCE POINT NOTES:

AT 0% 36" ABOVE BOTTOM OF PRZR VESSEL A

PROC OR SENS:

P i

i NUMBER OF SENSORS:

3 i

HOW PROCESSED:

AVERAGE i

SENSOR LOCATION:

36" ABOVE BOTTOM OF PRESSURIZER VESSEL j

ALARM / TRIP SET POINTS: 92 HIGH 1

i NI-DETECTOR POWER SUPPLY I

CUT-OFF POWER' LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILUe 5: MODE:N/A TEMPERATURE COMPENSATION

{

FOR DP TRANSMITTER:

Y i.

LEVEL REFERENCE LEG WET i-UNIQUE SYSTEM DESC:

NLP-151, NLP-152, NLP-1531 i

d 0

4 COOK ~ NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 91 OF 112' REVISION O' i

a 4

--~rw v.----,

93--

y,.f-rye-tm,yy,..p

-gy-

--,syrn,

- we

n. a memem t+w w wet-rvr ' 4 h *f Fw ave t e-e w 's w -+ v-w r.a w w 7 + '-v 4.y -=--+eev-+y1 7

+w-cr*

1 e m 3--rw- -w e< =m-w eT

- - -...~

- _. ~.. -. -. -.

tj j.. -

a 1

DATE:

June 11, 1992 REACTOR UNIT:

CK2 i

DATA FEEDER:

N/A.

NRC ERDS PARAMETER:

RCS CHG/MU POINT ID:

U1613 t-PLANT SPEC POINT DESC: TOTAL CHARGING FLOW GENERIC /COND DESC:

PRIMARY SYSTEM CHARGING OR MAKEUP FLOW ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: GPM j

ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

200.0 ZERO POINT,

REFERENCE:

N/A REFERENCE POIhT NOTES:

N/A f

PROC OR SENSt.

P.

NUMBER OF SENSORS:

5 HOW PROCESSED:

SUM i

SENSOR LOCATION:

DISCHARGE HEADER.OF CHARGING PUMPS AND CotD LEG OF ALL FOUR LOOPS t

ALARM / TRIP SET POINTS:. 40.0 HIGH NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A l

NI DETECTOR-POWER SUPPLY TURN-ON POWER' LEVEL:

N/A INF")-SMFNT FAILURE. MODE:N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

.N l

LEVEL' REFERENCE LEG:

N/A l

UNIQUE ~ SYSTEM-DESC:

QFI-200, IFI-51,.IFI-52, IFI-53, IFI-54 t

l.

~

COOK-NUCLEAR PLANT - EMERGENCY RESPONSE DATA' SYSTEM DATA-POINT-. LIBRARY PAGE 92 OF 112 REVISION.,, _ _..

-_._...;......2..-....

,,,.--..-..;....-~

4

.. _ -. -. -.-,c-

~.

1 DATE:

June 11, 1992 j

REACTOR UNIT:

CK2 4

1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

HP SI FLOW l

POINT ID:

-U1603 1-

]

PLANT SPEC POINT DESC:

TOTAL SAFETY INJECTION FLOW i

GENERIC /COND DESC:

HIGH PRESSURE SAFETY INJECTION FLOW ANALOG / DIGITAL:

A

]

ENGR UNITS / DIG STATES: GPM l

ENGR UNITS CONVERSION - N/A l

l MINIMUM INSTR RANGE:

0.0 2

MAXIMUM INSTR RANGE:

1600.0 ZERO POINT REFERENCES.

N/A REFERENCE. POINT NOTES _ N/A PROC OR-SENS:

P 4

l NUMBER OF SENSORS:

2 HOW PROCESSED:

SUM SENSOR LOCATION:

SI PUMP DISCHARGE LINE 1N) COLD LEGS l'

j ALARM / TRIP SET POINTS:

N/A i

NI DETECTOR' POWER SUPPLY j

CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A i

l-TEMPERATURE COMPENSATION j

FOR DP; TRANSMITTER:

N i

LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC -

_IFI-260, IFI-266 4

i e

i f

l COOK' NUCLEAR PLANT -- EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 93 OF 112 REVISION O F

t i

_ __._ ~.-.. _.. _ -

~ _... _

i l

i-

.l DATE:

June 11, 1992 1

)

REACTOR UNIT:

CK2 ll DATA FEEDER.

