Change 1,Rev 2 to Procedure OP 2384, Engineered Safeguards Actuation Sys Operation
ML20101D065
Person / Time
Site: Millstone 
(OP-2384)
Issue date: 04/07/1983
From:
NORTHEAST NUCLEAR ENERGY CO.
To:
Shared Package
ML20101D053 List:
References
TAC-51701, NUDOCS 8412210287
Download: ML20101D065 (35)


Text

{{#Wiki_filter:._ =. M "*d" b Fars Appt ec/Dy 5t&ttipperintendeAt Effective Date r STATION PR0tE00tf 08 FORM CHANGE '[~ l A. 10ENT]FICATION (- @ One) FORN Mus ta //8 ume arv. A cNANct No. f 4 PROCEDURE]OR FORN 111LE 54l&/ 55 EO ' C/ V WY bC VJ L6srcle One) e / GP 1NITIATED BY !b s. g!!g!g ~ YL k cwc s i C. REASON FOR CHANGf 1 $g g, 0 I l'c? c.s gts &s W-scm&.a s,.14 wk. s lar~a Yu s /DA fft4-4 ca eY ty fles J uM Yo* r Z 2/oek) - w ( 0. NON-INTENT CHAN:t AUTHORIZAT10N (N/A for Intent Changes) T1111. 51cNATutt aAff Shif t 5utervisor fon dutv) E. REVIEWE0 Department Need i i ifnreviewed Saf stfon Eve' watten Documentatten teeutred: 151gnificant chang $AR)e in procedure method or scope as described in r [ ] TES [ i (If yes, docueent in PORC/$0RC netting slavies) ENv1RO WENTAL 1MPACT (Adverse environrental fepect) [ ] TES [ T WO (If yes, document in PORC/50RC meeting etnotes) F. Pott /404t' REC 0864tN05 APPROVAL (or confirmation of laterte change within 14 drys) PORCAQ$nt Neetfng Nsaker _.2-83-3(o 8. APPROVAL AND INPLfrfNTAff0N The change is bereby laplacanted and is effective this date, sacept for interte chan es whic were ispleeented and effective per the Author a tien of 9 above. Y/if N ktA 't 5ta luperintendeet/ Unit luperi ndent Date 1 5F 302 Rev. 5 8412210287 841204 '*"

  • I PDR ADOCK 05000336 P

PDR

8' PROCEDURE FOR RESTORING +24VDC POWER TO THE ESAS ACTUATION CABINET WHEN IN THE SHUTDOWN MODE WITH VALID PRZ. PRESS. AND S/G PRESS. TRIPS. ..( \\

1. REMOVE BOTH THE +15VDC POWER FUSES AT THE AFFECTED ACTUATION CABINET.

THIS ACTION WILL RESET THE TRIP LATCH CIRCUITRY. (WITH THE' EXCEPTION OF THE SIAS, CIAS, EBFAS AND MSI ACTUATION MODULES) f

2. RE-INSTALL THE +15VDC FUSES RIMOVED IN STEP 1.
3. AT THE AF'FECTED ACTUATION CABINET, PUSH THE EIGHT (8) " ACTUATION RESET" PUSH-BUTTONS. f e; SIAS, SRAS, EBFAS, AEAS, CSAS, MSI, UV AND CIAS.

s NOTE: AT THIS~ POINT ALL ACTUATION MODULES.SHOULD BE RESET WITH THE EXCEPTION OF THE SIAS, CIAS, EBFAS' AND MSI MODULES. CAUTION:THE IMPLdMENTATION OF STEP FOUR (4) WIL,L CAUSE THE FOLLOWING TO OCCUR;

1. EBFAS ACTUATION WILL OCCUR.
2. CTMT SAMPLE VLV. (RAD MONITORS) WILL SHUT.
3. ENGINEERED SAFEGUARDS ROOM VENTILATION WILL SHIFT.

( (INBOARDANDOUTBOARD)

4. AT THE AFFECTED ACTUATION CABINET, INSTALL THE +24VDC POWER " BLOCK" FUSE.
5. AT PANEL C01 RE-ESTABLISH THE SIAS AND MSI BLOCKS.
6. AT THE AFFECTED ACTUATION CABINET, PUSH AND HOLD IN THE " ACTUATION RESET" PUSH-BUTTONS
7. RE-INSTALL THE REMAINING +24VDC POWER FUSE.

i I

8. AT THIS POINT THE AFFECTED ACTUATION CABINET SHOULD BE RESTORED T

~ OPERATIONAL MODE WITH ALL BLOCK FUNCTIONS INITIATED. 'IF THIS i CONTACT THE UNIT 2 I&C DEPT. FOR RESOLUTION. i L D.W. CLARK U-2 I&C ENGINEER 3-19-82 s

E.J. Mroczka 12-28-81 Form Approved by Station Superintendent Effective Date f1 STATION PROCEDURE COVER SHEET A. IDENTIFICATION, Number OP 2384 Rev. 2 Title ENGINEERED SAFEGUARDS ACTUATION SYSTEM OPERATION Prepared By S. J. Baker B. REVIEW I have reviewed the above procedure and have found it to be satisfactory. TITLE SIGNATURE DATE ,d, a 247I5 DEPARTMENT HEAD i C. UNREVIEWED SAFETY QUESTION EVALUATION DOCUMENTATION REQUIRED: () (Significant change in procedure method or scope as described in FSAR) YES [ ] NO [M (If yes, document in PORC/SORC meeting minutes) ENVIRONMENTAL IMPACT (Adverse environmental impact) YES [ ] NO d (If yes, document in PORC/SORC meeting minutes) D. PORC/SGAC-APPROVAL PORC/60EG-Meeting Number 1-83-1l l E. APPROVAL AND IMPLEMENTATION The attached procedure is hereby approved, and effective on the date below: P 3b y ~ St(%2in/ Serv 6rfe7 Unit Superintendent Effective Date SF-301 Rev. 5 k c

'~ OP 2384 Page 1 Rev. 2

{

UNIT 2 ENGINEERED SAFEGUARDS ACTUATION SYSTEM OPERATION ~ Page No. Eff. Rev. 1 - 32 2 1 f i. 1 ~ i t

. t 2._, ? OP 2384 Pe,e 2 Rev. 2 + '(" 1. OBJECTIVE 1.1 The objective of this precedure is to provide instructions for the startup, shutdown, normal and casualty operation of the Engineered Safeguards Actuation System. f 2. LICENSE REQUIREMENTS 2.1 Technical Specifications: 3.3.2.1 3. FSAR REFERENCES 3.1 Chapter 6 3.2 Chapter 7, Section 7.3

3.3 Other

Logic Drawing 25203-28150, Sh. 1-4 4. PLANT OPERATING REQUIREMENTS 4.1 The system functions are implemented by means of redundant sensors, instrument loops, logic and actuation devices. -Independence is provided between redundant elements to preclude ( any interactions between channels during maintenance or in the event of channel malfunction. Redundant elements are electrically isolated from each other such that events affecting one element are not reflected in any other element. 4.2 The Engineered Safety Actuation System detects incident conditions and initiates the safety features systems which are designed to t localize, control, mitigate, and terminate such incidents. The Engineered Safety Features Actuation System is divided into four sensor channels (A, B, C, and D), two actuation channels, and two logic channels for sequentially loading the emergency l generators. 4.3 All process variables are transmitted as analog signals. Loss of voltage on the 4.16kV emergency bus is detected by potential transformers and bistables. 4.4 Four essential or vital power sources are provided for the ESAS. Two emergency diesel generators are provided to supply power to the actuated equipment of the protective systems in

