Text
-
'O CONTAINMENT SYSTEMS CONTAINMENT VENTILATION SYSTEM LIMITING CONDITION FOR OPERATION 3.6.1.6 The containment purge supply and exhaust isolation valves shall be l
closed and handswitch keys removed.'
I APPLICABILITY:
MODES 1, 2, 3 and 4.
ACTION:
With one or more containment purge supply or exhaust-isolation valve (s) not--
closed with the handswitch keys removed, place the valve (s) in the closed position with handswitch' key (s) removed within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within-the following 30 i
hours.
i SURVEILLANCE REOUIREMENTS i
- 4. 6.1. 6 The containment purge supply and exhaust isolation valves shall be determined closed at least once per 31 days.
I F
l i
)
ARKANSAS - UNIT 2 3/4 6-9a 8503200423 850315
~
PDR ADOCK 05000368 p