N/A j-NRC ERDS PARAMETER:

LP SI FLOW POINT ID:

U1604 PLANT SPEC POINT DESC: TOTAL RHR FLOW j

GENERIC /COND DESC:

LOW PRESSURE SAFETY INJECTION FLOW ANALOG / DIGITAL:

A 1

j ENGR UNITS / DIG STATES: GPM I

ENGR UNITS CONVERSION: N/A MINIMUM. INSTR RANGE:

0.0 l

MAXIMUM INSTR rat?GE:

10000.0 1

ZERO POINT

REFERENCE:

N/A l

REFERENCE POINT NOTES:

N/A' PROC OR SENS:

P 1.

I NUMBER OF SENSORS:

4 e

i.

l HOW PROCESSED:

SELECT PROPER RANGE FOR EACH LEG, SUM LEGS I'

SENSOR LOCATION:

RHR PUMP DISCHARGE TO HOT LEGS ALARM / TRIP SET POINTS: N/A 1

i NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A 4'

NI DETECTOR POWER SUPPLY j-

. TURN-ON POWER LEVEL:

N/A t'

]

INSTRUMENT FAILURE MODE N/A i

?

TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

. N l

t LEVEL REFERENCE LEG:

N/A f._

UNIQUE SYSTEM DESC -

-IFI-310, IFI-311, IFI-320, IFI-321 i=

1 -

i d

l>

COOK NUCLEAR PLANT - EMERGENCY RESPONSE. DATA SYSTEM i

DATA POINT LIBRARY PAGE 94 OF 112 REVISION 0:

4 a

s

_,._,,__s..,

.,,_.,-,,-,,,,,.,,,..,,4,,m.

. -. ~ ~

. ~ -

l-4 DATES-June-11, 1992 REACTOR UNIT:

CK2 DATA FEEDER:

N/A

,l-NRC-ERDS PARAMETER:

CTMNT'SMP NR 1

POINT ID:

U1605 1

PLANT SPEC POINT DESC: AVG CNTMT SUMP NR' LEVEL j

CENEPIC/COND DESC:

CONTAINMENT SUMP NARROW' RANGE LEVEL 4

ANALOG / DIGITAL:

A l

ENGR UNITS / DIG STATES: %

ENGR UNITS CONVERSION:

0=589'-5"

-100=599'-8" MINIMUM INSTR RANGE:

0.0

~

j' MAXIMUM INSTR-RANGE:

100.0 ZERO POINT

REFERENCE:

COMPLX j

REFERENCE POINT NOTES: AT 0% 5 INCHES ABOVE BOTTOM OF SUMP I

PROC OR SENS:

P

{_

NUMBER OF SENSORS:

2 i

HOW PROCESSED:

AVERAGE f

SENSOR' LOCATION:

LOWER CNTMT SUMP ALARM / TRIP SET POINTSt. 83.75 HI 8.95 LOW.

i NI DETECTOR POWER SUPPLY

{

CUT-OFF POWER. LEVEL:

N/A l

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A i

INSTRUMENT FAILURE MODE N/A c

I' TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

-Y-LEVEL REFERENCE LEG N/A l-UNIQUE SYSTEM DESC -

NLA-310, NLI-311

[-

f

~

. COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM l

DATA POINT LIBRARY PAGE 95 OF 112 l-REVISION O l

i l

f f

. ~..

s.-

.. =.. -.. _,

..s

DATE:

June 11, 1992 REACTOR UNIT:

CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:'

CTMNT SMP WR POINT ID:

U1606 PLANT SPEC POINT DESC:

AVG CTMNT SUMP WR LEVEL GENERIC /COND DESC:

CONTAINMENT SUMP WIDE RANGE LEVEL ANALOG /TIGITAL:

A ENGR UNITS / DIG STATES:

ENGR UNITS CONVERSION:

0=599'-3" 100=614' MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGES-100.0 ZERO POINT

REFERENCE:

COMPLX REFERENCE POINT NOTES:

0% AT ELEV. 599'-3" PROC OR SENS:

P NUMBER OF SENSORS:

2 HOW PROCESSED:

AVERAGE

' SENSOR LOCATION:

LOWER CNTMT SUMP ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY

-TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A' TEMPERATURE COMPdNSATION FOR DP TRANSMITTER:

Y LEVEL REFERENCE LFW N/A UNIQUE. SYSTEM DESC:

NLI-320, NLI-321 i

S COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM i

DATA POINT. LIBRARY PAGE 96 OF 112

)

REVISION 0:

- - -.. -.. ~

... -. ~.

