Amend 59 to License NPF-6,revising Tech Spec Table 3.3-11 Re Fire Detection Instrumentation,Allowing Replacement of Heat Detector in Emergency Diesel Generator Rooms
ML20100J772
Person / Time
Site: Arkansas Nuclear 
(NPF-06-A-059, NPF-6-A-59)
Issue date: 11/23/1984
From: John Miller
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20100J773 List:
References
NUDOCS 8412100443
Download: ML20100J772 (5)


Text

.-

/ p snua yk UNITED STATES 7

g NUCLEAR REGULATORY COMMISSION j

WASHINGTON. D. C. 20555

%...../

ARKANSAS POWER & LIGHT COMPANY DOCKET N0. 50-368 ARKANSAS NUCLEAR ONE, UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 59 License No. NPF-6 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment by Arkansas Power and Light Company (the licensee) dated January 5,1982 complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and-safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-6 is hereby amended to read as follows:

x hh0 P

=

. Technical-Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 59, are hereby incorporated in the license. The 'icensee shall operate the facility in accordance with the Technical Specifications, except where otherwise stated in specific license conditions.

3.

This. license amendment is effective as of its date of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION

~M w 1

James R. Miller, Chief Operating Reactors Branch No. 3 Division of Licensing

Attachment:

Changes to the Technical Specifications Date of Issuance:

Novenber 23, 1984

s.

r.-

TABLE 3.3-11 FIRE DETECTION INSTRUMENTS INSTRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE HEAT SM0KE 1.

Containment North Penetration Area-Upper 2/ Area 2/ Area North Penetration-Area-Lower 2/ Area 2/ Area South Penetration Area-Upper 2/ Area 2/ Area South Penetration Area-Lower 2/ Area 2/ Area 2.

Cable Spreading Protective Wire 4

3.

Switchgear Room Room 2100 - Elev. 372 2

Room 2101 - Elev. 372 2

4.

Remote Shutdown Panels 1

5.

Emergency Diesel Generator Rooms Room 2093 - Elev. 369 2

2 Room 2094 - Elev. 369 2

2 6.

Diesel Fuel Storage Vaults 1/ Vault 7.

Penetration Rooms North Penetration Area-Upper 2/ Room

-North Penetration Area-Lower 2/Poom South Penetration Area-Upper 2/ Room South Penetration Area-Lower 2/ Room ARKANSAS - UNIT 2 3/4 3-44 Amendment No. //, 59 2

?%

4 ATTACHMENT TO LICENSE AMENDMENT NO. 59 FACILITY OPERATING LICENSE NO. NPF-6 DOCKET NO. 50-368

- Replace the following page o the Appendix "A" Technical Specifications with i

the enclosed page. The rev. :d page is identified by Amendment number and contains vertical lines indiv ting the area of change.

Remove Insert 3/4 3-44 3/4 3-44 I

1 -

e-i I

L TABLE 3.3-11 FIRE DETECTION INSTRUMENTS INSTRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE HEAT SM0KE 1.

Containment North Penetration Area-Upper 2/ Area 2/ Area North Penetration Area Lower 2/ Area 2/ Area South Penetration Area-Upper 2/ Area 2/ Area South Penetration Area-Lower 2/ Area 2/ Area 2.

Cable Spreading Protective Wire 4

3.

Switchgear Room Room 2100 - Elev. 372 2

Room 2101 - Elev. 372 2

4.

Remote Shutdown Panels 1

5.

Emergency Diesel Generator Rooms Room 2093 - Elev. 369 2(flame) 2 Room 2094 - Elev. 369 -

2(flame) 2 6.

Diesel Fuel Storage Vaults 1/ Vault 7.

Penetration Rooms 2/ Room North Penetration Area-Upper North Penetration Area-Lower 2/ Room South Penetration Area-Upper 2/ Room South Penetration Area-Lower 2/ Room

[

ARKANSAS - UNIT 2 3/4 3-44 Amendment No. //,59 i