(,

case of loss of offsite power. ..,4a-m- -,s e.4m--.- e- ,.e.+w +m m. m---

-~ OP 2384 Page 3 Rev. 2 b . 4. 5 If offsite power is available, the safeguards equipment starts directly. If offsite power is not available, load shedding and sequencing are required for sequential loading of the diesel generators. 4.6 Each actuation channel (1 or 2) of each of the following actuation signals can be initiated by'a pushbutton located on the main control board: SIAS, CSAS, CIAS, EBFAS, SRAS, MSI, and AEAS. Each pushbutton initiates all actuation groups of the associated signal within its respective actuation channel. 5. PREREQUISITES 5.1 120 VAC power is available through vital AC panels: VIAC-1 (VA 10) Circuit Breaker 14 VIAC-1 (VA 10) Circuit Breaker 18 VIAC-3 (VA 30) Circuit Breaker 10 I VIAC-2 (VA 20) Circuit Breaker 17 j VIAC-2 (VA 20) . Circuit Breaker 18 ( VIAC-4 (VA 40) Circuit Breaker 12 [- 5.2 Detectors and bistables must meet calibration requirements as I per Technical Specification requirements,.Section 4.3.2.1.1. l 6. PRECAUTIONS 6.1 Do not test more than one channel at a time. l 6.2 When shutting down, ensure Main Steam Isolation Actuation trips are blocked prior to decreasing steam generator pressure below 520 PSIA. 6.3 The manual pushbuttons on C01 are used only to manually initiate l safeguards actuation. 6.4 When cooling down and depressurizing the Reactor Coolant System, ensure the Pressurizer Pressure Channel trips are blocked (SIAS Block) prior to decreasing coolant pressure below 1620 PSIA. i 6.5 Do not test a parameter in which one channel is already tripped. LL 1 l

OP 2384 Page 4 Rev. 2 .( 6.6 If an ESAS actuation has occurred and the signal cannot be reset, all equipment shall remain in the actuated condition unless (1) personnel or equipment safety will be affected, (2) specific operating procedures allow or require the signal to be cverridden, or (3) the equipment is n,ot required for the mode. If the signal to any equipment is overridden, credit for operability shall not be taken and the requirements of the appropriate action statement met. Bypass (override) status of ESAS actuated components shall be determined per surveillance shift checks. 7. PROCEDURE 7.1 Power Application NOTE: This section should only be performed when the ESAS is initially de-energized. NOTE: Refer to section 7.9 or 7.10 for restoration of ESAS cabinets (sensors and actuation) following loss of a ( vital instrument AC Bus (VA-10, 20, 30, or 40) or a fault resulting in sensor cabinet trips, actuation module trips, blown -15V, -15V, or +24V fuses on the actuation cabinets. 7.1.1 Bypass each sensor cabinet's inputs before energizing the cabinets. 7.1.2 Supply 120 VAC to the ESAS sensor cabinets and the actuation cabinets: a) At VIAC-1 CLOSE Breaker 14 (VA 1014) b) At VIAC-1 CLOSE Breaker 18 (VA 1018) c) At VIAC-2 CLOSE Breaker 17 (VA 2017) d) At VIAC-2 CLOSE Breaker 18 (VA 2018) e) At VIAC-3 CLOSE ireaker 10 (VA 3010) f) At VIAC-4 CLOSE Breaker 12 (VA 4012) 7.1.3 Reset any bistable module trip lamps (red) that are lighted, by depressing lamp. k m

OP 2384 Page 5 + Rev. 2 (

7. 2 Switch Alignment NOTE:

For the following switch aligr.ments, each sensor channel is similar. Both actuation cabinets are similar to each other. Thus, switch alignment for only Channel A sensor cabin,et and one actuation cabinet will be listed. Exceptions will be listed separately. 7.2.1 Sensor Cabinets 7.2.1.1 Calibration - test drawer 7.2.1.1.1 Calibration Test Selector switch in OPERATE. a) Seve Operate / Test switches in OPERATE (Spring return to OPERATE). 7.2.1.1.2 Trip Test switch in OPERATE. 7.2.1.1.3 Test Current Voltmeter switch in OFF. ([' 7.2.1.2 Bistable modules 7.2.1.2.1 Trip lamp (red) - Push to reset lamp. 7.2.1.2.2 UV Test Pane! Selector switch in OPERATE. 7.2.2 Actuation Cabinets 7.2.2.1 Test Permissive switch, S-501 (601) in OPERATE. 7.2.2.2 Test Group switch, S-502 (602) in GROUP 1. 7.2.2.3 Actuation reset: Seven reset pushbuttons reset the actuation modules after they have been tripped and conditions have returned to normal. NOTE: Also housed in actuation cabinet 5 is the Auto Test Inserter (ATI). The ATI provides an automatic test capability for the L

OP 2384 Page 6 Rev. 2

(

ESAS. It generates.the dual, 2 millisec pulses which are routed to each channel bistable (in combinations) to simulate a-momentary fault trip for test - purposes. 7.3 Channel Bypass 7.3.1 When any of the below conditions exist, use the parameter bypass key (s) to place the affected parameter (s) in a 2/3 logic condition. 7.3.1.1 Surveillance of one channel 7.3.1.2 Channel malfunction or inoperability as required (see Technical Specifications) NOTE: Loss of vital AC power to either actuation cabinet will trip all the actuation modules associated with that cabinet. NOTE: A loss of vital AC power to one of the four sensor ( cabinets will result in a one out of four trip on both actuation cabinets even if all parameters on that cabinet are inhibited. 7.3.2 Observe the ESAS 2/3 Logic Alarm Annunciator at Panel C01 for the affected channel (s). 7.4 Manual Operation f NOTE: Manual initiation of any of the below safeguards functions can be accomplished by depressing the pushbuttons (covered) on the apron section of Panel C01. 7.4.1 Lift pushbutton cover. 7.4.2 Depress desired pushbutton. 7.4.3 Observe indications to ensure channel has been initiated. 7.4.4 Verify equipment response by observing blue lights on C01X. kY l e.+- .vu.w.. ,.w-- ..m.,y,,mww,_m .--,cm,w__ .,mr-esy,-m--,,.---,+p---ym<<-wr,.s-,w-.i-w.ww.e www% ,y