-. - ~ -

_ _ _. ~.

i 4

4 h

DATE:

June 11, 1992 e

i REACTOR UNIT:

CK2 DATA' FEEDER:

N/A f

NRC ERDS PARAMETER:

EFF GAS RAD i -

POINT ID:

U1614 i

PLANT SPEC POINT DESC: UNIT VENT EFFLUENT MONITOR 1

GENERIC /COND DESC:

RADIOACTIVITY OF RELEASED GASES-5 ANALOG / DIGITAL:

A 1

ENGR UNITS / DIG STATES: pCI/HR i

4 ENGR UNITS CONVERSION:

N/A I

MINIMUM INSTR RANGE:

0.0

{

MAXIMUM INSTR RANGE:

3,OE+16 ZERO POINT

REFERENCE:

N/A l

REFERENCE POINT NOTES:

N/A 4

i PROC OR SENS:

P NUMBER.OF SENSORS:

4 i-HOW PROCESSED:

SELECTION, MULTIPLICATION SENSOR LOCATION:

AUX BLDG VENT STACK-i ALARM / TRIP SET POINTS - N/A I

j.

NI DETECTOR POWER SUPPLY j.

CUT-OFF POWER LEVEL:

N/A i

NI DETECTOR POWER SUPPLY-

- TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A' j

TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A 4

1 j

LEVEL REFERENCE LEG N/A 4

i UNIQUE SYSTEM DESC:

VRS-2505, VRS-2507, VRS-2509, VRS-2510 SELECTION OF

-LOW, MEDIUM, AND HIGH UNIT VENT INSTRUMENTS. BASED ON

-EFFLUENT CONCENTRATION TIMES THE MEASURED FLOW RATE-IN-

[

UNITS OF pCI/HR

~

0 i

i j

COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM j

DATA POINT LIBRARY PAGE 97 OF 112 REVISION 0~

-, ~.

,....,-a.~,.m

--.._m..._.-

..~._ _

I i

1.

DATE:

June 31, 1992 REACTOR UNIT:

CK2 I-DATA FEEDER:

N/A i'

l NRC ERDS PARAMETER:

EFF LIQ RAD 4

i POINT ID:

RMS001 PLANT SPEC POINT DESC: WASTE DISPOSAL SYSTEM EFFLUENT MONITOR i

j GENERIC /COND DESC:

RADIOACTIVITY OF RELEASED LIQUIDS 4

ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES : CPM ENGR UNITS CONVERSION: 'N/A 4

MINIMUM INSTR RANGE:

5.0 MAXIMUM. INSTR-RANGE:

5.0E+05 1

j ZERO POINT

REFERENCE:

'N/A

{

REFERENCF POINT NOTES:

N/A i

i PROC OR SENS:

S' l

NUMBER OF SENSORS:

1 4

HOW PROCESSED:

N/A i

SENSOR LOCATION:

LIQUID WASTE DISPOSAL SYSTEM DISCHARGE' ALARM / TRIP SET POINTS = N/A I

NI DETECTOR POWER SUPPLY' CUT-OFF POWER LEVEL -

N/A 1

1 NI-DETECTOR POWER SUPPLY

^

!=

TURN-ON POWER LEVEL:

N/A i

2 INSTRUMENT FAILURE MODE N/A i

i TEMPERATURE COMPENSATION-FOR - DP TRAN".MITTER:

N/A 5

LEVEL REFERENCE LEG:

N/A i

UNIQUE SYSTEM DESC -

RRS-1001=

k.

