U

,i

.w s

g GPU Nuclear Corporation Uhgg7 Post Office Box 388 Route 9 South Forked River,New Jersey 08731-0388 609 971-4000 Writer's Direct Dial Number:

October 18, 1984 Dr. Thomas E. Murley, Administrator Region I U.S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, PA 19406

Dear Dr. Murley:

Subject:

Oyster Creek Nuclear Generating Station Docket No. 50-219 License No. DPR-16 Operability of Radioactive Gaseous Effluents Monitoring System (RAGEMS)

Although the new RAGEMS stack monitoring system will be inctalled prior to plant restart, it will not be fully operational. Startup testing performed on RAGEMS has revealed that the system cannot be used for continuous monitoring because of software problems.

Until RAGEMS can be made completely avaliable, GPUN intends to utilize the existing monitoring system for Technical Specification compliance. The RAGEMS stack monitoring system will be employed in the unlikely event of an emergency that requires adherence to NUREG 0737 guidelines.

This will be accomplished as follows:

1.

The RAGEMS stack monitoring system will be placed into service when the existing stack monitor reads > 106 CPS or at the discretion of the Emergency Director. The applTcable Emergency Plan Procedure will be changed to reflect this.

2.

The RAGEMS stack monitoring system will begin monitoring gaseous l

emissions upon realigning two valves in the stack RAGEMS building.

The total time required to perfonn this manipulation will not exceed two minutes following entry into the building. A change to the applicable 400 series procedure will provide these details.

GPUN estimates that operation in this mode should not exceed six (6) months provided that no additional software problems are encountered during remaining startup testing. We are making every effort to place RAGEMS in a fully operable status as quickly as possible.

8412120371 841018 PDR ADOCK 05000219 F

PDR GPU Nuclear Corporation is a subsidiary of the General Public Utilities Corporation

..e e..

. . W. Darroll G. Eis:nhut, Director U.S. Nuclear Regulatory Comission Page 2 If you have any questions or coments, please contact Mr. Drew G. Holland, Oyster Creek Licensing Manager at (609)971-4643.

Very truly yours, a

ter. Fiedler Vice President and Director Oyster Creek PBF/ dam cc: Mr. Walter A. Paulson, Acting Chief Division of Licensing Operating Reactors Branch No. 5 U.S. Nuclear Regulatory Comission Washington, DC 20555 NRC Resident Inspector Oyster Creek Nuclear Generating Station Forked River, NJ 08731 i

.,.