4 OP 2384 Page 7 Rev. 2 , 7. 5~ Manual Blocks 7.5.1 MSI Actuation Block 7.5.1.1 Observe the following conditions: 7.5.1.1.1 Any 3 out of 4 channels Steam Generator decreased to 600 PSIA. 7.5.1.1.2 SG Press Ch l'(Ch 2) Manual Block Permitted Annunciator at C01 Panel, Window A25 (or C25). 7.5.1.2 Depress MSI Channel 1 Block (or Ch 2) l pushbutton on Panel C01. i 7.5.1.3 Observe SG Ch 1 Lo Lo Press Manually Blocked (or Ch 2) annunciated at Panel C01, Window B25 (or D25). 7.5.2 Pressurizer Pressure SIAS Block i l 7.5.2.1 Observe the following conditions: 7.5.2.1.1 Any 3 out of 4 channels Pressurizer l ( Pressure decreased below 1750 PSIA. 7.5.2.1.2 Pzr Press SIAS Ch 1 (or Ch 2) Manual Block Permitted Annunciator at C01 Panel, Window A19 (or i C19). l 7.5.2.2 Depress SIAS Ch 1 Block (or Ch 2) pushbutton on C01. i 7.5.2.3 Observe SIAS Blocked Ch 1 (or Ch 2) Annunciator at C01 on Window B19 (or D19). 7.6 Safecuards Status Panel (C01X) 7.6.1 Test Pushbuttons: Channel 1, 2, and 5 - Depress Test l pushbutton to test indicator lamps. l NOTE: Blue lamps indicate actuation (Trip) condition and White lamps indicate a component which will not l l function as intended (Loss of Power). I L

.I - OP 2384 Page 8 Rev. 2 ..( , 7. 7 Auto Test Inserter (ATI) - Cabinet 5 NOTE: The ATI unit performs a recurring test sequencing operation which -is repeated every 27 seconds. It generates the dual 2 as pulses whicn are routed to each channel bistable (in combinations) to simulate a ~ momentary fault trip for test purposes. Each channel is tested end-to-end in a programmed sequence. All test results are routed back to the 6N91 module over reset lines. Each bistable test status is synchronously sampled during its test time by timing pulses. The test results are indicated locally by a panel ATI fault lamp. The testing sequence order is: a) SG A Press, SG B Press, UV-2A, UV-4A,' Area Exhaust Radiation, RWST Level, Pressurizer Pressure, Containment Pressure Hi and Containment Pressure Hi-H1; using two channels at a time: ( Channels A and B, A and C, A and D, B and C, B and D, C and D. b) Containment Radiation Ch A, Containment Raalation Ch 8, Containment Radiation Ch C, Containment Radiation Ch D. c) Sequence A, Sequence B. 7.7.1 Refer to SP 2619A for shift check of ATI operation. 7.8 Actuated Equipment Override l NOTE: Components which receive ESAS actuation signals are provided with control schemes to allow override of the actuation signal and positioning / operation of the component to a condition other than that called for by ESAS. NOTE: Certain of the ESAS actuated components receive dual actuation signals, and overriding the actuation of the component with one actuation signal present also prevents actuation by the other signal. The following components receiving dual actuation signals are of l this type:

h ~ OP 2384 .Page 9 Rev. 2 ? 'h Component-Actuation 2-MS-220A/HV-4246 - SG1 Blowdown Isolation CIAS-1 Closes RIS4262 Closes 2-MS-220B/HV-4248 - SG2 Blowdown' Isolation CIAS-2 Closes RIS4262 Closes 2-EB-60/HV-8143 - Fuel Handl. Area Vent EBFAS-1 Closes to Plenum AEAS-10 pens 2-EB-61/HV-8062 - Fuel Handl. Area Vent EBFAS-2 Closes to Plenum AEAS-20 pens 2-EB-55/HV-8654 - SJAE Discharge to Stack EBFAS-2 Closes AEAS-2 Closes ( 2-EB-56/HV-8695 - SJAE CTMT Leak Cleanup EBFAS-1 Closes AEAS-1 Closes i 2-EB-41/HV-8070 - EBFS A0 Damper EBFAS-20 pens AEAS-20 pens 2-EB-51/HV-8074 - EBFS A0 Damper EBFAS-10 pens AEAS-10 pens 2-EB-50/HV-8153 - EBFS M0 Damper EBFAS-10 pens AEAS-1 Closes 2-EB-40/HV-8063 - EBFS M0 Damper EBFAS-20 pens AEAS-2 Closes 2-EB-72/HV-8650 - CTNT Leak Cleanup EBFAS-1 Closes AEAS-1 Closes L

^ ' ~ ~ ~^ ~ ^ .~... .. ~.. OP 2384 Page 10 Rev. 2 ({ 2-EB-73/HV-8651 CTMT Leak Cleanup EBFAS-2 Closes AEAS-2 Closes EBFS Fan EBFAS-15 tarts F25A 4 AEAS-15 tarts EBFS Fan EBFAS-2 Starts F258 AEAS-2 Starts Control Room Filter Fan EBFAS-15 tarts F32A t AEAS-15 tarts l F32B Control Room Filter Fan EBFAS-25 tarts + AEAS-25 tarts NOTE: If EBFAS is initially present, AEAS has no effect. r-7.8.1 Refer to Precaution 6.6 prior to bypassing any equipment actuated by any ESAS. 7.8.2 For determining applicable action statements, refer to the note above for equipment with dual signals.

7. 9 Restoration of sensor cabinets 'D' and C (cabinets 3 and 4).

7.9.1 Following sensor cabinet alarms and other indications of a lost bus or bus transfer, verify AC power restored to the cabinet. 7.9.2 If power has not been restored verify breaker VA3010 or VA4012 (for cabinet 3 or 4) closed. 7.9.3 Upon restoration of AC power to the sensor cabinet, reset all bistables by depressing the bistable trip lamp.

7. a.
  • Verify all 1 out of 5 lamps on actuation cabinets 5 and 6 have r-*=c based on plant conditions.

(; -_.,_%w9_, ,,y-w__,y-w_____7_.ww9_,.m_g_9p,, _ _. .-,-g-.7,,. w y p.y9,9,9..n ._w,y_.. m,*,.mw.c_-,,..y-w ~%%, _,,,,.,%.,f-w.sw ay,

J. OP 2384 Page 11 Rev. 2 ( 7.9.5 If the previous steps do not resolve the sensor cabinet trips, bypass the chsanel inaccordance with Tech Specs and have the I&C Department investigate. 7.10 Restoration of sensor cabinets A and B (cabinets 1 and 2) and actuation cabinets 5 and 6. 7.10.1 Following sensor cabinet alarms and other indications of a lost bus or bus transfer, verify AC power restorad to the sensor and actuation cabinet. 7.10.2 If power has not been restored verify breakers VA1014 & VA101B are closed for sensor cabinet 1 and actuation cabinet 5 or breakers VA2017 and VA2018 are closed for sensor cabinet 2 and actuation cabinet 6. 7.10.3 Upon restoration of AC power to the sensor cabinet, a. reset all bistables by depressing the bistable trip lamp. 7.10.4 Verify all input parameters are indicating properly. 7.10.5 Check all 1 out of 5 lamps on actuation cabinet are l( extinguished. Some 1 out of 5 lamps may be on depending on plant conditions. This is particularly true of the CTMT radiation causing purge valve actuation. NOTE: Any pertibations on the 120 VAC bus cause pertibations on the +15V power in the actuation cabinet. This in turn will cause the ' crow bar' circuit to blow the 24 volt fuses. 7.10.6 Examine the actuation cabinet for blown fuses and/or trips. Attempt to reset any trips by depressing the i actuation signal reset buttons. 7.10.7 If the 24 volt fuses are blown remove them from the fuse holder. 7.10.8 Again attempt to reset any trip lamps on the actuation modules using the reset buttons. l k e _.-.-,-..---.,..-y,,,,,,,,,r_ ._w.,__,_--,_--.._-,._,,..,.,,,,._._.-.%...-..__r.,._, y.,- o,