I i

l COOK NUCLEAR PLANT - EMERGENCY RESPONSE-DATA SYSTEM.

DATA POINT LIBRARY.

PAGE 98 OF 112 j

REVISION.O i.

k a

4'

.,.m.

,r,

=

_ =

i

$ i-1-

DATE:

June.11, 1992.

1 REACTOR UNIT:

CK2

. DATA FEEDER:

N/A NRC ERDS PARAMETER:

COND A/E RAD-5 1

A POINT ID:

U1615 t

k PLANT SPEC POINT DESC:

SJAE EFFLUENT MONITOR

~

I GENERIC /COND DESC:

CONDENSER AIR EJECTOR RADIOACTIVITY ANALOG /DIGITALt.

A 1

j ENGR UNITS / DIG STATES: pCI/HR ENGR UNITS CONVERSION: N/A I

j MINIMUM INSTR RANGE:

0.0 t

MAXIMUM INSTR RANGE:

3.0E+16 ZERO POINT

REFERENCE:

N/A 1

l REFERENCE POINT NOTES:. N/A PROC OR SENS:

P i-1 NUMBER OF SENSORS:

4 I

HOW PROCESSED:

SELECTION,-MULTIPLICATION SENSOR LOCATION:

CONDENSER STEAM JET AIR EJECTOR DISCHARGE VENT ALARM / TRIP SET POINTS: N/A i

NI DETECTOR POWER SUPPLY CUT-OFF-POWER LEVEL:

N/A i

NI DETECTOR POWER SUPPLY

?

TURN-ON POWER LEVEL:

N/A l1 INSTRUMENT FAILURE MODE N/A

{

TEMPERATURE COMPENSATION j

FOR DP TRANSMITTER:

N/A I

LEVEL REFERENCE-LEG N/A

{

UNIQUE SYSTEM DESC:

SRA-2905, SRA-2907, SRA-2909,- SRA-2910 - SELECTI'ON OF l

LOW, MEDIUM, AND HIGH SJAE-MONITORS BASED ON EFFLUENT i

CONCENTRATION TIMES THE MEASURED FLOW RATE'IN UNITS OF-pCI/HR-i i:

COOK NUCLEAR PLA'NT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 99 OF 112 REVISION O' I

b i-

.--c

+

- ~

z...,

,n.--

+ -

DATE:

June 11, 1992 REACTOR UNIT:

CK2

. DATA FEEDER:

N/A NRC ERDS PARAMETER:

CTMNT RAD POINT ID:

RMS064 PLANT SPEC POINT DESC:

HI RANGE CTMNT AREA MONITOR GENERIC /COND DESC:

RADIATION LEVEL IN THE CONTAINMENT ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:- R/HR ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

1.OE+00 MAXIMUM INSTR RAMGE:

1.OE+07 ZERO POINT

REFERENCE:

N/A.

REFERENCE POINT NOTES:

N/A PROC-OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR LOCATION:

INSIDE CONTAINMENT ALARM / TRIP SET POINTS:

1.OE+01 NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG -

N/A UNIQUE SYSTEM DESC:

-ERS-2410 COOK NUCLEAR PLANT -EMERGENCY RESPONSE DATA SYdTEM-DATA ~ POINT LIBRARY-PAGE 100-OF-112-REVISION ~0 q

i

--n

. - - -. - ~

.. -. ~

....... - - -.. ~. -. - - -.. -... -,. -.. -

M j

)

3

.)

DATES-

. June.11, 1992 REACTOR UNIT:

CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

SG BD RAD 1A l

POINT ID:

R0024A 1

i PLANT SPEC POINT DESC:

SG BLONDOWN TREATMENT MONITOR GENERIC /COND DESC:

STM GEN 1 BLOWDOWN RAD LEVEL ANALOG /DIGTTAL:

A l

ENGR UNITt

.G STATES:

CPM i

. N/A i

ENGR UNITS CONVERSION:

~

MINIMUM INSTR RANGE:

10.0 MAXIMUM INSTR RANGE:

1000000.0 i.