4 h ^ OP 2384 Page 12 ~, Rev. 2 h 7.10.9 If actuation signal trips cannot be reset, remove the f +15 volt fuse, then re-insert this action should f clear all trip signals. If not, have I&C investigate the problem. 7.10.10.The 24 volt fuses may now be re-insert /raplaced without actuation. 8. ALARMS AND MALFUNCTIONS 8.1 ESAS UV Ch 1 Trip - C01 - C33 Initiatina Device Setpoint Bistable AM 527 85.5 VAC ACTION j Auto { a) Breaker 52-A302 Trip (RSST #1 Supply to Bus 24C) b) Breaker 52-A304 Trip (24A Bus Supply to Bus 24C) c) Load shed Pila (R8CCW) d) Load shed P41A (HPSI) ( e) Load shed PSA (Service Water) f) Load shed P43A (Containment Spray) l. g) Load shed L105 (Press. Prop. Htrs, Group 1) l h) Load shed P9A (Aux. Feed Pump) 1) Load shed LO46A (CEDM MG Set #1) j) DG Auto Start [ k) OKR 52-A305 Permissive (Bus 24C Supply to Bus 24E) h 1) Load shed P118 (R8CCW) ( m) Load shed P418 (HPSI) n) Load shed P58 (Service Water) l c) Breaker 52-A505 Trip (24F Bus Supply to 24E) Initial and Subsequent a) Monitor Status panel to ensure auto action occurs. ,I b) Refer to Emergency Procedure 2503 (LNP). 1 ( +-,-.e.w.,_,-,._,-.,_,-.,,-...---.,..-w.. .w....%m.mm... _..r..- _.,.--.--,.y- .m _.m_,---,..g,m.

l ~~' ~ ^ OP 2384 Page 13 Rev. 2 f. 8.2 ESAS UV Channel 2 Trip - C01 - D33 Initiating Device Setpoint Bistable AM 627 85.5 VAC ACTION Auto ~ a) Breaker 52-A410 Trip (24B Bus Supply.to 240) b) Breaker 52-A411 Trip (RSST #1 Supply to 240) c) Load shed P11C (RBCCW) d) Load shed P41C (HPSI) e) Load shed P42B (LPSI) m f) Load shed P5C (Service Water) g) Load shed P43B (Containment Spray) h) Load shed L106 (Press. Prop. Htrs, Group 2) i) Load shed P98 (Aux. Feed Pump) j) Load shed LO46B (CEDM MG Set #2) k) DG Auto Start 1) Breaker 52-A408 Permissive (24D Bus Supply to 24E) ( m) Load shed P11B (RBCCW) n) Load shed P418 (HPSI) o) Load shed P5B (Service Water) p) Breaker 52-A505 Trip (24F Bus Supply to 24E) Initial and Subsequent I a) Monitor indications to ensure auto action occurs. b) Refer to Emergency Procedure 2503. l 8.3 SIAS Actuation Signal Ch 1 Trip - Col - A34 Initiatina Device Setpoint Any one of SIAS bistables 2/4 Cont Press at 3.8 PSIG j 1A through 12A 2/4 Przr Press at 1620 PSIA ' ACTION Auto l Test Diesel Group Module # Sea. Equipment Function 'A AM 515 1 P14A Ctat Air Recirc Cooler.......... Start Half Speed 1A AM 515 1 P14C Ctat Air Recirc Cooler.......... Start Half Speed i I-l t

s my OP 2384 Page 14 3 Rev. 2 . ( 1A. AM 515 4 1 P5A Service Water Pump............... Start 1A AM 515 1 PSB Service Water Pump (5)........... Start 2A. ~ AM 514 1 P41A HPSI Pump....................... Start ' 2A AM 514 1 P41B HPSI Pump (5)................... Start i 2A AM 514 4 F112A Battery Room Vent Fan.......... Start 3A AM 516 2 P11A RBCCW Pump...................... Start 3A AM 516 2 P11B RBCCW Pump (5).................. Start 3A AM 516 2 P18A Charging Pump................... Start 3A AM 516 2 P18B Charging Purp................... Start 3A AM 516 2 1 Key Interlock (NP1881) 4A AM 517 3 P42A LPSI Pump....................... Start SA AM 518 4 Chiller Syst Valves (X169A).......... 0 pen SA-AM 518 4 F54A Vital sw/g Room Cooling Fan..... Start SA AM 518 4 P122A Vital sw/g Room Chilled Water Pump................................. Start 6A AM 519 2CH-506 Boric Acid Grav. Feed Valve..Open 6A AM 519 2CH-509 Volume Control Make-Up ( Va1ve............................... 0 pen 6A AM 519 2CH-512 Volume Control Make-Up Va1ve................................Close 7A AM 520 4 F15A Eng Sfgrd Re Air Recirc......... Start l: 8A AM 521 251-615 LPSI Valve.................. 0 pen 8A AM 521 251-625 LPSI Valve.................. 0 pen 8A AM 521 251-617 LPSI Valve.................. 0 pen 8A AM 521 251-627 HPSI Valve.................. 0 pen 8A AM 521 2SI-637 HPSI Valve.................. 0 pen 8A AM 521 2SI-647 HPSI Valve.................. 0 pen 9A 4 AM 522 2SI-618 SI Check Valve Leakage Cont..Close 9A AM 522 251-628 SI check Valve Leakage Cont..Close 10A AM 523 2-SW-81A RSCCW Ht Exch Valve........ 0 pen 10A AM 523 2-SW-818 RBCCW Ht Exch Valve........ 0 pen 10A AM 523 2-SW-3.2A TBCCW Nt Exch Valve........Close 10A AM 523 251-614 SI Tank outlet Valve........ 0 pen 10A AM 523 u 251-624 SI Tank outlet Valve.........open

(

L

k e OP 2384 Page 15 ~* Rev. 2 '( 10A. AM 523 2CH-515 Reactor Coolant Letdown Va1ve................................Close 10A 'AM 523 2CH-501 Volume Cont Tank Discharge Va1ve................................Close 11A AM 524 2-RB-68.1A ES Room RBCCW Air Cooler..Close - 11A AM 524 2-RB-28.3C Ctat Air Recirc Cool Outlet (C)................................. 0 pen 11A JM 524 2-R8-8.lA SFP Hx (A) RBCCW Outlet.....Close 11A AM 524 2-R8-28.3A Ctat Air Recirc Cool (A) 0utlet...............................Open 11A AM 524 DGH7A Diesel Gen (A)................. Start 12A AM 525 DG SIAS Start Annunciator (C-34) 2-CH-196.............................Close Initial and Subsequent Refer to Emergency Procedure 2506 and/or 2509. ( 8.4 SIAS Actuation Signal Ch 2 Trip - Col - B34 Initiatina Device Setpoint Any one of SIAS bistables 2/4 Cont Press at 3.8 PSIG 18 through 12B 2/4 Przr Press at 1620 PSIA ACTION Auto Test Diesel Group Module # Sea. Equipment Function IB AM 615 1 F148 Ctat Air Recirc Cooler.......... Start Half Speed IB AM 615 1 'F140 Ctat Air Recirc Cooler.......... Start Half Speed 1B AM 615 1 2CH-514 Boric Acid to Charging Line Va1ve............................... 0 pan 18 AM 615 1 P58 Charging Pump.................... Start 18 AM 615 1 PSC Charging Pump.................... Start 28 AM 614 1 P41B HPSI Pump....................... Start 28 AM 614 1 P41C HPSI Pump....................... Start 28 AM 614 4 Battery Room Vent Fan F1128.......... Start ([ 3B AM 616 2 P118 RBCCW Pump (B).................. Start

.a OP '384 Page 16 2

  • ^

Rev. 2 (- 3B AM 616 2 P11C RBCCW Pump (C).................. Start 3B AM 616 2 P188 Charging Pump (B)............... Start 3B AM 616 2 P18C Charging Pump (C)............... Start 3B AM 616 2 Key Interlock NP1882 48 AM 617 3 P42B LPSI Pump (B)................... Start '5B AM 618 4 Chiller System Valve (X169B).........Open SB AM 618 4 Chilled Water System Valves..........Open 5B AM 618 4 Vital sw/g Room Chilled Water Pump P1228................................ Start SB AM 618 4 Vital sw/g Room Cooling Fan F-548.... Start 6B AM 619 2CH-510 Boric Acid Recirc Valve......Close 6B AM 619 2CH-511 Boric Acid Recirc Valve......Close 7B AM 620 4 F158 Eng. Sfgrd Rm Air Recirc........ Start 88 AM 621 251-635 LPSI Valve.................. 0 pea 88 AM 621 251-645 LPSI Valve.................. 0 pen 88 AM 621 251-616 LPSI Valve.................. 0 pen 88 AM 621 2SI-626 HPSI Valve.................. 0 pen ( 88-AM 621 2SI-636 HPSI Valve.................. 0 pen i 88 AM 621 2SI-646 HPSI Valve.................. 0 pen 98 AM 622 2SI-638 SI Check Valve Leakage Cont..Close 98 AM 622 2SI-648 SI Check Valve Leakage Cont..Close l 99 AM E22 CEA Cooling Fan F138................. Start 10B AM 623 2-SW-8.1C RBCCW Ht Exch Valve........ 0 pen 10B AM 623 2-SW-8.1B RBCCW Ht Exch Valve........ 0 pen 108 AM 623 2-SW-3.2A TBCCW Ht Exch Valva........Close 10B AM 623 25I-634 SI Tank Outlet Valve........ 0 pen 10B AM 623 2SI-644 SI Tank Outlet Valve........ 0 pen 11B AM 624 2-RB-28.3B Ctat Air Recirc Cool Outlet (B)..................................Open llB AM 624 2-RB-210 Degasifier Effl Cool Letdown j-Shutoff..............................C1cse 11B AM 624 2-RB-28.30 Ctat Air Recirc Cool Outlet (D)..................................Open 7 l 118 .AM 624 2-RP.-68.1B ES Room RBCCW Air Cooler. 0 pen i( r i

I a O OP 2384 Page 17 Rev. 2 [

11B, AM 624 2-RB-8.1B SFP Hx (B) RBCCW Outlet....Close 11B AM 624 DG-H78 Diesel Gen H78................ Start 128 AM 625 2

P19A Boric Acid Pump................. Start 128 ~AM 625 2 P198 Boric Acid Pump................. Start F 142 Vital Swgr Rm Exhaust Fan Initial and Subsequent Refer to Emergency Procedure 2506 and/or 2509. 8.5 CSAS Act Sig Ch 1 Trip - C01 - C34 Initiatina Device Setpoint Either CSAS bistable 1A, 2A 2/4 Cont Press at 25.8 PSIG ACTION Auto Test Diesel Group Module # Sea. Equipment Function 1A AM 509 3 P43A Ctat Spray Pump................. Start-2A AM 510 3 2-CS-4.1A Ctat Spray Cont Valve......Open { u Initial and Subsequent Refer to Emergency Procedure 2506 and/or 2509. i 8.6 CSAS Act sig Ch 2. Trip - C01 - D34 Initiating Device Setpoint Either CSAS bistable 1B, 2B 2/4 Cont Press at 25.8 PSIG ACTION Auto Test Diesel Group Module # Sea. Equipment Function i 1B AM 609 3 P43B Ctat Spray Pump................. Start 28 AM 610 3 2-CS-4.18 Ctat Spray Control Valve...Open Initial and Subsequent Refer to Emergency Procedure 2506 and/or 2509. k. l -

e OP 2384 Page 18 Rev. 2 ( 8.7 CIAS Act Sig Ch 1 Trip - C01 - A35 Initiatina Device Setpoint Any one of CIAS B/S 1A 2/4 Cont Press at 3.8 PSIG through 6A 2/4 Przr Press at 1620 PSIA ACTION Auto Test Group Module # Equipment Function 1A AM 502 2-AC-8 Enc 1 Bldg Purge Outlet Damper........... 0 pen 1A AM 502 2-AC-47 Ctat Air Sample Valve...................Close 1A AM 502 F39A Ctat Radiation Monitoring Fan..............Stop 1A AM 502 2-AC-15 Ctat Air Sample Valve...................Close 2A AM 503 2-MS-220A Sta Gen #1 Blowdown Valve.............Close 2A AM 503 2-MS-191A Stm Gen #1 Sample Line Valve..........Close 3A AM 504 2-EB-99 H Purge Isolation Valve................Close 2 3A AM 504 2-EB-100 H Purge Isolation Valve...............Close 2 3A AM 504 2-ER-88 Ctat H M nitoring Sample Isolation.....Close 2 4A AM 505 2CH-505 RCP Controlled Bleedoff Isol Valve......Close { SA AM 506 2-LRR-43.2 PDT Pump Discharge Valve.............Close 5A AM 506 2-GR-11.2 Waste Gas Surge Tank Inlet Valve......Close 5A AM 506 2-SSP-16.2 CTNT Sump Isol Viv Outside CTMT......Close 5A AM 506 2-PMW-43C Quench Tank Make-up Valve.............Close 6A AM 507 2-AC-1 Ctat Clean-up Damper.....................Close 6A AM 507 2-RC-45 RC Sampling Isolation Valve.............Close Initial and Subsequent Refer to Emergency Procedure 2506 and/or 2509. 8.8 CIAS Act Sig Ch 2 Trip - Col - 835 Initiatina Device Setpoint Any one of CIAS B/S 1B 2/4 Cont Press at 3.8 PSIG through 68 2/4 Przr Press at 1620 PSIA ACTION Auto b - +- - <m---g y-,; g ec w. - ..yw-- .g e e-y---g-+- g -y i- --- --eea--