^

ZERO POINT

REFERENCE:

N/A 1

{

REFERENCE POINT NOTES:

N/A 1.

l PROC OR SENS:

S t

l NUMBER OF SENSORS:

1

[

HOW PROCESSED:

N/A SENSOR LOCATION:

OUTLET OF THE STEAM GENERATOR BLOWDOWN HEADER ALARM / TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A l-NI DETECTOR POWER SUPPLY

{

TURN-ON. POWER LEVEL:

.N/A.

' INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION j.

FOR DP TRANSMITTER:

N/A-

-LEVEL REFERENCE LEG :

N/A i

UNIQUE SYSTEM DESC:

DRA-353 COMMON FOR SG-1,2,3,4 e

!i l

i

-COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM' DATA POINT LIBRAR'i-PAGE 101 OF-112 REVISION O

-~

~

---.---e

DATE:

June 11,-1992 REACTOR UNIT:

CK2 DATA FEEDER:

N/A NRC ERDS PARAMETER:

SG BD RAD 2B POINT ID:

R0024A PLANT SPEC POINT DESC:

SG BLOWDOWN TREATMENT MONITOR GENERIC /COND DESC:

STM GEN 2 BLOWDOWN RAD LEVEL ANALOG / DIGITAL A

ENGR UNITS / DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

10.0 MAXIMUM INSTR RANGE:

1000000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS:

S NUMBER O'? SENSORS:

1 HOW PROCESSED:.

N/A SENSOR LOCATION:

OUTLET OF THE STEAM GENERATOR BLOWDOWN HEADER ALARM / TRIP SET POINTS: N/A NI-DETECTOR POWER SUPPLY CUT-OFF' POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION

.FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG:

N/A-UNIQUE SYSTEM DESC:

DRA-353 COMMON FOR SG-1,2,3,4 COOK NUCLEAR PLANT --EMERGENCY RESPONSE DATA-SYSTEM.

DATA-POINT LIBRARY PAGE.102 OF 112 REVISION O 3

. -..... ~. - -.~.

- + _. _-- -

a r

j -.

a h

DATE:

_ June 11, 1992 4

REACTOR UNIT:

CK2 DATA FEEDER:

N/A

-t NRC ERDS PARAMETER: _

SG BD RAD 3C POINT ID:

R0024A

)

PLANT SPEC POINT DESC:

SG BLOWDOWN TREATMENT MontTOR

]-

GENERIC /COND DESC:

STM GEN 3 BLOWDOWN IUMD LEVEL ANALOG / DIGITAL:

A 1:

ENGR UNITS / DIG STATES: CPM i

l-ENGR UNITS CONVERSION:

N/A 4

j.

MINIMUM INSTR KANGEs.

10.0 1

. MAXIMUM INSTR RANGE:

.1000000.0-

- ZERO POINT

REFERENCE:

N/A j.

REFERENCE POINT-NOTES: N/A i

i PROC OR SENS:

S i

NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A I

SENSOR LOCATION.

OUTLET.OF THE STEAM GENERATOR BLOWDOWN HEADER 1

ALARM / TRIP SET POINTS:

N/A l

i NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A-1 l

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A-TEMPERATURE COMPENSATION i

FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG N/A t

UNIQUE SYSTEM DESC:

DRA-353-COMMON FOR SG-1,2,3,4 i

i i.

4 i

I' COOK. NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM l

DATA POINT LIBRARY-

~ PAGE.103 OF 112 1

REVISION'O t-r

- j 4

-]

i r

m....,.. _..

,,,.i.,,,

-v,

--... m.-.

-. -. -v -.. -

.,mm.m,

1 ~

I i

1:

DATE:

June 11, 1992 i

E

- REACTOR UNIT:

CK2 i

DATA FEEDER:

N/A j

'NRC ERDS PARAMETER:

SG BD RAD 4D 1

i POINT ID:

R0024A j

..dT SPEC POINT DESC:

SG BLOWDOWN TREATMENT MONITOR v

GENERIC /COND DESC:

STM GEN 4 BLOWDOWN RAD LEVEL 4

ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: CPM I

4 ENGR UNITS CONVERSION - N/A l

MINIMUM INSTR RANGE:

10,0

-t j

i MAXIMUM INSTR RANGE -

2000000.0

~

N/A ZERO POINT

REFERENCE:

i REFERENCE POINT NOTES: N/A I-i PROC OR SENS:

S NUMBER OF SENSORS:

1 I

i HOW PROCESSED:

N/A l

SENSOR LOCATION:

OUTLET OF THE STEAM GENERATOR BLOWDOWN HEADER l

ALARM / TRIP SET POINTSt. N/A t

l NI DETECTOR POWER SUPPLY CUT-OFF' POWER LEVEL -

N/A 1-l

'NI DETECTOR POWER SUPPLY:-

j' TURN-ON POWER LEVEL:

N/A INSTRUMENT FA! LURE MODE N/A i

j.

TEMPERATURE COMPENSATION FOR DP. TRANSMITTER:

N/A LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC:

DRA-353 COMMON FOR SG-1,2,3,4 4

i,.

1 J

\\

l COOK-NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM 4

DATA POINT LIBRARY

~

PAGE 104 OF 112 REVISION'O 4-3 i

l' n

4 rm.

.....m.,

,,.~.,.,m.__.,

..s.

,.m-w-.-.y--,%.3..-r-,

w.,._v.-.g...

,..,. ~

..... -~

~

.. - =..~...... - -.

4 4

3..

i

=

3 DATE:

June 11, 1992 j'

REACTOR-UNIT:

CK2 1

DATA FEEDER:

N/A NRC ERDS PARAMETER:

CNTMNT PRESS POINT ids.

U1000 I -

PLANT SPEC POINT DESC: CONTAINHENT P 1/2/3/4 AVG s

GENERIC /COND DESC CONTAINMENT PRESSURE ANALOG / DIGITAL:

A 1

j.

ENGR UNITS / DIG STATES: PSIG ENGR UNITS CONVERSION: N/A k

HINIMUM INSTR. RANGE:

-5.000 4

MAXIMUM INSTR RANGE:

12.000 ZERO POINT

REFERENCE:

N/A l

REFERENCE POINT NOTES: N/A l

PROC OR SENS:

P i

NUMBER OF SENSORS:

4 I

HOW PROCESSED:

AVERAGE SENSOR LOCATION:

-INSIDE CONTAINMENT I-ALARM / TRIP SET POINTS:

1.1 HIGH 2.9 HIGH-HIGH l

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A

+

i NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

.N/A LEVEL REFERENCE LEG N/A i-UNIQUE SYSTEM DESC:

PPP-300, PPP-301, PPP-302, PPP-303 i

l COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM j

DATA POINT LIBRARY PAGE 105 OF 112 REVISION O 1

(I i

.--,4,--,

.m.o+ - - -

.,m e nm n

t y

g I

DATE:

June 31, 1992-1-

)

REACTOR UNIT:

CK2 k

. DATA FEEDER:

N/A NRC ERDS PARAMETER:

_ CTMNT TEMP l--

i POINT ID:

U1609 I

PLANT SPEC POINT DESC:

MAXIMUM CONTAINMENT TEMPERATURE l

GENERIC /COND DESC:

CONTAINMENT TEMPERATURE f

ANALOG / DIGITAL:

A f

ENGR UNITS / DIG STATES:

DEG F ENGR UNITS CONVERSION:

N/A 3

{

MINIMUM INSTR RANGE:

0.00 MAXIMUM-INSTR RANGE:

300.00:

i' ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A 4

PROC OR SENS:

P j-NUMBER OF SENSORS:

- 15 f

HOW PROCESSED -

MAXIMUM SENSOR LOCATION:

INSIDE CONTAINMENT AT VARIOUS LOCATIONS l

ALARM / TRIP SET POINTS: - N/A i

l NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER-SUPPLY l1 TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE' COMPENSATION l

FOR DP TRANSMITTER:

N/A i

LEVEL REFERENCE LEG N/A i

-UNIQUE SYSTEM DESC '

ETR-102,JETR-112, ETR-126, ETR-122,"ETR-117, ETR-118, ETR-119, ETR-121,-ETR-113, ETR-127, ETR-136

}

1 r

i l

[.