  • c-
  • ---wM- - - " - - - = ^----

OP 2384 Page 19 Rev. 2 ( Test Group Module # Equipment Function 18 AM 602 F23 Ctat Purge Supply Fan.....................Stop IB-AM 602 2-AC-11 Ctat & Enc Bldg Purge Out Damper......Open 18 AM 602 2-AC-12 Ctat Air Sample Valve.................Close 1B AM 602 F39B Ctat Radiation Monitoring Fan............ Stop 18 AM 602 2-AC-20 Ctat Air Sample Valve.................Close 2B AM 603 2-MS-220B Stm Gen #2 Blowdown Valve...........Close 2B AM 603 2-MS-151B Stm Gen #2 Sample Line Valve........Close 3B AM 604 2CH-516 Reactor Coolant Letdown Valve.........Close 3B AM 604 2-CH-089 Reg Ht Exch Disch to Letdown Hx......Close 3B AM 604 2CH-506 RCP Controlled Bleedoff Isol Valve....Open 4B AM 605 2-EB-92 H Purge Isolation Valve..............Close 2 48 AM 605 2-EB-91 H Purge Isolation Valve..............Close 2 4B AM 605 2-EB-59 Ctat H Monitoring Sample Isol Valve..Close 2 j 5B AM 606 2-LLR-61.1 PDT Sample Shutoff Valve...........Close SB AM 606 2-RC-003 Pzr Sta Sampling Valve...............Close -{ 5B AM 606 2-RC-002 Pzr Steam Sampling Valve.............Close SB AM 606 2-RC-001 RC Hot Leg Sagling Valve............Close 6B AM 607 2-LRR-43.1PDT Pump Discharge Valve............Close j 6B AM 607 2-GR-11.1 Waste Gas Surge Tk Inlet Valve......Close 6B AM 607 2-SSP-16.1 Ctat Drain Sump Isolation Valve....Close 6B AM 607 2-SI-312 N to SI Tanks Shutoff Vs1ve.........Close 2 Initial and Subsequent Refer to Emergency Procedure 2506/2509. 8.9 SRAS Act Sig Ch 1 Trip - Col - C35 Initiatino Device Setpoint Either SRAS Bistable 1A or 2A 2/4 RWST levels at 5.0% l ACTION Auto (In association with other actions, i.e., SIAS, CSAS) -5**-T 4 w+ e -*-y sv-s =r--e e mw+,ee-=ww-=*,+te-e-wme, -,urme, mwe e-m. . e w -w -wrew -www w ew emww,-=e-e-s, e mm e-y,-*----w-- -v-

-~ 1 l OP 2384 Page 20 Rev. 2 ( Test Group Module # Equipment Function 1A AM 511 2-RB-13.1A Shutdown Ht Ex A.................. 0 pen 1A AM 511 2-CS-16.1A Ctat Sump Recirc Stop Valve........Open 1A AM 511 2SI-659 SI Sump Recirc Hdr Shutof f............Close 2A AM 612 P42A LPSI Pump...........'.....................Stop Initial and Subsequent Refer to Emergency Procedure 2506/2509. 8.10 SRAS Act Sig Ch 2 Trip - C01 - D35 Initiatina Device Setpoint Either SRAS Bistable 1B or 2B 2/4 RWST Levels at 5% ACTION Auto (In association with other actions, i.e., SIAS, CSAS) Test Group Mod:le # Equipment Function 1B AM 611 2-CS-16.1B Ctat Sump Recirc Stop Valve.... Open 1B AM 611 2SI-660 SI Sump Recirc Hdr Shutof f............Close 18 AM 611 2-RB-13.1B Shutdown Ht Ex (B) C.W............ 0 pen 28 AM 612 P42B LPSI Pump................................Stop Initial and Subsequent Refer to Emergency Procedure 2506/2509. 8.11 MSI Act. Sig Ch 1 Trip - C01 - A36 Initiatina Device Setpoint MSI Bistable 1A 2/4 Steam Gen. Pressure Ch 5 0 520 PSIA ACTION Auto . Test Group Module # Equipment Function lA AM 532 2-MS-64A Sta Gen #1 Isol Valve................ Close lA AM 532 2-MS-64B Sta Gen #2 Isol Valve................ Close 1A AM 532 HSA S.G.F.P.T.................................Stop (L-

OP 2384 Page 21 Rev. 2 ( 1A, AM 526 2-MS-64A Stm Gen #1 Isol Valve................ Close 1A AM 526 2-FW-51A Sta Gen #1 F.W. Reg Valve............ Close 1A AM 526 2-FW-5A Stm Gen #1 F.W. Isol Valve............ Close J 1A AM 526 2-MS-265A Main Stm Leg Low Pt. Drain..........Close Initial and Subsequent Refer to Emergency Procedure 2506/2509. 8.12 MSI Act. Sig Ch 2 Trip - C01 - B36 Initistina Device Setpoint MSI Bistable 18 2/4 Steam Gen. Pressure Ch 5 9 520 PSIA ACTION Auto Test Group Module # Equipment Function 1B AM 632 2-MS-64A Stm Gen #1 Isolation Valve...........Close 1B AM 632 2-MS-64B Stm Gen #2 Isolation Valve...........Close 1B AM 632 H SB S. G. F. P. T................................. S top { 18 AM 626 2-MS-65B Stm Gen #2 Isol Valve Bypass.........Close 18 AM 626 2-FW-5B Stm Gen #2 F.W. Isol Valve............ Close 1D AM 626 2-FW-51B Stm Gen #2 F.W. Reg Valve............Close 1B AM 626 2-MS-266A Main Stm Leg Low Pt Drain...........Close l Initial and Subsequent Refer to Emergency Procedure 2506/2509. 8.13 EBFAS Act Sig Ch 1 Trip - C01 - A37 Initiating Device Setpoint EBFAS Bistable 1A 2/4 Cont Press Channels at 3.8 PSIG I 2/4 Przr Press Channels at 1620 PSIA ACTION Auto l l r--- p-w -e y-, ,r-- %-,---w, ,--,-wy-- ~-,-- --,r --v--a-o--,e + + - - - - w-----m- + - - - -,---e w

l OP 2384 Page 22 Rev. 2 (~ Test Diesel Group Module # Sea. Equipment Function 1A AM 508 4 F32A Control Rm Filter Fan and Dampers.............................. Start 1A AM 508 3 F25A Encl Bldg Filtration Fan........ Start 1A AM 508 2-HV-107 ES Room Air Supply Valve....Close 1A AM 508 2-HV-116 ES Room Air Supply Valve....Close 1A AM 508 2-EB-51 Ctat H O Monitoring Sample 2 Iso Va1ve............................Open 1A AM 508 2-EB-56 Steam Jet Air Injector Mov...Close 1A AM 508 2-EB-60 Fuel Handling Area Vent to P1en.................................Close 1A AM 508 2-EB-72 Ctat Clean-up Damper......... Close Initial and Subsequent Refer to Emergency Procedure 2506/2509. 8.14 EBFAS Act Signal Ch 2 Trip - C01 - B37 Initiating Device Setpoint EBFAS Bistable 1B ?/4 Cont Press Channels at 3.8 PSIG 2/4 Przr Press Channels at 1620 PSIA ACTION Auto Test Diesel Group Module # Sea. Equipment Function 1B AM 608 4 F32B Control Rm Filter Fan & Dampers.............................. Start 18 AM 608 3 F25B Enc 1 Bldg Filtration Fan........ Start 18 AM 608 2-HV-106 ES Room Air Supply Valve....Close 1B AM 608 2-HV-117 ES Room Air Supply Valve....Close 1B AM 608 2-EB-40 Enc 1 Bldg Plenus Isol Damp...Open 1B AM 608 2-EB-41 Enc 1 Bldg Vent Suct Isol Damp.................................Open 1B AM 608 2-EB-55 Stm Jet Air Inject. Nov. to P1enum...............................Close

l OP 2384 Page 23 Rev. 2 1B; AM 608 2-EB-61 Fuel Handling Area Vent......Close 18 AM 608 2-EB-73 Ctat Clean-up Damper......... Close Initial and Subsequent Refer to Emergency Procedure 2506/2509. 8.15 AEAS Act Signal Ch 1 Trip - Col - 037 Initiating Device Setpoint-AEAS Bistable 1A 2/4 Fuel Handling Area Rad Hi ACTION -Auto Test Group Module # Eguipment Function 1A AM 513 Fuel Handling Sys Discharge Damp...............Close 1A AM 513 Fuel Handling Area Vent to Plenum............. 0 pen 1A AM.513 Ctat H O Monitoring Sep1 Iso Valve.............Close 2 1A AM 513 Ctat H O Monitoring Sep1 Iso Valve............ 0 pen 2 ( 1A AM 513 F25A Enc 1 Bldg Filtration Fan.................. Start 1A AM 513 Steam Jet Air Injector Mov.....................C1ose 1A. AM 513 F20 Fuel Handling Area H&V Fan................. Close 1A AM 513 Ctat Clean-up Damper........................... Cl ose 1A AM 513 F32A Control Rm Filter Fan and Damper.......... Start Initial and Subsequent Refer to Emergency Procedure 2506/2509. 8.16 AEAS Act Sig Ch 2 Trip - Col - D37 Initiatina Device Setpoint AEAS Bistable 1B 2/4 Fuel Handling Area Rad Hi ACTION Auto Test Groco Module # Equipment Function 1B 'AM 613 Spent Fuel Isol Damper........................C1ose 1B AM 613 Fuel Handling Area Vent to Damp.............. 0 pen t w a ,_.....,_-...-..,____.v. ,-,.c.,_,n_ ,v._,s., ,,,,,w ,,,__y.,.....,.,-,,w,-,,. ,._wym,.., mmm.

9 OP 2384 Page 24 Rev. 2 f 1B AM 613' Encl-Bldg Plenum Isol Damp................... 0 pen 1B AM 613 Enc 1 Bldg Suct Isol Damp..................... 0 pen 1B AM 613 F25B Enc 1 Bldg Filtration Fan................. Start 1B AM 613 Steam Jet Ai r Injection Mov................... C1ose 1B AM 613 Fuel Handling Damper..........................Close ~ 1B AM 613 Ctat Clean-up Damper..........................Close 1B AM 613 F32B Control Room Filter Fan.................. Start Initial and Subsequent Refer to Emergency Procedure 2506/2509. 8.17 Pressurizer Ch 1 Lo Lo Pressure SIAS Manually Blocked - C01 - B19 Pressurizer Ch 2 Lo Lo Pressure SIAS Manually Blocked - C01 - D19 Initiatina Device Setpoint SIAS Block Bistable 6N92(502) 3/4 Przr Press Channels 1750 PSIA SIAS Block Bistable 6N92(602) 3/4 Przr Press Channels 1750 PSIA ACTION ( Auto I a) Inhibits SIAS Actuation from Low Pressurizer Pressure. NOTE: Automatically removed of 2/4 Pressurizer Pressure Channels increase to 1730 + 15 PSIA. Initial None Subsequent l None 8.18 SG Ch 1 Lo Lo Pressure Manually Blocked - C01 - B25 SG Ch 2 Lo Lo Pressure Manually Blocked - C01 - B25 Initiating Device Setpoint Sta Gen Block Bistable 6N92(501) 3/4 SG Press Channels 600 PSIA l Sta Gen Block Bistable,6N92(601) 3/4 SG Press Channels 600 PSIA l ACTION Auto l a) Inhibits MSI Actuation. k

~

.u.

t OP 2384 Page 25 Rev. 2 ( NOTE: Automatically removed of 2/4 SG Pressure Channels increase to 580 + 15 PSIA. Initial None Subsequent None 8.19 Sequence 1 Operating - C01 - A39 Sequence 2 Operating - C01 - B39 Initiating Device Setpoint 6N93 - SEQ 501 SIAS (1 of 6) contacts open UV contact open 6N93 - SEQ 601 Remote breaker contacts open Remote reset ACTION Auto a) Accident with Loss of Normal Power (LNP): i) Actuation modules are tripped in acccrdance with the type of accident. ( ii) Sequencer operates through complete cycle. b) LNP without an Accident Condition: 1) For Seq 501: only actuation modules for SIAS 1, SIAS 3, and SIAS 5 are tripped. ii) Sequencer operates through compirce cycle. iii) For Seq 601: only actuation modules for SIAS 1, SIAS 3, SIAS 5, and SIAS 12 are tripped. iiii) Sequencer operates t:. cough complete cycle. c) LNP without an accident, fo;10wed by a subsequent SIAS during initial sequencing: 1) Same as (b) above until SIAS occurs. ii) SIAS causes sequencer to reset to TIME ZERO. iii) Sequence then repeats through its complete cycle picking up the additional SIAS modules to control the accident. Initial and Subsequent Refer to Emergency Procedure 2502, 2506. (

e OP 2384 Page 26 Rev. 2 ( 8.20 ESAS' Auto Test System Failure - C01 - A41 Initiatina Device Setpoint 6N91 - AT501 Auto Test Failure ACTION s Auto None Initial and Subsequent Immediately notify I&C Supervisor. 8.21 ESAS Component Under Test Failure - C01 - 841 Initiatina Device Setpoint 6N91 - AT501 Component Failed Auto Test ACTION Auto None Initial and Subsequent a) Determine which parameter and channel has failed. . _l(( 1) Lamp on steady for failed point. t

11) Lamp fails to light for failed point.

b) Immediately notify I&C Supervisor. 8.22 CTM Rad Act Signal Ch 1 Trip - C01 - C36 CTM Rad Act Signal Ch 2 Trip - C01 - D36 Initiatina Device Setpoint AM 501, AM 601 1/4 Ctat Rad CIAS - Hi Rad i ACTION Auto Purge valves close. Initial and Subsequent Refer to Emergency Procedure 2501. 8.23 Pressurizer Pressure Lo Block "A" C01 A-18 Pressurizer Pressure Lo Block "B" Col B-18 Pressurizer Pressure Lo Block "C" C01 C-18 i e n---rcr~-n4-- ,.w-mswn-,----w---

OP 2384 Page 27 Rev. 2 ( Pressurizer Pressure Lo Block "D" C01 0-11 Initiatino Device Setr oint Pressurizer Pressure Block Bistable BA107 1750 PSIA Pressurizer Pressure Block Bistable BA207 1750 PSIA Pressurizer Pressure Block Bistable BA307 1750 PSIA Pressurizer Pressure Block Bistable BA407 1750 PSIA ACTION Auto None Initial a) Manually block the respective channels using the pushbuttons on C01. b) If on 3 out of 4 coin.idences, the block permissive for either channel fails to annunciate, or manual blocking cannot be accomplished, maintain pressurizer pressure greater that 1635 PSIA and contact the I&C Supervisor immediately. (. Subsequent None 8.24 Pressurizer Pressure Ch 1 SIAS Manual Block Permitted C01 A-19 Pressurizer Pressure Ch 2 SIAS Manual Block Permitted C01 C-19 Initiatino Device Setpoint SIAS 3/4 Block Matrix 6N92 (502) 3/4 1750 PSIA SIAS 3/4 Block Matrix 6N92 (602) 3/4 1750 PSIA ACTION Auto j None Initial a) See Section 8.23. ~ NOTE: 2 out of 4 pressurizer pressure detectors, increasing above the blocking setpoint, will automatically remove the manual block. Subsequent ( None , - = - -.,..,-.,,,-.m u. -,-e., o.m,,,,%__ ,y.., .,-,.9 -.,c_,. .y..,