COOK-NUCLEAR PLANT; _ EMERGENCY RESPONSE DATA'SYGTEM DATA POINT LIBRARY PAGE 106 OF 112-REVISION O l

1 i

I

.--m.

....a..

u.-

-.u.

.....,,, w

_ _. -..~

.-.m 4

/

9 i-:

', ~

DATE:

June 11, 1992 I

REACTOR UNIT:

CK2

]'

DATA FEEDER:

N/A i

.NRC ERDS PARAMETER:

H2 CONC POINT ID:

U1610 i

PLANT SPEC POINT DESC: AVERAGE CONTAINMENT H2 CONC 1

GENERIC /COND DESC:

CONTAINMENT HYDROGEN CONCENTRATION ANALOG / DIGITAL:

A i

l ENGR UNITS / DIG STATESt- %

~

ENGR UNITS CONVERSION: N/A

{

MINIMUM INSTR RANGE:

0.00 MAXIMUM INSTR RANGE:

30.00 ZERO POINT

REFERENCE:

N/A a

REFERENCE POINT NOTES: N/A i

i PROC OR SENS:

P NUMBER OF SENSORS:

2 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

INSIDE CONTAINMENT J

[

ALARM / TRIP SET POINTS: N/A

~

l-NI DETECTOR POWER SUPPLY 4

CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY 4

j-TURN-ON POWER LEVELt N/A l-INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION l

FOR DP TRANSMITTER:

N/A i-LEVEL REFERENCE LEG:

N/A l :-

-UNIQUE SYSTEM'DESC:

_H2-AH, H2-BH i

i~

{

1 i

k COOK NUCTEAR PLANT - EMERGPMOY RESPONSE DATA SYSTEM 5

DATA POINT LIBRARY PAGE 107 OF 112 I

REVISION O 1

l l'

~..

. ~ - ~ -.. -.

= - ~ - - -.

~ - -. -.

j-DATE:

June 11, 1992 i

REACTOR UNIT:

CK2

I.

DATA FEEDER:

N/A 3

i ;-

NRC ERDS PARAMETER:

BWST LEVEL-l L

POINT ID:

U1611 PLANT SPEC POINT DESC: AVERAGE RWST LEVEL GENERIC /COND DESC:

BORATED WATER STORAGE TANK LEVEL ANALOG / DIGITAL:

A j

ENGR UNITS / DIG STATES:

ENGR UNITS CONVERSION:

N/A i

l MINIMUM INSTR RANGE:

0.0 l

l!

MAXIMUM INSTR RANGE:

100.0 ZERO POINT

REFERENCE:

COMPLX REFERENCE POINT NOTES:

89% = 364,434 GALLONS PROC OR SENS:

P

}

NUMBER OF SENSORS:

2 e'

HOW PROCESSED '

AVERAGE

{

SENSOR LOCATION:

TAPS ON THE WALLS OF THE RWST-a ALARM / TRIP SET POINTS:

9P 3 HIGH 32.2 LOW' 9.1 LOW-LOW NI DETECTOR POWER. SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR ~ POWER SUPPLY TURN-ON~ POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

Y LEVEL REFERENCE LEG:

WET UNIQUE SYSTEM DESC:

ILS-950,.ILS-951 COOK-NUCLEAR PLANT ' - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 108 OF 112 REVISION O I

i 1

4 l-DATES.

June 11, 1992 REACTOR UNIT:

CK2 9

DATA FEEDER:

N/A NRC ERDS PARAMETER:

Wl,7 SPEED POINT ID:

UO804 PLANT SPEC POINT DESC: HIDAS WIND SPEED (30 M MAIN) a GENERIC /COND DESC:

WIND SPEED AT THE REACTOR SITE ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: MPH 2

ENGR UNITS CONVERSION: N/A 4

MINIMUM INSTR RANGE:

0.0 4

J MAXIMUM INSTR RANGE:

125.0 ZERO POINT

REFERENCE:

N/A i

J REFERENCE POINT NOTES: N/A PROC OR SENSs S

j NUMBER OF SENSORS:

1 HOW PROCESSED:

AVERAGE l

SENSOR LOCATION:

APPROXIMATELY 1 MILE ENE OF PLANT ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER-SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A f

TEMPERATURE COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESC:

EFR-402, AVERAGE OVER 15 MINUTES AND UPDATED EVERY 15 MINUTES

}

t i

l COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 109 OF 112 REVISION O i

9 i

?