s_ o 4 OP 2384 Page 28 Rev. 2 ([~ 8.25 Pressurizer Pressure Lo Lo "A" C01 A-20 Pressurizer Pressure Lo Lo "B" C01 B-20 Pressurizer Pressure Lo Lo "C" C01 C-20 Pressurizer Pressure Lo Lo "D" C01 D-20 Initiating Device Setpoint Pressurizer Pressure Bistable BA106 1620 PSIA Pressurizer Pressure Bistable BA206 1620 PSIA Pressurizer Pressure Bistable BA306 1620 PSIA Pressurizer Pressure Bistable BA406 1620 PSIA ACTION Auto SIAS Not Blocked: 1. SIAS generated on 2/4 coincidence. SIAS Manually Blocked: None One Alarm Only: None Initial SIAS Generated: ([ 1. Carry out actions set forth in Emergency Procedure 2506, Loss of Coolant. SIAS Manually Blocked: None One Alarm Only: 1. Monitor pressurizer pressure on C03. If alarm is not j valid, place the keylock bypass for that sensor in inhibit. Subsequent One Alarm Only: 1. Notify I&C Supervisor to investigate and repair the sensor channel. 8.26 CTM Pressure Hi "A" C01 A-21 CTM Pressure Hi "B" C01 B-21 CTM Pressure Hi "C" C01 C-21 l CTM Pressure Hi "D" C01 0-21 l 1. (1 n

4 4 -y 9 OP 2384 Page 29 o Rev. 2 (_ Initiatino Device Setpoint CTM Press SIAS/CIAS Bistable BA101 3.8 PSIG CTM Press SIAS/CIAS Bistable BA201 3.8 PSIG CTM Press SIAS/CIAS Bistable BA301 3.8 PSIG CTM Press SIAS/CIAS Bistable BA401 3.8 PSIG ACTION Auto '2/4 Coincidence: 1. SIAS/CIAS generated. One Alarm Only: None Initial 2/4 Coincidence: 1. Carry out actions set forth in Emergency Procedure 2506, Loss of Coolant. One Alarm Only: 1. Monitor containment pressure on C01. If alarm is not valid, place the keylock bypass for that sensor in inhibit. ( Subsequent One Alarm Only: 1. Notify I&C Supervisor to investigate and repair the sensor r-channel. l-8.27 CTM Pressure Hi Hi "A" C01 A-22 CTM Pressure Hi Hi "B" C01 B CTM P-' essure Hi Hi "C" C01 C-22 CTM Pressure Hi Hi "D" C01 D-22 l Initiatina Device Setpoint CTM Press CSAS Bistable BA102 25.8 PSIG l~ CTM Press CSAS Bistable BA202 25.8 PSIG l CTM Press CSAS Bistable BA302 25.8 PSIG CTM Press CSAS Bistable BA402 25.8 PSIG (c I ~ t

-o 4 i OP 2384 Page 30 a o~ Rev. 2 {' -ACTION Auto 2/4 Coincidence: 1. CSAS generated. One Alarm Only: None ^ Initial 2/4 Coincidence: 1. Carry out actions. set forth in Emergency Procedure 2506, Loss of Coolant. One Alarm Only: 1. Monitor containment pressure on C01. If alarm is not valid, place the keylock bypass for that sensor in inhibit. Subsequent .One Alarm Only: 1. Notify I&C Supervisor to investigate and repair the sensor . channel. ( 8.28 Pressurizer Lo Lo Press SIAS 2/3 Logic C01 A-31 Containment Hi Press SIAS/CIAS 2/3 Logic C01 B-31 Containment Hi Hi Press CSAS 2/3 Logic C01 C-31 SG 1 Lo Lo Press MSI 2/3 Logic C01 A-32 RWST Lo Lo Level SRAS 2/3 Logic C01 B-32 i-Radiation Hi AEAS 2/3 Logic C01 C-32 ESAS UV Ch 1 2/3 Logic C01 A-33 ESAS UV Ch 2 2/3 Logic C01 B-33 Initiatina Oevice Setpoint Any of the four actuation signal key-NA lock bypasses. in the INHIBIT position. ACTION Auto a) Accident signal actuation shifts to 2 out of 3 logic. Initial and Subsequent a) Ensure steps are taken to correct any sensor abnormality and return the accident signal actuation to 2 out of 4 ( logic. L

O e OP 2384 Page 31-j Rev. 2 . ( 8.29 ESAS Panel Rear Access Door Open COI C-41 Initiating Device Setpoint Any of 8 microswitches on ESAS NA panels rear doors ACTION Auto None Initial a) Determine cause for opening any of the ESAS panels' rear doors. Subsequent a) Close all doors and clear alarm when possible. 8.30 ESAS UV 1 A Trip Bus 24C C01 A-43 ESAS UV 1 B Trip Bus 24C C01 B-43 ESAS UV 1 C Trip Bus 24C C01 C-43 ESAS UV 1 D Trip Bus 24C C01 D-43 l, Initiatino Device Setpoint UV 1 Bistable Ball 2 85.5 VAC t UV 1 Bistable BA212 85.5 VAC UV 1 Bistable BA312 85.5 VAC UV 1 Bistable BA412 85.5 VAC ACTION Auto One Alarm Only: None 2/4 Coincidence: 1. Load shed 24C and start DG H7A. Initial One Alarm Only: 1. Monitor parameters on C08. If alarm is not valid, place the keylock bypass switch for that sensor in inhibit. 2/4 Coincidence: 1. Refer to Emergency Procedure 2503 (LNP). , _ _, -. -. - _ _ - - -, - - _,.., ~ _,,_.7 ,.,._.o- -.-,.._-_,,m. .,, _.. ~ _.., -..

u -

3 . OP 2384 Paga 32 Rev. 2

h Subsequent One Alarm Only

1.. Notify I&C Supervisor.to investigate and repair the sensor j channel. 8.31 ESAS UV 2A Trip Bus 24D C01 A-44 ESAS UV 26 Trip Bus 24D C01 B-44 ESAS UV 2C Trip Bus 240 C01 C-44 ESAS UV 2D' Trip Bus 24D C01 D, Initiating Device Setpoint UV 2 Bistable BA113 85.5 VAC i UV 2 Bistable BA213 85.5 VAC UV 2 Bistable BA313 85.5 VAC 1' UV 2 Bistable BA413 85.5 VAC ACTION Auto One Alarm Only: ' None ! ( 2/4 Coincidence: 1. Load shed 243 and start DG H78. ~ -Initial One Alarm Only: 1. Monitor parameters on C08. If alarm is not valid, place the keylock bypass switch for that sensor in inhibit. 2/4 Coincidence: l 1. Refer to Emergency Procedure 2503 (LNP). [ Subsequent One Alarm Only: 1. Notify I&C Supervisor to investigate.and repair the sensor channel. l SJB:jic a y.nyy e -. _ m _.--,,, - -- -_ .q., -._,g.-w-- -. c .m m}}