... -., -, -. ~

.= -.

~...

.1 DATE:

June 11, 1992

{

REACTOR UNIT:

CK2 DATA' FEEDER:

N/A 1

NRC ERDS PARAMETER:

WIND DIR POINT ID:

UO803 PLANT SPEC POINT DESC: MIDAS WIND DIRECTION (10 M MAIN)

GENERIC /COND DESC:

WIND DIRECTION AT THE REACTOR SITE ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: DEGFR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

360.0 ZERO POINT REFERENCES.

N/A REFERENCE. POINT NOTES: N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

AVERAGE SENSOR LOCATION:

APPROXIMATELY 1 MILE ENE OF PLANT ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER. LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION-FOR.DP TRANSMITTER -

N/A LEVEL REFERENCE LEG:

N/A

. UNIQUE SYSTEM DESC EFR-412, AVERAGE _OVER 15 MINUTES AND UPDATED EVERY 15 MINUTES.

COOK NUCLEAR PLT.NT - EMERGENCY RESPONSE DATA' SYSTEM

-. DATA POINT LIBRARY PAGE 110 OF 112 REVISION O a

I DATE:

JL 14, 1992 L

REACTOR UNIT CK2

[

DATA FEEDER:

N/A i

NRC EPOS PARAMETER:

STAB CLASS

[

POINT ID:

L302 i

PLANT SPEC POINT DESC: MIDAS DELTA TEMP (MAIN)

GENERIC /COND DESC:

Aan STABILITY AT THE REACTOR SITE 7

ANALOG / DIGITAL:

A i

ENGR UNITS /DIO STATES:

DaG F/$0 M i

ENGR UNITS CONVERSION:

N/A

{

MINIMUM INSTR RANGE:

-10.0 MAXIMUM INSTR RANGE:

10.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

P.

l NUMBER OF SENSORN:

2 MOW PROCESSED:

SUBTRACTION SENSOR LOCATION:

APPROXIMATELY I MILE ENE OF PLANT ALARM / TRIP SET POINTS:- N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE. COMPENSATION FOR DP TRANSMITTER:

N/A LEVEL REFERENCE. LEG N/A UNIQUE SYSTEM DESC:

ETO-403, AVERAGE OVER 15 MINUTES AND U.QATED EVERY 15 MINUTES COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY.

-PAGE 111 OF 112' REVISION O

)

.. ~,. -......

. a.

i j

1 l

i f

?

f DATE:

Juno II, 1992 REACIOR UNIT:

CK2 j

DATA FEEDER:

N/A 1

1 NRC ERDS PARAMETER:

N/A J

r i

POINT ID:

K5502 1

l PLANT SPEC POINT DESC:

ERDS PLANT OR SIMULATED DATA i'

GENERIC /COND DESCs N/A i

ANALOG / DIGITAL:

D ENGR UNITS / DIG STATESs N/A i

ENGR UNITS CONVERSION:

N/A t

j MINIMUM TNSTR RANGE:

0.0 i

MAXIMUM INSTR RANGE:

1.0 1

j ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A i

PROC OR SENS:

N/A i

i NUMBER OF SENSORS:

N/A l

HOW PROCESSED:

N/A i

SENSOR Ls '. TION :

N/A l

ALARM / TRIP SET "OINTS:

N/A 1

i NI DETECTOR POWER SUPPLY i

CUT-OFF POWER LEVEL:

N/A i

i NI DETECTOR POWER SUPPLY

]

TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE N/A i

TEMPERATURE COMPENSATION FOR DP-TRANSMITTER:

N/A 1

LEVEL REFERENCE LEG N/A i

UNIQUE SYSTEM DESC:

0.0 MEANS REAL PLANT DATA 1.0 i4EANS SIMUALTED-PLANT DATA l

4 l

l

-COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEMJ DATA' POINT LIBAARY PhGE 112 OF 112 REVISION O 4

>